MHI KXZ ODU1
From Technical Support Wiki
This is the support page for the Micro Model Heat Pump outdoor units for MHI VRF air conditioners.
| Micro Model Heat Pump Systems (FDC) | |
| Voltage | 220V-380V |
|---|---|
| Capacities (kW) | 11.2-15.5 |
| Heat Pump? | Yes |
Model Numbers
- FDC112KXEN6
- FDC140KXEN6
- FDC155KXEN6
- FDC112KXES6
- FDC140KXES6
- FDC155KXES6
Specifications
| Item | Unit | FDC112KXEN6 | FDC140KXEN6 | FDC155KXEN6 | FDC112KXES6 | FDC140KXES6 | FDC155KXES6 | |||
|---|---|---|---|---|---|---|---|---|---|---|
| Nominal Horse Power | 4HP | 5HP | 6HP | 4HP | 5HP | 6HP | ||||
| Power Source | 1 Phase 220V, 60Hz | 3 Phase 380V, 60Hz | ||||||||
| Starting Current | A | 5 | ||||||||
| Max Current | A | 23 | 23.3 | 13.5 | ||||||
| Nominal Capacity | Cooling | kW | 11.2 | 14.0 | 15.5 | 11.2 | 14.0 | 15.5 | ||
| Heating | 12.5 | 16.0 | 16.3 | 12.5 | 16.0 | 16.3 | ||||
| Electrical Characteristics | Power Consumption | Cooling | kW | 2.80 | 4.17 | 4.71 | 2.80 | 4.17 | 4.71 | |
| Heating | 2.89 | 4.31 | 4.38 | 2.89 | 4.31 | 4.38 | ||||
| Exterior Dimensions | HxWxD | mm | 845x970x370 | |||||||
| Net Weight | kg | 85 | 87 | |||||||
| Sound Pressure Level | Cooling/Heating | dB(A) | 52/54 | 53/57 | 53/57 | 52/54 | 53/57 | 53/57 | ||
| Refrigerant | Type/GWP | R410A/2088 | ||||||||
| Charge | kg/TCO2Eq | 5.0 / 10.44 | ||||||||
| Refrigerant Piping Size | Liquid Line | mm (in) | ⌀9.52 (3/8") | |||||||
| Gas Line | ⌀15.88 (5/8") | |||||||||
| Capacity Connection | % | 80~150 | ||||||||
| Number of Connectable Indoor Units | 6 | 8 | 8 | 6 | 8 | 8 | ||||