Difference between revisions of "A16CI4H4R36"
From Technical Support Wiki
| Line 248: | Line 248: | ||
== Wiring Diagram == | == Wiring Diagram == | ||
[[File:Mini-36K-ODU-WD.jpg|none|thumb|500px|A16CI4H4R36 Wiring Diagram]] | [[File:Mini-36K-ODU-WD.jpg|none|thumb|500px|A16CI4H4R36 Wiring Diagram]] | ||
| + | == Exploded View and Parts List == | ||
| + | [[File:Mini-36K-ODU-EV.jpg|thumb|500px|A16CI4H4R36 Exploded View]] | ||
| + | {| class="wikitable" | ||
| + | ! Number | ||
| + | ! Part Name | ||
| + | |- | ||
| + | | 1 | ||
| + | | Front Grill | ||
| + | |- | ||
| + | | 2 | ||
| + | | Cabinet | ||
| + | |- | ||
| + | | 3 | ||
| + | | Front Side Plate | ||
| + | |- | ||
| + | | 4 | ||
| + | | Axial Flow Fan | ||
| + | |- | ||
| + | | 5 | ||
| + | | Drainage Plug | ||
| + | |- | ||
| + | | 6 | ||
| + | | Chassis Sub-Assy | ||
| + | |- | ||
| + | | 7 | ||
| + | | Drainage Connector | ||
| + | |- | ||
| + | | 8 | ||
| + | | Compressor Gasket | ||
| + | |- | ||
| + | | 9 | ||
| + | | Compressor and Fittings | ||
| + | |- | ||
| + | | 10 | ||
| + | | Electrical Heater | ||
| + | |- | ||
| + | | 11 | ||
| + | | Magnet Coil | ||
| + | |- | ||
| + | | 12 | ||
| + | | 4-Way Valve Assy | ||
| + | |- | ||
| + | | 13 | ||
| + | | Right Side Plate | ||
| + | |- | ||
| + | | 14 | ||
| + | | Valve Support Assy | ||
| + | |- | ||
| + | | 15 | ||
| + | | Cut-Off Valve | ||
| + | |- | ||
| + | | 16 | ||
| + | | Valve Cover | ||
| + | |- | ||
| + | | 17 | ||
| + | | Retaining Plate | ||
| + | |- | ||
| + | | 18 | ||
| + | | Handle Assy | ||
| + | |- | ||
| + | | 19 | ||
| + | | Wiring Clamp | ||
| + | |- | ||
| + | | 20 | ||
| + | | Capillary Sub-Assy | ||
| + | |- | ||
| + | | 21 | ||
| + | | Temperature Sensor | ||
| + | |- | ||
| + | | 22 | ||
| + | | Rear Grill | ||
| + | |- | ||
| + | | 23 | ||
| + | | Condenser Assy | ||
| + | |- | ||
| + | | 24 | ||
| + | | Clapboard | ||
| + | |- | ||
| + | | 25 | ||
| + | | Condenser Support Plate | ||
| + | |- | ||
| + | | 26 | ||
| + | | Motor Support Sub-Assy | ||
| + | |- | ||
| + | | 27 | ||
| + | | Top Cover Sub-Assy | ||
| + | |- | ||
| + | | 28 | ||
| + | | Electric Box Cover | ||
| + | |- | ||
| + | | 29 | ||
| + | | Reactor | ||
| + | |- | ||
| + | | 30 | ||
| + | | Electric Box Sub-Assy | ||
| + | |- | ||
| + | | 31 | ||
| + | | Pass Wire Ring Sub-Assy | ||
| + | |- | ||
| + | | 32 | ||
| + | | Left Handle | ||
| + | |- | ||
| + | | 33 | ||
| + | | Left Side Plate | ||
| + | |- | ||
| + | | 34 | ||
| + | | Fan Motor | ||
| + | |- | ||
| + | | 35 | ||
| + | | Electric Box Cover | ||
| + | |- | ||
| + | | 36 | ||
| + | | Main Board | ||
| + | |- | ||
| + | | 37 | ||
| + | | Electric Box | ||
| + | |- | ||
| + | | 38 | ||
| + | | Radiator | ||
| + | |- | ||
| + | | 39 | ||
| + | | Terminal Board | ||
| + | |- | ||
| + | | 40 | ||
| + | | Electric Box Assy | ||
| + | |- | ||
| + | | 41 | ||
| + | | Capillary Sub-Assy (Oil Returning) | ||
| + | |- | ||
| + | | 42 | ||
| + | | Electrical Heater (Chassis) | ||
| + | |} | ||
== Accessories == | == Accessories == | ||
*[[Wall Bracket (QBR-19.5)]] | *[[Wall Bracket (QBR-19.5)]] | ||
*[[Universal Remote (QTH-4000)]] | *[[Universal Remote (QTH-4000)]] | ||
Revision as of 14:27, 11 December 2013
A16CI4H4R36 is the 16 SEER 36,000 Btu mini split condenser.
