Serene Plus Series Error Codes

From Technical Support Wiki
Revision as of 15:25, 15 January 2026 by ACINT (talk | contribs)
Jump to: navigation, search
Code Reason Remark
E0 IDU & ODU communication failure. Check wiring between indoor and outdoor unit.
E1 IDU room temperature sensor failure. Check IDU room temperature sensor and IDU PCB.
E2 IDU coil temperature sensor failure. Check IDU coil tempeature sensor and IDU PCB.
E3 ODU coil temperature sensor failure. Check ODU coil temperature sensor and ODU PCB.
E4 AC cooling system abnormal. Check for refrigerant leakage, 2-way or 3-way valve blockage, etc.
E5 IDU/ODU mismatch failure. IDU and ODU model number mismatch.
E6 IDU PG fan motor / DC fan motor abnormality. Check fan motor, fan blade and PCB.
E7 ODU ambient temperature sensor failure. Check ODU ambient temperature sensor and ODU PCB.
E8 ODU discharge temperature sensor failure. Check ODU discharge temperature sensor and ODU PCB.
E9 IPM / Compressor driving control abnormal. Check ODU PCB and compressor.
EA ODU current test circuit failure. Check ODU PCB.
Eb Communication abnormal between IDU PCB and IDU display board. Check display board and IDU PCB.
EE ODU EEPROM failure. Check ODU PCB or re-power AC unit.
EF ODU DC fan motor failure. Check ODU fan motor or ODU PCB.
EU ODU voltage test circuit abnormal. Check ODU PCB.
P0 IPM module protection Check ODU PCB.
P1 Over / under voltage protection. Check ODU PCB and power supply.