Blue Series Troubleshooting (18K & 24K)
From Technical Support Wiki
NO. | Malfunction Name | Display Method of Indoor Unit | Display Method of Outdoor Unit | A/C Status | Possible Causes | ||||||
Dual-8 Code Display | Indicator Display | Indicator Display | |||||||||
Operation Indicator | Cooling Indicator | Heating Indicator | D40/D5 | D41/D6 | D42/D16 | D43/D30 | |||||
1 | System High Pressure Protection | E1 | Off 3s blink once | off | Blinking | Blinking | Blinking | During cooling and drying operation, all loads except the indoor fan stop operation. During heating operation, the entire unit stops. |
| ||
2 | Antifreezing protection | E2 | Off 3s and blink twice | On | Off | On | Off | During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. |
| ||
3 | High discharge temperature protection of compressor | E4 | Off 3s and blink 4 times | On | Off | On | Blinking | During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heating, all loads stop. | Please refer to the service manual | ||
4 | Overcurrent protection | E5 | Off 3s and blink 5 times | Off | On | Blinking | Off | During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heating, all loads stop. |
| ||
5 | Communication malfunction | E6 | Off 3s and blink 6 times | Off | Off | Off | Blinking | During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heating, all loads stop. | Please refer to the service manual | ||
6 | High temperature resistant protection | E8 | Off 3s and blink 8 times | On | Off | On | On | During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heating, all loads stop. | Please refer to the service manual | ||
7 | Internal motor (fan motor) does not operate | H6 | Off 3s and blink 11 times | Internal fan motor, external fan motor, compressor and electric heater stop operation. Guid louver stops at present location. |
| ||||||
8 | Malfunction protection of jumper cap | C5 | Off 3s and blink 15 times | Indoor unit does not respond to the wireless remote commands. |
| ||||||
9 | Indoor ambient temperature sensor is open/short circuited | F1 | Off 3s and blink once | During cooling and drying operation, indoor unit operates while other loads will stop. During heating operation the complete unit will stop operation. |
| ||||||
10 | Indoor evaporator temperature sensor is open/short circuited | F2 | Off 3s and blink twice | AC stops operation once it reaches the set temperature. Cooling/drying: internal fan motor stops operation while other loads stop operation. Heating: AC stops operation. |
| ||||||
11 | Outdoor ambient temperature sensor is open/short circuited | F3 | Off 3s and blink 3 times | Off | Off | Blinking | On | During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heating, all loads stop. | Outdoor temperature sensor hasn't been connected well or is damaged. | ||
12 | Outdoor condenser temperature sensor is open/short circuited | F4 | Off 3s and blink 4 times | Off | Off | Blinking | Off | During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heating, all loads stop. | Outdoor temperature sensor hasn't been connected well or is damaged. | ||
13 | Outdoor discharge temperature sensor is open/short circuited | F5 | Off 3s and blink 5 times | Off | Off | Blinking | Blinking | During cooling and drying operation, compressor will stop after operating for about 3 mins while indoor fan will operate. During heating operation, the complete unit will stop after operating for about 3 minutes. |
| ||
14 | Limit/decrease frequency due to overload | F6 | Off 3s and blink 6 times | On | Off | Blinking | Blinking | All loads operate normally, while operation frequency for compressor is decreased. | Please refer to the service manual | ||
15 | Decrease frequency due to overcurrent | F8 | Off 3s and blink 8 times | On | On | Off | On | All loads operate normally, while operation frequency for compressor is decreased. | The input supply voltage is too low; System pressure is too high and overload; | ||
16 | Decrease frequency due to high air discharge | F9 | Off 3s and blink 9 times | On | On | Off | Off | All loads operate normally, while operation frequency for compressor is decreased. |
|