Difference between revisions of "Multi Plus ODU Main Board Troubleshooting"

From Technical Support Wiki
Jump to: navigation, search
Line 65: Line 65:
 
* The setting fan speed is too low
 
* The setting fan speed is too low
 
* The indoor unit is not standard installed, air inlet is too near with air outlet
 
* The indoor unit is not standard installed, air inlet is too near with air outlet
 +
|
 +
* Check the indoor fan, indoor fan motor and evaporator
 +
* Clean the filter
 +
* Check the volume control valve, duct length etc.
 +
* Set the speed with high speed
 +
* Reinstall the indoor unit refer to the user manual to change the distance between the indoor unit and the wall or ceiling.
 +
|-
 +
| 7
 +
| Communication fault between the indoor unit and outdoor unit
 +
|
 +
* The connection between the indoor unit and
 +
outdoor unit is poor
 +
* The communication cable is loose
 +
* The communication cable is faulty
 +
* The indoor control board is faulty
 +
* The outdoor control board is faulty
 +
* Communication circuit fuse is open
 +
* The specification of communication cable is incorrect
 +
|-
 +
| 13
 +
| Compressor overheat protector device
 +
|
 +
* The wiring of the overload protector connection is loose
 +
* The overload protector has failed
 +
* Insufficient refrigerant
 +
* The copper pipping is longer than normal, but no additional refrigerant has been added
 +
* The expansion valve has failed
 +
* The outdoor control board has failed
 +
|
 +
* Reconnect the wiring of the
 +
overload protector
 +
* Replace the overload
 +
protector
 +
* Check for a refrigerant leak, fix it and re-add refrigerant
 +
* If there is no leak, add refrigerant according to the length of the copper tubing.
 +
* Replace expansion valve
 +
* Replace the outdoor control
 +
board
 
|-
 
|-
 
 
|}
 
|}

Revision as of 18:34, 25 September 2019

Fault Code Fault Description Possible Reason for Fault Potential Fixes
1 Outdoor Ambient Temperature Sensor Fault
  • The outdoor ambient temperature sensor connection is loose
  • The outdoor ambient temperature sensor has failed
  • The sampling circuit has failed
  • Reconnect the outdoor ambient temperature sensor
  • Replace the outdoor ambient temperature sensor
  • Replace the outdoor board
2 Outdoor Coil Temperature Sensor Fault
  • The outdoor coil temperature sensor connection is loose
  • The outdoor coil temperature sensor has failed
  • The sampling circuit has failed
  • Reconnect the outdoor coil temperature sensor
  • Replace the outdoor coil temperature sensor
  • Replace the outdoor board
3 The Unit Over-Current Turn Off Fault
  • Control board current sampling circuit has failed
  • The current is too high because the supply voltage is too low
  • The compressor is blocked
  • Overload in heating mode
  • Overload in cooling mode
  • Replace the control board
  • Replace the compressor
4 EEprom Data Error
  • EE components have failed
  • EE components control circuit failed
  • EE components have been inserted incorrectly
  • Replace the EE components
  • Replace the outdoor control board
  • Reassemble the EE components
5 Cooling Freezing

Protection (the indoor coil temperature is too low) or Heating Overload (indoor coil temperature is too high)

  • The indoor unit isn't blowing air normally
  • The room temperature is too low in cooling mode or the room temperature is too high in heating
  • Air filter is dirty
  • The duct resistance is too high to result in low air flow
  • The setting fan speed is too low
  • The indoor unit is not standard installed, air inlet is too near with air outlet
  • Check the indoor fan, indoor fan motor and evaporator
  • Clean the filter
  • Check the volume control valve, duct length etc.
  • Set the speed with high speed
  • Reinstall the indoor unit refer to the user manual to change the distance between the indoor unit and the wall or ceiling.
7 Communication fault between the indoor unit and outdoor unit
  • The connection between the indoor unit and

outdoor unit is poor

  • The communication cable is loose
  • The communication cable is faulty
  • The indoor control board is faulty
  • The outdoor control board is faulty
  • Communication circuit fuse is open
  • The specification of communication cable is incorrect
13 Compressor overheat protector device
  • The wiring of the overload protector connection is loose
  • The overload protector has failed
  • Insufficient refrigerant
  • The copper pipping is longer than normal, but no additional refrigerant has been added
  • The expansion valve has failed
  • The outdoor control board has failed
  • Reconnect the wiring of the

overload protector

  • Replace the overload

protector

  • Check for a refrigerant leak, fix it and re-add refrigerant
  • If there is no leak, add refrigerant according to the length of the copper tubing.
  • Replace expansion valve
  • Replace the outdoor control

board