Difference between revisions of "Starling Series 30K & 36K Specs"
From Technical Support Wiki
Line 97: | Line 97: | ||
| 4000 | | 4000 | ||
| 4000 | | 4000 | ||
+ | |- | ||
+ | !scope="row" rowspan="2" | Rated Current | ||
+ | ! Cooling | ||
+ | | A | ||
+ | | 20 | ||
+ | | 20 | ||
+ | |- | ||
+ | ! Heating | ||
+ | | A | ||
+ | | 20 | ||
+ | | 20 | ||
+ | |- | ||
+ | !scope="col" colspan="2" | Min. Circuit Ampacity | ||
+ | | A | ||
+ | | 27 | ||
+ | | 24 | ||
+ | |- | ||
+ | !scope="col" colspan="2" | Starting Current | ||
+ | | A | ||
+ | | 5 | ||
+ | | 5 | ||
+ | |- | ||
+ | !scope="col" colspan="2" | Max Over Current Protection | ||
+ | | A | ||
+ | | 30 | ||
+ | | 35 | ||
|- | |- | ||
|} | |} | ||
Return to [[Starling Series]] main page. | Return to [[Starling Series]] main page. |
Revision as of 13:20, 2 May 2025
Parameter | Unit | Value | ||
---|---|---|---|---|
Model | TACCI7H4R30/TACEM7H4R30-S | TACCI7H4R36/TACEM7H4R36-S | ||
Power Supply | Rated Voltage | V | 208/230 | 208/230 |
Rated Frequency | Hz | 60 | 60 | |
Phases | 1 | 1 | ||
Cooling | Cooling Capacity | BTU/h | 30000 | 33600 |
EER2 | BTU/W.h | 10.9 | 10.6 | |
SEER2 | BTU/W.h | 22 | 21 | |
Min Cooling Capacity | BTU/h | 3000 | 7850 | |
Max Cooling Capacity | BTU/h | 36000 | 37500 | |
Cooling Power Input | W | 2750 | 3169 | |
Min Cooling Power Input | W | 250 | 700 | |
Max Cooling Power Input | W | 4000 | 4000 | |
Heating | Heating Capacity | BTU/h | 30000 | 34000 |
Min Heating Capacity | BTU/h | 5800 | 10000 | |
Max Heating Capacity | BTU/h | 35500 | 37500 | |
Heating Power Input | W | 2750 | 3267 | |
Min. Heating Power Input | W | 330 | 650 | |
Max. Heating Power Input | W | 4000 | 4000 | |
Rated Current | Cooling | A | 20 | 20 |
Heating | A | 20 | 20 | |
Min. Circuit Ampacity | A | 27 | 24 | |
Starting Current | A | 5 | 5 | |
Max Over Current Protection | A | 30 | 35 |
Return to Starling Series main page.