| GMV5 Max | |
| Voltage | 380V-415V |
|---|---|
| Cooling Capacities (kW) | 78.5-90.0 |
| Heat Pump? | Yes |
Model Numbers
- GMV-786W/A-M
- GMV-900W/A-M
Specifications
| Model | GMV-786W/A-M | GMV-900W/A-M | ||
|---|---|---|---|---|
| Capacity Range | HP | 28 | 32 | |
| Capacity | Cooling | kW | 78.5 | 90.0 |
| Heating | kW | 87.5 | 100.0 | |
| EER | W/W | 3.22 | 3.25 | |
| COP | W/W | 3.74 | 3.82 | |
| Power Supply | V/Ph/Hz | 380-415V/3/50 | ||
| Max Circuit/Fuse Current | A | 57.2/63 | 71.5/80 | |
| Power Consumption | Cooling | kW | 24.4 | 27.7 |
| Heating | kW | 23.4 | 26.2 | |
| Maximum Drive IDU NO | unit | 46 | 53 | |
| Refrigerant Charge Volume | kg | 18.9 | 24.0 | |
| Sound Pressure Level | dB(A) | 65 | 65 | |
| Connecting Pipe Diameter | Liquid | mm | ⌀19.05 | ⌀19.05 |
| Gas | mm | ⌀31.8 | ⌀31.8 | |
| Dimension (WxDxH) | Outline | mm | 2200x880x1675 | |
| Package | mm | 2267x952x1867 | ||
| Net Weight/Gross Weight | kg | 557/592 | 600/635 | |
| Loading Quantity | 40' GP | set | 12 | 12 |
| 40' HQ | set | 12 | 12 | |