Line 51: Line 51:
 
|-
 
|-
 
| 5
 
| 5
 +
| Cooling Freezing
 +
Protection (the indoor
 +
coil temperature is too
 +
low) or Heating
 +
Overload (indoor coil
 +
temperature is too
 +
high)
 
|  
 
|  
 +
* The indoor unit isn't blowing air
 +
normally
 +
* The room temperature is too low in
 +
cooling mode or the room
 +
temperature is too high in heating
 +
* Air filter is dirty
 +
* The duct resistance is too high to
 +
result in low air flow
 +
* The setting fan speed is too low
 +
* The indoor unit is not standard
 +
installed, air inlet is too near with
 +
air outlet
 +
}-
 +
 
|}
 
|}

Revision as of 18:13, 25 September 2019

Fault Code Fault Description Possible Reason for Fault Potential Fixes
1 Outdoor Ambient Temperature Sensor Fault
  • The outdoor ambient temperature sensor connection is loose
  • The outdoor ambient temperature sensor has failed
  • The sampling circuit has failed
  • Reconnect the outdoor ambient temperature sensor
  • Replace the outdoor ambient temperature sensor
  • Replace the outdoor board
2 Outdoor Coil Temperature Sensor Fault
  • The outdoor coil temperature sensor connection is loose
  • The outdoor coil temperature sensor has failed
  • The sampling circuit has failed
  • Reconnect the outdoor coil temperature sensor
  • Replace the outdoor coil temperature sensor
  • Replace the outdoor board
3 The Unit Over-Current Turn Off Fault
  • Control board current sampling circuit has failed
  • The current is too high because the supply voltage is too low
  • The compressor is blocked
  • Overload in heating mode
  • Overload in cooling mode
  • Replace the control board
  • Replace the compressor
4 EEprom Data Error
  • EE components have failed
  • EE components control circuit failed
  • EE components have been inserted incorrectly
  • Replace the EE components
  • Replace the outdoor control board
  • Reassemble the EE components
5 Cooling Freezing

Protection (the indoor coil temperature is too low) or Heating Overload (indoor coil temperature is too high)

  • The indoor unit isn't blowing air

normally

  • The room temperature is too low in

cooling mode or the room temperature is too high in heating

  • Air filter is dirty
  • The duct resistance is too high to

result in low air flow

  • The setting fan speed is too low
  • The indoor unit is not standard

installed, air inlet is too near with air outlet }-