MHI KXZ ODU2
From Technical Support Wiki
This is the support page for the Micro Model Heat Pump outdoor units for MHI VRF air conditioners.
| Micro Model Heat Pump Systems (FDC) | |
| Voltage | 220V-380V |
|---|---|
| Capacities (kW) | 22.4-33.5 |
| Heat Pump? | Yes |
Model Numbers
- FDC224KXE6M
- FDC280KXE6M
- FDC335KXE6M
- FDC224KXE6G
- FDC280KXE6G
- FDC335KXE6G
Specifications
| Item | Unit | FDC224KXE6M | FDC280KXE6M | FDC335KXE6M | FDC224KXE6G | FDC280KXE6G | FDC335KXE6G | |||
|---|---|---|---|---|---|---|---|---|---|---|
| Nominal Horse Power | 8HP | 10HP | 12HP | 8HP | 10HP | 12HP | ||||
| Power Source | 3 Phase-3wire 220V, 60Hz / 3 Phase-4wire 220V, 60Hz | 3 Phase 380V, 60Hz | ||||||||
| Starting Current | A | 5 | 6 | 5 | ||||||
| Max Current | A | 33 | 35 | 36 | 20 | 20 | 23 | |||
| Nominal Capacity | Cooling | kW | 22.4 | 28.0 | 33.5 | 22.4 | 28.0 | 33.5 | ||
| Heating | 25.0 | 31.5 | 37.5 | 25.0 | 31.5 | 37.5 | ||||
| Electrical Characteristics | Power Consumption | Cooling | kW | 5.85 | 8.57 | 9.82 | 5.60 | 8.09 | 9.82 | |
| Heating | 6.38 | 8.70 | 10.12 | 6.03 | 8.21 | 10.12 | ||||
| Exterior Dimensions | HxWxD | mm | 1675x1080x480 | |||||||
| Net Weight | kg | 212 | 215 | 218 | ||||||
| Sound Pressure Level | Cooling/Heating | dB(A) | 58/58 | 59/60 | 61/61 | 58/58 | 59/60 | 61/61 | ||
| Refrigerant | Type/GWP | R410A/2088 | ||||||||
| Charge | kg/TCO2Eq | 11.5/24.012 | ||||||||
| Refrigerant Piping Size | Liquid Line | mm (in) | ⌀9.52 (3/8") | ⌀12.7 (1/2") | ⌀9.52 (3/8") | ⌀12.7 (1/2") | ||||
| Gas Line | ⌀19.05 (3/4") | ⌀22.22 (7/8") | ⌀25.4 (1") [⌀28.58 (1 1/8")] | ⌀19.05 (3/4") | ⌀22.22 (7/8") | ⌀25.4 (1") [⌀28.58 (1 1/8")] | ||||
| Capacity Connection | % | 50~150 | ||||||||
| Number of Connectable Indoor Units | 22 | 24 | 24 | 22 | 24 | 24 | ||||