Line 375: | Line 375: | ||
|- | |- | ||
| 1 | | 1 | ||
− | | | + | | Too much refrigerant |
− | + | | Discharge refrigerant and refill to the appropriate level | |
+ | |- | ||
+ | | 2 | ||
+ | | The outdoor ambient temperature is too high | ||
+ | | Please use within the rated ambient temperature range | ||
+ | |- | ||
+ | | 3 | ||
+ | | The air outlet and the air inlet of the outdoor unit has short circuited | ||
+ | | Adjust the installation according to the installation manual | ||
+ | |- | ||
+ | | 4 | ||
+ | | The outdoor heat exchanger is dirty | ||
+ | | Clean the heat exchanger of the outdoor unit | ||
+ | |- | ||
+ | | 5 | ||
+ | | The speed of the outdoor fan motor is too low | ||
+ | | Check the outdoor fan motor or fan capacitor | ||
+ | |- | ||
+ | | 6 | ||
+ | | The outdoor fan is broken or the outdoor fan is blocked | ||
+ | | Check the outdoor fan | ||
+ | |- | ||
+ | | 7 | ||
+ | | The air inlet and outlet and been blocked | ||
+ | | Remove the blockage | ||
+ | |- | ||
+ | | 8 | ||
+ | | The expansion valve or the capillary has failed | ||
+ | | Replace the expansion valve or the capillary | ||
+ | |- | ||
+ | |} | ||
+ | {| class="wikitable" | ||
+ | ! colspan="3" | Overload in Heating Mode Addendum | ||
+ | |- | ||
+ | ! Number | ||
+ | ! Cause | ||
+ | ! Corrective Measures | ||
+ | |- | ||
+ | | 1 | ||
+ | | Too much refrigerant | ||
+ | | Discharge refrigerant and refill to the appropriate level | ||
+ | |- | ||
+ | | 2 | ||
+ | | The indoor ambient temperature is too high | ||
+ | | Please use within the rated ambient temperature range | ||
+ | |- | ||
+ | | 3 | ||
+ | | The air outlet and the air inlet of the indoor unit has short circuited | ||
+ | | Adjust the installation according to the installation manual | ||
+ | |- | ||
+ | | 4 | ||
+ | | The indoor filter is dirty | ||
+ | | Clean the indoor filter | ||
+ | |- | ||
+ | | 5 | ||
+ | | The speed of the indoor fan motor is too low | ||
+ | | Check the indoor fan motor or fan capacitor | ||
+ | |- | ||
+ | | 6 | ||
+ | | The indoor fan is broken or the outdoor fan is blocked | ||
+ | | Check the indoor fan | ||
+ | |- | ||
+ | | 7 | ||
+ | | The air inlet and outlet and been blocked | ||
+ | | Remove the blockage | ||
+ | |- | ||
+ | | 8 | ||
+ | | The expansion valve or the capillary has failed | ||
+ | | Replace the expansion valve or the capillary | ||
+ | |- | ||
|} | |} | ||
Go back to [[Multi Plus]] page | Go back to [[Multi Plus]] page |
Latest revision as of 12:59, 27 September 2019
Fault Code | Fault Description | Possible Reason for Fault | Potential Fixes |
---|---|---|---|
1 | Outdoor Ambient Temperature Sensor Fault |
|
|
2 | Outdoor Coil Temperature Sensor Fault |
|
|
3 | The Unit Over-Current Turn Off Fault |
|
|
4 | EEprom Data Error |
|
|
5 | Cooling Freezing
Protection (the indoor coil temperature is too low) or Heating Overload (indoor coil temperature is too high) |
|
|
7 | Communication fault between the indoor unit and outdoor unit |
outdoor unit is poor
|
|
13 | Compressor overheat protector device |
|
overload protector
protector
board |
14 | The high pressure switch operates or the unit turns off for high pressure protection |
|
|
15 | Low pressure switch protection or the unit turned off for low pressure protection |
|
board |
16 | Overload protection in cooling mode | System Overload | Refer to "Overload in Cooling Mode addendum" |
17 | Discharge temperature sensor fault |
|
|
18 | AC voltage is abnormal |
|
|
19 | Suction temperature sensor fault |
|
|
22 | Defrosting sensor fault |
|
|
23 | Expansion valve A tube (thin) sensor fault |
|
|
24 | Expansion valve B tube (thin) sensor fault |
|
|
25 | Expansion valve C tube (thin) sensor fault |
|
|
26 | Expansion valve D tube (thin) sensor fault |
|
|
27 | Expansion valve A tube (thick) sensor fault |
|
|
28 | Expansion valve B tube (thick) sensor fault |
|
|
29 | Expansion valve C tube (thick) sensor fault |
|
|
30 | Expansion valve D tube (thick) sensor fault |
|
|
45 | IPM fault | Please refer to "drive board fault codes" for more information | Please refer to "drive board fault codes" for more information |
46 | IPM and control board communication fault |
|
|
47 | Discharge temperature too high fault |
|
|
48 | Outdoor DC fan motor fault (upper fan motor) |
|
|
49 | Outdoor DC fan motor fault (lower fan motor) |
|
|
91 | The unit turned off due to the IPM board over heating fault |
|
|
96 | The refrigerant of the unit is not enough fault | Insufficient amount of refrigerant |
|
97 | 4-way valve communication failure fault |
|
|
Overload in Cooling Mode Addendum | ||
---|---|---|
Number | Cause | Corrective Measures |
1 | Too much refrigerant | Discharge refrigerant and refill to the appropriate level |
2 | The outdoor ambient temperature is too high | Please use within the rated ambient temperature range |
3 | The air outlet and the air inlet of the outdoor unit has short circuited | Adjust the installation according to the installation manual |
4 | The outdoor heat exchanger is dirty | Clean the heat exchanger of the outdoor unit |
5 | The speed of the outdoor fan motor is too low | Check the outdoor fan motor or fan capacitor |
6 | The outdoor fan is broken or the outdoor fan is blocked | Check the outdoor fan |
7 | The air inlet and outlet and been blocked | Remove the blockage |
8 | The expansion valve or the capillary has failed | Replace the expansion valve or the capillary |
Overload in Heating Mode Addendum | ||
---|---|---|
Number | Cause | Corrective Measures |
1 | Too much refrigerant | Discharge refrigerant and refill to the appropriate level |
2 | The indoor ambient temperature is too high | Please use within the rated ambient temperature range |
3 | The air outlet and the air inlet of the indoor unit has short circuited | Adjust the installation according to the installation manual |
4 | The indoor filter is dirty | Clean the indoor filter |
5 | The speed of the indoor fan motor is too low | Check the indoor fan motor or fan capacitor |
6 | The indoor fan is broken or the outdoor fan is blocked | Check the indoor fan |
7 | The air inlet and outlet and been blocked | Remove the blockage |
8 | The expansion valve or the capillary has failed | Replace the expansion valve or the capillary |
Go back to Multi Plus page