Difference between revisions of "Blue Series Troubleshooting (18K & 24K)"
From Technical Support Wiki
Line 140: | Line 140: | ||
* Jumper cap is damaged; | * Jumper cap is damaged; | ||
* Abnormal detecting circuit of main board; | * Abnormal detecting circuit of main board; | ||
+ | |- | ||
+ | | 9 | ||
+ | | Indoor ambient temperature sensor is open/short circuited | ||
+ | | F1 | ||
+ | | | ||
+ | | Off 3s and blink once | ||
+ | | | ||
+ | | | ||
+ | | | ||
+ | | | ||
+ | | | ||
+ | | During cooling and drying operation, indoor unit operates while other loads will stop. During heating operation the complete unit will stop operation. | ||
+ | | | ||
+ | * Loosening or bad contact of indoor ambient temp. sensor and main board terminal; | ||
+ | * Components in main board fell down leading to short circuit; | ||
+ | * Indoor ambient temp. sensor damaged; | ||
+ | * Main board damaged; | ||
+ | |- | ||
+ | | 10 | ||
+ | | Indoor evaporator temperature sensor is open/short circuited | ||
+ | | F2 | ||
+ | | | ||
+ | | Off 3s and blink twice | ||
+ | | | ||
+ | | | ||
+ | | | ||
+ | | | ||
+ | | | ||
+ | | AC stops operation once it reaches the set temperature. Cooling/drying: internal fan motor stops operation while other loads stop operation. Heating: AC stops operation. | ||
+ | | | ||
+ | * Loosening or bad contact of indoor evaporator temp. sensor and main board terminal; | ||
+ | * Components in main board fell down leading to short circuit; | ||
+ | * Indoor evaporator temp. sensor damaged; | ||
+ | * Main board damaged; | ||
|- | |- |
Revision as of 17:50, 1 May 2014
NO. | Malfunction Name | Display Method of Indoor Unit | Display Method of Outdoor Unit | A/C Status | Possible Causes | ||||||
Dual-8 Code Display | Indicator Display | Indicator Display | |||||||||
Operation Indicator | Cooling Indicator | Heating Indicator | D40/D5 | D41/D6 | D42/D16 | D43/D30 | |||||
1 | System High Pressure Protection | E1 | Off 3s blink once | off | Blinking | Blinking | Blinking | During cooling and drying operation, all loads except the indoor fan stop operation. During heating operation, the entire unit stops. |
| ||
2 | Antifreezing protection | E2 | Off 3s and blink twice | On | Off | On | Off | During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. |
| ||
3 | High discharge temperature protection of compressor | E4 | Off 3s and blink 4 times | On | Off | On | Blinking | During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heating, all loads stop. | Please refer to the service manual | ||
4 | Overcurrent protection | E5 | Off 3s and blink 5 times | Off | On | Blinking | Off | During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heating, all loads stop. |
| ||
5 | Communication malfunction | E6 | Off 3s and blink 6 times | Off | Off | Off | Blinking | During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heating, all loads stop. | Please refer to the service manual | ||
6 | High temperature resistant protection | E8 | Off 3s and blink 8 times | On | Off | On | On | During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heating, all loads stop. | Please refer to the service manual | ||
7 | Internal motor (fan motor) does not operate | H6 | Off 3s and blink 11 times | Internal fan motor, external fan motor, compressor and electric heater stop operation. Guid louver stops at present location. |
| ||||||
8 | Malfunction protection of jumper cap | C5 | Off 3s and blink 15 times | Indoor unit does not respond to the wireless remote commands. |
| ||||||
9 | Indoor ambient temperature sensor is open/short circuited | F1 | Off 3s and blink once | During cooling and drying operation, indoor unit operates while other loads will stop. During heating operation the complete unit will stop operation. |
| ||||||
10 | Indoor evaporator temperature sensor is open/short circuited | F2 | Off 3s and blink twice | AC stops operation once it reaches the set temperature. Cooling/drying: internal fan motor stops operation while other loads stop operation. Heating: AC stops operation. |
|