Malfunction Information Table

Name of Malfunction Display of indoor unit State of the lamps on the outdoor unit PCB
Error Code Yellow Red Green Reasons
Compressor running (normal) blink 1 time Part of normal operation
Automatic defrosting (normal) H1 blink 2 times Part of normal operation
Anti-freezing protection E2 blink 3 times Refrigerant leakage / indoor unit airflow blocked up / filter duty
Stop for IPM module protection (over current) H5 blink 4 times IPM model over current / outdoor unit air flow blocked up
Stop for over current protection E5 blink 5 times Outdoor unit over current / ambient temperature is abominable
Overload protection H4 blink 6 times Ambient temperature is abominable / heat exchanger is blocked up
Stop for exhaust protection E4 blink 7 times low refrigerant / capillary blocked up / ambient temperature is abominable
Stop for compressor overload protection H3 blink 8 times Compressor shell overheat / low refrigerant / capillary blocked up
Stop for overpower protection L9 blink 9 times Ambient temperature is abominable
Stop for IPM module protection (overheat) H5 blink 10 times IPM module overheat / outdoor unit airflow blocked up
Stop for EEPROM read-write function EE blink 11 times The EEPROM on the outdoor PCB mainboard cannot read or write