Difference between revisions of "Multi Plus ODU Specs"

From Technical Support Wiki
Jump to: navigation, search
Line 129: Line 129:
 
| 1920 (420-4020)
 
| 1920 (420-4020)
 
| 3060 (600-6000)
 
| 3060 (600-6000)
 +
|-
 +
! scope="row" rowspan="2" | Rated Current
 +
! Cooling
 +
| 95°F
 +
| A
 +
| 8.7
 +
| 11
 +
|-
 +
! Heating
 +
| 47°F
 +
| A
 +
| 8.7
 +
| 13
 
|-
 
|-
 
|}
 
|}

Revision as of 14:03, 25 September 2019

Type Up to 3 Indoor Units Up to 4 Indoor Units
Model Name AMSCI4H4S24 AMSCI4H4S36
Gas R410A R410A
Capacity Cooling Capacity 95°F BTU/h 24000 32000
Heating Rated Capacity 47°F BTU/h 24000 36000
17°F BTU/h 15400 22800
Heating Maximum Capacity 17°F BTU/h 26000 40000
5°F BTU/h 24000 36000
Cooling 95°F BTU/h 24000(8000-30200) 32000(12000-42000)
Heating 47°F BTU/h 24000(5200-37000) 36000(8000-52000)
Air Flow m3/h 4000 5000
CFM 2350 2941
EER 95°F BTU/Wh 12.5 12.5
COP 47°F BTU/Wh 3.66 3.37
SEER BTU/Wh 22.0 21.0
HSPF BTU/Wh 11.0 11.0
Noise Level (Max) dB(A) 59 59
Operating Range Cooling °F 14-114.8 14-114.8
Heating °F (-13)-75.2 (-13)-75.2
Compressor Model Model EATF250D22UMT EATF400D42UMTA
Brand GMCC GMCC
Electrical Data
Power V/Hz/Ph 208-230/60/1 208-230/60/1
Power Input Cooling 95°F W 1920 (420-2640) 2520 (700-5000)
Heating 47°F W 1920 (420-4020) 3060 (600-6000)
Rated Current Cooling 95°F A 8.7 11
Heating 47°F A 8.7 13