TD Prime Heat Pump Specs

From Technical Support Wiki
Revision as of 19:41, 9 September 2021 by ACINT (talk | contribs)
Jump to: navigation, search

Specification Table of the Heat Pump TD Prime ducted units.

Outdoor Model ATDCI4H4G24 ATDCI4H4G36 ATDCI4H4G48 ATDCI4H4G60
Outdoor Power Supply V/Ph/Hz 208-203V/1Ph/60Hz 208-203V/1Ph/60Hz 208-203V/1Ph/60Hz 208-203V/1Ph/60Hz
Cooling Capacity Btu/h 24000 34500 47000 56000
EER Btu/h.W 11.6 11.6 11.6 10.8
SEER 17.5 17.5 17.5 17.5
Heating Capacity Btu/h 24000 34000 46500 55000
COP Btu/h.W 13.0 11.9 12.9 11.5
HSPF 9.5 9.0 9.5 9.5
Compressor Type GMCC Twin-rotary DC Mitsubishi Twin-rotary DC
Outdoor Dimension Unit (WxHxD) inch 29x25x29 29x25x29 29x33x29 29x33x29
Packaging (WxHxD) inch 30x26x30 30x26x30 30x35x30 30x35x30
Indoor Model ATDEM4H4G24 ATDEM4H4G36 ATDEM4H4G48 ATDEM4H4G60
Cooling Capacity Btu/h 24000 34500 47000 56000
SEER 17.5 17.5 17.5 17.5
Heating Capacity Btu/h 24000 34000 46500 55000
HSPF 9.5 9.0 9.5 9.5
Indoor Max Current A 0.91 1.35 2.39 2.43
Indoor Air Flow CFM 780 1300 1500 1750
ESP Pa 25 37 50 50
Indoor Dimension Unit (WxHxD) inch 20x46x22 20x46x22 22x53x24 22x53x24
Packaging (WxHxD) inch 23x48x26 23x48x26 26x55x28 26x55x28