Gree Electric Appliances VRF
AHU Kit
MHI-FDT-IDU.png
Voltage 220V
Cooling Capacities (kW) 3.6-168
Heat Pump? Yes

Model Numbers

  • GMV-N36U/B-T
  • GMV-N71U/B-T
  • GMV-N140U/B-T
  • GMV-N280U/B-T
  • GMV-N560U/B-T
  • GMV-N560U/BT+GMV-N140U/B-T
  • GMV-N560U/BT+GMV-N280U/B-T
  • GMV-N560U/BT+GMV-N560U/B-T

Specifications

Model GMV-N36U/B-T GMV-N71U/B-T GMV-N140U/B-T GMV-N280U/B-T GMV-N560U/B-T
Defaulted Capacity of Ex-Factory Capacity 36 71 140 280 560
Cooling kW 3.6 7.1 14.0 28.0 56.0
Heating kW 4.0 8.0 16.0 31.5 63.0
Adjustable Capacity Capacity 28 36 45 56 71 90 112 140 224 280 335 400 450 504 560 840
Power Supply V/Ph/Hz 220-240/1/50 & 208-230/1/60
Power Consumption W 15 15 20 40 40
Airflow Volume (H/M/L) m3/h 400/320/270 400/320/270 480/400/310 680/600/500 680/600/500
CFM 235/188/159 235/188/159 282/235/182 400/353/294 400/353/294
Rated Current Cooling A 0.17 0.17 0.25 0.4 0.4
Heating A 0.17 0.17 0.25 0.4 0.4
Water Heating A / / / / /
ESP Pa 0 0 0 0 0
Sound Pressure Level (H/M/L) dB(A) 38/33/27 38/33/27 40/37/32 46/43/39 46/43/39
Connecting Pipe Diameter Liquid mm ⌀6.35 ⌀6.35 ⌀6.35 ⌀6.35 ⌀6.35
Gas mm ⌀9.52 ⌀9.52 ⌀9.52 ⌀12.7 ⌀12.7
Drain Pipe External Dia. mm ⌀28 ⌀28 ⌀28 ⌀28 ⌀28
Thickness mm 1 1 1 1 1
Dimension (WxDxH) Outline mm 700x215x600 700x215x600 700x215x600 700x215x600 700x215x600
Package mm 788x283x777 788x283x777 788x283x777 788x283x777 788x283x777
Net Weight/Gross Weight kg 16/19 16/19 16/19 16/19 16/19
Loading Quantity 40' GP set 348 348 348 348 348
40' HQ set 348 348 348 348 348