Fault Code
|
Fault Description
|
Possible Reason for Fault
|
Potential Fixes
|
1
|
Outdoor Ambient Temperature Sensor Fault
|
- The outdoor ambient temperature sensor connection is loose
- The outdoor ambient temperature sensor has failed
- The sampling circuit has failed
|
- Reconnect the outdoor ambient temperature sensor
- Replace the outdoor ambient temperature sensor
- Replace the outdoor board
|
2
|
Outdoor Coil Temperature Sensor Fault
|
- The outdoor coil temperature sensor connection is loose
- The outdoor coil temperature sensor has failed
- The sampling circuit has failed
|
- Reconnect the outdoor coil temperature sensor
- Replace the outdoor coil temperature sensor
- Replace the outdoor board
|
3
|
The Unit Over-Current Turn Off Fault
|
- Control board current sampling circuit has failed
- The current is too high because the supply voltage is too low
- The compressor is blocked
- Overload in heating mode
- Overload in cooling mode
|
- Replace the control board
- Replace the compressor
|
4
|
EEprom Data Error
|
- EE components have failed
- EE components control circuit failed
- EE components have been inserted incorrectly
|
- Replace the EE components
- Replace the outdoor control board
- Reassemble the EE components
|
5
|
Cooling Freezing
Protection (the indoor
coil temperature is too
low) or Heating
Overload (indoor coil
temperature is too
high)
|
- The indoor unit isn't blowing air normally
- The room temperature is too low in cooling mode or the room temperature is too high in heating
- Air filter is dirty
- The duct resistance is too high to result in low air flow
- The setting fan speed is too low
- The indoor unit is not standard installed, air inlet is too near with air outlet
|