GMV5 Max
From Technical Support Wiki
This is the support page for the GMV5 Max outdoor unit for Gree GMV VRF air conditioners.
GMV5 Max | |
Voltage | 380V-415V |
---|---|
Cooling Capacities (kW) | 78.5-90.0 |
Heat Pump? | Yes |
Model Numbers
- GMV-786W/A-M
- GMV-900W/A-M
Specifications
Model | GMV-786W/A-M | GMV-900W/A-M | ||
---|---|---|---|---|
Capacity Range | HP | 28 | 32 | |
Capacity | Cooling | kW | 78.5 | 90.0 |
Heating | kW | 87.5 | 100.0 | |
EER | W/W | 3.22 | 3.25 | |
COP | W/W | 3.74 | 3.82 | |
Power Supply | V/Ph/Hz | 380-415V/3/50 | ||
Max Circuit/Fuse Current | A | 57.2/63 | 71.5/80 | |
Power Consumption | Cooling | kW | 24.4 | 27.7 |
Heating | kW | 23.4 | 26.2 | |
Maximum Drive IDU NO | unit | 46 | 53 | |
Refrigerant Charge Volume | kg | 18.9 | 24.0 | |
Sound Pressure Level | dB(A) | 65 | 65 | |
Connecting Pipe Diameter | Liquid | mm | ⌀19.05 | ⌀19.05 |
Gas | mm | ⌀31.8 | ⌀31.8 | |
Dimension (WxDxH) | Outline | mm | 2200x880x1675 | |
Package | mm | 2267x952x1867 | ||
Net Weight/Gross Weight | kg | 557/592 | 600/635 | |
Loading Quantity | 40' GP | set | 12 | 12 |
40' HQ | set | 12 | 12 |