Malfunction Information Table
| Name of Malfunction | Display of indoor unit | State of the lamps on the outdoor unit PCB | |||
| Error Code | Yellow | Red | Green | Reasons | |
| Compressor running (normal) | blink 1 time | Part of normal operation | |||
| Automatic defrosting (normal) | H1 | blink 2 times | Part of normal operation | ||
| Anti-freezing protection | E2 | blink 3 times | Refrigerant leakage / indoor unit airflow blocked up / filter duty | ||
| Stop for IPM module protection (over current) | H5 | blink 4 times | IPM model over current / outdoor unit air flow blocked up | ||
| Stop for over current protection | E5 | blink 5 times | Outdoor unit over current / ambient temperature is abominable | ||
| Overload protection | H4 | blink 6 times | Ambient temperature is abominable / heat exchanger is blocked up | ||
| Stop for exhaust protection | E4 | blink 7 times | low refrigerant / capillary blocked up / ambient temperature is abominable | ||
| Stop for compressor overload protection | H3 | blink 8 times | Compressor shell overheat / low refrigerant / capillary blocked up | ||
| Stop for overpower protection | L9 | blink 9 times | Ambient temperature is abominable | ||
| Stop for IPM module protection (overheat) | H5 | blink 10 times | IPM module overheat / outdoor unit airflow blocked up | ||
| Stop for EEPROM read-write function | EE | blink 11 times | The EEPROM on the outdoor PCB mainboard cannot read or write | ||
| Stop for low voltage protection | PL | blink 12 times | DC voltage is too low | ||
| Stop for high voltage protection | PH | blink 13 times | DC voltage is too high | ||
| Stop for PFC circuit over current protection | HC | blink 14 times | The PFC circuit over current | ||
| No feedback of indoor fan motor | H6 | / | / | / | Indoor fan is abnormal |
| Stop for ID and OD doesn't match | LP | blink 16 times | The indoor unit and outdoor unit does not match | ||
| Compressor frequence limit by over current protection | blink 1 time | Outdoor unit over current / ambient temperature is abominable | |||
| Compressor frequence limit by exhaust protection | blink 2 times | low refrigerant / capillary blocked up / ambient temperature is abominable | |||
| Compressor frequence limit by overload protection | blink 3 times | Ambient temperature is abominable / heat exchanger is blocked up | |||
| Compressor frequence limit by anti-freezing protection | blink 4 times | Refrigerant leakage / indoor unit airflow blocked up / filter duty | |||
| Outdoor pipe temperature sensor malfunction | F4 | blink 5 times | Open circuit or short circuit for outdoor condenser pipe temp. sensor | ||
| Outdoor ambient temperature sensor malfunction | F3 | blink 6 times | Open circuit or short circuit for outdoor environment temp. sensor | ||
| Outdoor exhaust temperature sensor malfunction | F5 | blink 7 times | Open circuit or short circuit for outdoor gas-discharge pipe temp. sensor | ||
| The indoor temp. reach to operate compressor (normal) | blink 8 times | Part of normal operation / Compressor preparing to run | |||
| Compressor frequence limit by IPM protection | blink 11 times | IPM module overheat / outdoor unit airflow blocked up | |||
| Compressor frequence limit by over power protection | blink 13 times | Ambient temperature is abominable | |||
| Indoor ambient temperature sensor malfunction | F1 | Open circuit or short circuit for indoor environment temp. sensor | |||
| Indoor tube temperature sensor malfunction | F2 | Open circuit or short circuit for indoor environment pipe temp. sensor | |||
| Stop for communication malfunction | E6 | off | Communication line failure / main PCB failure / interfere source / connect line wrong | ||
| Communication is normal | blink 1 time | Communication is normal | |||
| Jumper cap malfunction protection | C5 | The jumper misfit the main board | |||
| No feedback from outdoor fan motor | blink 14 times | ||||
| High pressure protection | E1 | blink 16 times | |||
| Note: The lamps blink 0.5s on, 0.5s off. There is a 2s off interval between error codes. | |||||
Wiring Diagram
Exploded View and Parts List
| Number | Part Name |
|---|---|
| 1 | Front Grill |
| 2 | Cabinet |
| 3 | Front Side Plate |
| 4 | Axial Flow Fan |
| 5 | Drainage Plug |
| 6 | Chassis Sub-Assy |
| 7 | Drainage Connector |
| 8 | Compressor Gasket |
| 9 | Compressor and Fittings |
| 10 | Electrical Heater |
| 11 | Magnet Coil |
| 12 | 4-Way Valve Assy |
| 13 | Right Side Plate |
| 14 | Valve Support Assy |
| 15 | Cut-Off Valve |
| 16 | Valve Cover |
| 17 | Retaining Plate |
| 18 | Handle Assy |
| 19 | Wiring Clamp |
| 20 | Capillary Sub-Assy |
| 21 | Temperature Sensor |
| 22 | Rear Grill |
| 23 | Condenser Assy |
| 24 | Clapboard |
| 25 | Condenser Support Plate |
| 26 | Motor Support Sub-Assy |
| 27 | Top Cover Sub-Assy |
| 28 | Electric Box Cover |
| 29 | Reactor |
| 30 | Electric Box Sub-Assy |
| 31 | Pass Wire Ring Sub-Assy |
| 32 | Left Handle |
| 33 | Left Side Plate |
| 34 | Fan Motor |
| 35 | Electric Box Cover |
| 36 | Main Board |
| 37 | Electric Box |
| 38 | Radiator |
| 39 | Terminal Board |
| 40 | Electric Box Assy |
| 41 | Capillary Sub-Assy (Oil Returning) |
| 42 | Electrical Heater (Chassis) |