MHI KXZ ODU2
From Technical Support Wiki
This is the support page for the Micro Model Heat Pump outdoor units for MHI VRF air conditioners.
Micro Model Heat Pump Systems (FDC) | |
Voltage | 220V-380V |
---|---|
Capacities (kW) | 22.4-33.5 |
Heat Pump? | Yes |
Model Numbers
- FDC224KXE6M
- FDC280KXE6M
- FDC335KXE6M
- FDC224KXE6G
- FDC280KXE6G
- FDC335KXE6G
Specifications
Item | Unit | FDC224KXE6M | FDC280KXE6M | FDC335KXE6M | FDC224KXE6G | FDC280KXE6G | FDC335KXE6G | |||
---|---|---|---|---|---|---|---|---|---|---|
Nominal Horse Power | 8HP | 10HP | 12HP | 8HP | 10HP | 12HP | ||||
Power Source | 3 Phase-3wire 220V, 60Hz / 3 Phase-4wire 220V, 60Hz | 3 Phase 380V, 60Hz | ||||||||
Starting Current | A | 5 | 6 | 5 | ||||||
Max Current | A | 33 | 35 | 36 | 20 | 20 | 23 | |||
Nominal Capacity | Cooling | kW | 22.4 | 28.0 | 33.5 | 22.4 | 28.0 | 33.5 | ||
Heating | 25.0 | 31.5 | 37.5 | 25.0 | 31.5 | 37.5 | ||||
Electrical Characteristics | Power Consumption | Cooling | kW | 5.85 | 8.57 | 9.82 | 5.60 | 8.09 | 9.82 | |
Heating | 6.38 | 8.70 | 10.12 | 6.03 | 8.21 | 10.12 | ||||
Exterior Dimensions | HxWxD | mm | 1675x1080x480 | |||||||
Net Weight | kg | 212 | 215 | 218 | ||||||
Sound Pressure Level | Cooling/Heating | dB(A) | 58/58 | 59/60 | 61/61 | 58/58 | 59/60 | 61/61 | ||
Refrigerant | Type/GWP | R410A/2088 | ||||||||
Charge | kg/TCO2Eq | 11.5/24.012 | ||||||||
Refrigerant Piping Size | Liquid Line | mm (in) | ⌀9.52 (3/8") | ⌀12.7 (1/2") | ⌀9.52 (3/8") | ⌀12.7 (1/2") | ||||
Gas Line | ⌀19.05 (3/4") | ⌀22.22 (7/8") | ⌀25.4 (1") [⌀28.58 (1 1/8")] | ⌀19.05 (3/4") | ⌀22.22 (7/8") | ⌀25.4 (1") [⌀28.58 (1 1/8")] | ||||
Capacity Connection | % | 50~150 | ||||||||
Number of Connectable Indoor Units | 22 | 24 | 24 | 22 | 24 | 24 |