MHI KXZ ODU1
From Technical Support Wiki
This is the support page for the Micro Model Heat Pump outdoor units for MHI VRF air conditioners.
Micro Model Heat Pump Systems (FDC) | |
Voltage | 220V-380V |
---|---|
Capacities (kW) | 11.2-15.5 |
Heat Pump? | Yes |
Model Numbers
- FDC112KXEN6
- FDC140KXEN6
- FDC155KXEN6
- FDC112KXES6
- FDC140KXES6
- FDC155KXES6
Specifications
Item | Unit | FDC112KXEN6 | FDC140KXEN6 | FDC155KXEN6 | FDC112KXES6 | FDC140KXES6 | FDC155KXES6 | |||
---|---|---|---|---|---|---|---|---|---|---|
Nominal Horse Power | 4HP | 5HP | 6HP | 4HP | 5HP | 6HP | ||||
Power Source | 1 Phase 220V, 60Hz | 3 Phase 380V, 60Hz | ||||||||
Starting Current | A | 5 | ||||||||
Max Current | A | 23 | 23.3 | 13.5 | ||||||
Nominal Capacity | Cooling | kW | 11.2 | 14.0 | 15.5 | 11.2 | 14.0 | 15.5 | ||
Heating | 12.5 | 16.0 | 16.3 | 12.5 | 16.0 | 16.3 | ||||
Electrical Characteristics | Power Consumption | Cooling | kW | 2.80 | 4.17 | 4.71 | 2.80 | 4.17 | 4.71 | |
Heating | 2.89 | 4.31 | 4.38 | 2.89 | 4.31 | 4.38 | ||||
Exterior Dimensions | HxWxD | mm | 845x970x370 | |||||||
Net Weight | kg | 85 | 87 | |||||||
Sound Pressure Level | Cooling/Heating | dB(A) | 52/54 | 53/57 | 53/57 | 52/54 | 53/57 | 53/57 | ||
Refrigerant | Type/GWP | R410A/2088 | ||||||||
Charge | kg/TCO2Eq | 5.0 / 10.44 | ||||||||
Refrigerant Piping Size | Liquid Line | mm (in) | ⌀9.52 (3/8") | |||||||
Gas Line | ⌀15.88 (5/8") | |||||||||
Capacity Connection | % | 80~150 | ||||||||
Number of Connectable Indoor Units | 6 | 8 | 8 | 6 | 8 | 8 |