Specification Table of the Heat Pump TD Prime ducted units.

Outdoor Model ATDCI4H4G24 ATDCI4H4G36 ATDCI4H4G48 ATDCI4H4G60
Outdoor Power Supply V/Ph/Hz 208-203V/1Ph/60Hz 208-203V/1Ph/60Hz 208-203V/1Ph/60Hz 208-203V/1Ph/60Hz
Cooling Capacity Btu/h 24000 34500 47000 56000
W 7033 10110 13774 16411
EER Btu/Wh 11.6 11.6 11.6 10.8
SEER Btu/Wh 17.5 17.5 17.5 17.5
Heating Capacity Btu/h 24000 34000 46500 55000
W 7033 10110 13627 16118
COP Btu/Wh 13.0 11.9 12.9 11.5
HSPF Btu/Wh 9.5 9.0 9.5 9.5
Min. Circuit Ampacity (IU/OU) A 3.5/17.7 5.1/24.2 7.5/31.9 7.5/36.5
Max Fuse/Breaker (IU/OU) A 15/30 15/40 15/50 15/60
Cooling Operation Range °F 64~118 64~118 64~118 64~118
°C 18~47 18~47 18~47 18~47
Cooling Operation Range °F 5~109 5~109 5~109 5~109
°C -15~42 -15~42 -15~42 -15~42
Compressor Type GMCC Twin-rotary DC Mitsubishi Twin-rotary DC
Outdoor Dimension Unit (WxHxD) inch 29x25x29 29x25x29 29x33x29 29x33x29
Packaging (WxHxD) inch 30x26x30 30x26x30 30x35x30 30x35x30
Indoor Model ATDEM4H4G24 ATDEM4H4G36 ATDEM4H4G48 ATDEM4H4G60
Cooling Capacity Btu/h 24000 34500 47000 56000
SEER 17.5 17.5 17.5 17.5
Heating Capacity Btu/h 24000 34000 46500 55000
HSPF 9.5 9.0 9.5 9.5
Indoor Max Current A 0.91 1.35 2.39 2.43
Indoor Air Flow CFM 780 1300 1500 1750
ESP Pa 25 37 50 50
Indoor Dimension Unit (WxHxD) inch 20x46x22 20x46x22 22x53x24 22x53x24
Packaging (WxHxD) inch 23x48x26 23x48x26 26x55x28 26x55x28