Indoor Units
Outdoor Units
Malfunction Indicators
| NO. | Malfunction description | LED1 | LED2 | LED3 | LED4 |
| 0 | Normal stop | off | off | off | off |
| 1 | Compressor run | on | off | off | off |
| 2 | Compressor overload protection | blinking | off | off | off |
| 3 | Discharge protection | off | on | off | off |
| 4 | Outdoor unit overload protection | on | on | off | off |
| 5 | High pressure protection | blinking | on | off | off |
| 6 | Over current protection | off | blinking | off | off |
| 7 | IMP protection | on | blinking | off | off |
| 8 | IMP overheating protection | blinking | blinking | off | off |
| 9 | PFC protection (including PFC overheating protection) | off | off | on | off |
| 10 | Phase current protection | on | off | on | off |
| 11 | Over voltage protection | blinking | off | on | off |
| 12 | Insufficient voltage protection | off | on | on | off |
| 13 | Start failure | on | on | on | off |
| 14 | Compressor desynchronizing | blinking | on | on | off |
| 15 | Compressor phase-lacking protection | off | blinking | on | off |
| 16 | Compressor phase current detection malfunction | on | blinking | on | off |
| 17 | Memory chip mistake | blinking | blinking | on | off |
| 18 | DC power supply short-circuit | off | off | blinking | off |
| 19 | Defrosting | on | off | blinking | off |
| 20 | Oil return | blinking | off | blinking | off |
| 21 | Complete unit frequency restriction protection | off | on | blinking | off |
| 22 | Complete unit frequency dropping protection | on | on | blinking | off |
| 23 | Unit A frequency restriction or frequency dropping protection | blinking | on | blinking | off |
| 24 | Unit B frequency restriction or frequency dropping protection | off | blinking | blinking | off |
| 25 | Unit C frequency restriction or frequency dropping protection | on | blinking | blinking | off |
| 26 | Unit D frequency restriction or frequency dropping protection | blinking | blinking | blinking |