This is the support page for the 4 way ceiling cassette indoor unit (FDT) for MHI VRF air conditioners.

Mitsubishi Heavy Industries VRF
4 way Ceiling Cassette (FDT)
MHI-FDT-IDU.png
Voltage 220V
Capacities (kW) 2.8-16.0
Heat Pump? Yes

Model Numbers

  • FDT28KXZE1
  • FDT36KXZE1
  • FDT45KXZE1
  • FDT56KXZE1
  • FDT71KXZE1
  • FDT90KXZE1
  • FDT112KXZE1
  • FDT140KXZE1
  • FDT160KXZE1

Specifications

Item Unit FDT28KXZE1 FDT36KXZE1 FDT45KXZE1 FDT56KXZE1 FDT71KXZE1 FDT90KXZE1 FDT112KXZE1 FDT140KXZE1 FDT160KXZE1
Nominal Cooling Capacity kW 2.8 3.6 4.5 5.6 7.1 9.0 11.2 14.0 16.0
Nominal Heating Capacity kW 3.2 4.0 5.0 6.3 8.0 10.0 12.5 16.0 18.0
Power Source 1 Phase 220v, 60Hz
Power Consumption Cooling kW 0.02 0.03 0.04 0.08 0.13 0.14
Heating 0.02 0.03 0.04 0.08 0.13 0.14
Sound Power Level dB(A) 49 50 55 62 65 66
Sound Pressure Level dB(A) Hi: 33 Me: 30 Lo: 28 Hi: 33 Me: 31 Lo: 29 Hi: 35 Me: 32 Lo: 28 Hi: 38 Me: 36 Lo: 31 Hi: 39 Me: 37 Lo: 31 Hi: 42 Me: 39 Lo: 32 Hi: 42 Me: 39 Lo: 33
Exterior Dimensions mm Unit: 236x840x840 Panel: 35x950x950 Unit: 298x840x840 Panel: 35x950x950
Net Weight kg Unit: 20 Standard Panel: 5 Unit: 21.5 Standard Panel: 5 Unit: 25 Standard Panel: 5
Air Flow m3/min Hi: 14 Me: 12 Lo: 10 Hi: 15 Me: 13 Lo: 10 Hi: 16 Me: 13 Lo: 11 Hi: 17 Me: 14 Lo: 12 Hi: 25 Me: 22 Lo: 15 Hi: 26 Me: 23 Lo: 17 Hi: 28 Me: 25 Lo: 18 Hi: 29 Me: 26 Lo: 19
Outside air intake Possible
Panel T-PSA-5AW-E, T-PSAE-5AW-E
Air Filter, Qty Pocket Plastic net x 1 (Washable)
Remote Control (option) wired: RC-EX3, RC-E5, RCH-E3 wireless: RCN-T-5AW-E2
Refrigerant Piping Size mm (in) Liquid Line: ⌀6.35 (1/4") Gas Line: ⌀9.52 (3/8") Liquid Line: ⌀6.35 (1/4") Gas Line: ⌀12.7 (1/2") Liquid Line: ⌀9.52 (3/8") Gas Line: ⌀15.88 (5/8")