Difference between revisions of "Blue Series Troubleshooting (18K & 24K)"
From Technical Support Wiki
Line 93: | Line 93: | ||
| Please refer to the [[:File:Service_Manual_Platinum.pdf|service manual]] | | Please refer to the [[:File:Service_Manual_Platinum.pdf|service manual]] | ||
|- | |- | ||
− | | | + | | 6 |
| High temperature resistant protection | | High temperature resistant protection | ||
| E8 | | E8 | ||
Line 105: | Line 105: | ||
| During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heating, all loads stop. | | During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heating, all loads stop. | ||
| Please refer to the [[:File:Service_Manual_Platinum.pdf|service manual]] | | Please refer to the [[:File:Service_Manual_Platinum.pdf|service manual]] | ||
+ | |- | ||
+ | | 7 | ||
+ | | Internal motor (fan motor) does not operate | ||
+ | | H6 | ||
+ | | Off 3s and blink 11 times | ||
+ | | | ||
+ | | | ||
+ | | | ||
+ | | | ||
+ | | | ||
+ | | Internal fan motor, external fan motor, compressor and electric heater stop operation. Guid louver stops at present location. | ||
+ | | | ||
+ | * Bad contact of DC motor feedback terminal; | ||
+ | * Bad contact of DC motor control end; | ||
+ | * Fan motor is stalling; | ||
+ | * Motor malfunction; | ||
+ | * Malfunction of main board rev detecting difficulty; | ||
|- | |- |
Revision as of 17:46, 1 May 2014
NO. | Malfunction Name | Display Method of Indoor Unit | Display Method of Outdoor Unit | A/C Status | Possible Causes | ||||||
Dual-8 Code Display | Indicator Display | Indicator Display | |||||||||
Operation Indicator | Cooling Indicator | Heating Indicator | D40/D5 | D41/D6 | D42/D16 | D43/D30 | |||||
1 | System High Pressure Protection | E1 | Off 3s blink once | off | Blinking | Blinking | Blinking | During cooling and drying operation, all loads except the indoor fan stop operation. During heating operation, the entire unit stops. |
| ||
2 | Antifreezing protection | E2 | Off 3s and blink twice | On | Off | On | Off | During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. |
| ||
3 | High discharge temperature protection of compressor | E4 | Off 3s and blink 4 times | On | Off | On | Blinking | During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heating, all loads stop. | Please refer to the service manual | ||
4 | Overcurrent protection | E5 | Off 3s and blink 5 times | Off | On | Blinking | Off | During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heating, all loads stop. |
| ||
5 | Communication malfunction | E6 | Off 3s and blink 6 times | Off | Off | Off | Blinking | During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heating, all loads stop. | Please refer to the service manual | ||
6 | High temperature resistant protection | E8 | Off 3s and blink 8 times | On | Off | On | On | During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heating, all loads stop. | Please refer to the service manual | ||
7 | Internal motor (fan motor) does not operate | H6 | Off 3s and blink 11 times | Internal fan motor, external fan motor, compressor and electric heater stop operation. Guid louver stops at present location. |
|