MHI VRF FDUT

From Technical Support Wiki
Revision as of 14:31, 5 November 2018 by ACINT (talk | contribs)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to: navigation, search

This is the support page for the Thin Duct Connected Low Static Pressure indoor unit (FDUT) for MHI VRF air conditioners.

Mitsubishi Heavy Industries VRF
Thin Duct Connected Low Static Pressure (FDUT)
MHI-FDUT-IDU.png
Voltage 220V
Capacities (kW) 1.5-7.1
Heat Pump? Yes

Model Numbers

  • FDUT15KXE6F-E
  • FDUT22KXE6F-E
  • FDUT28KXE6F-E
  • FDUT36KXE6F-E
  • FDUT45KXE6F-E
  • FDUT56KXE6F-E
  • FDUT71KXE6F-E

Specifications

Item Unit FDUT15KXE6F-E FDUT22KXE6F-E FDUT28KXE6F-E FDUT36KXE6F-E FDUT45KXE6F-E FDUT56KXE6F-E FDUT71KXE6F-E
Nominal Cooling Capacity kW 1.5 2.2 2.8 3.6 4.5 5.6 7.1
Nominal Cooling Capacity kW 1.7 2.5 3.2 4.0 5.0 6.0 8.0
Power Source 1 Phase 220V, 60Hz
Power Consumption Cooling kW 0.06 0.07 0.09 0.08
Heating 0.06 0.08 0.09 0.07
Sound Power Level dB(A) 52 57 58 59
Sound Pressure Level (1) dB(A) Hi: 28 Me: 26 Lo: 22 Hi: 28 Me: 26 Lo: 22 Hi: 33 Me: 30 Lo: 26 Hi: 34 Me: 32 Lo: 28 Hi: 35 Me: 33 Lo: 30 Hi: 35 Me: 31 Lo: 28
Sound Pressure Level (2) dB(A) Hi: 32 Me: 29 Lo: 25 Hi: 32 Me: 29 Lo: 26 Hi: 37 Me: 34 Lo: 28 Hi: 36 Me: 33 Lo: 27 Hi: 38 Me: 33 Lo: 29 Hi: 41 Me: 37 Lo: 32
Exterior Dimensions H x W x D mm 200x750x500 200x950x500 220x1150x565
Net Weight kg 21 22 25| 31
Air Flow m3/min Hi: 6 Me: 5 Lo: 4 Hi: 7.5 Me: 6 Lo: 5 Hi: 8.5 Me: 7 Lo: 5.5 Hi: 11.5 Me: 9 Lo: 7 Hi: 12.5 Me: 9 Lo: 7.2 Hi: 16 Me: 13 Lo: 9.5
External Static Pressure Pa Standard: 10 Max: 35 Standard: 10 Max: 50
Outside Air Intake Possible from Return Duct
Air Filter Filter kit: UM-FL1EF/UM-FL2EF/UM-FL3EF (option)
Remote Control (option) wired: RC-EX3, RC-E5, RCH-E3 wireless: RCN-KIT4-E2
Refrigerant Piping Size mm (in) Liquid Line: ⌀6.35 (1/4") Gas Line: ⌀9.52 (3/8") Liquid Line: ⌀6.35 (1/4") Gas Line: ⌀12.7 (1/2") Liquid Line: ⌀9.52 (3/8") Gas Line: ⌀15.88 (5/8")