This is the support page for the Heat Pump outdoor units for MHI VRF air conditioners.
Heat Pump Systems (FDC) | |
Voltage | 220V |
---|---|
Capacities (kW) | 142.5-168.0 |
Heat Pump? | Yes |
Model Numbers
- FDC1425KXZE1M (FDC475 + FDC475 + FDC475)
- FDC1450KXZE1M (FDC475 + FDC475 + FDC500)
- FDC1500KXZE1M (FDC500 + FDC500 + FDC500)
- FDC1560KXZE1M (FDC500 + FDC500 + FDC560)
- FDC1620KXZE1M (FDC500 + FDC560 + FDC560)
- FDC1680KXZE1M (FDC560 + FDC560 + FDC560)
Specifications
Item | Unit | FDC1425KXZE1M | FDC1450KXZE1M | FDC1500KXZE1M | FDC1560KXZE1M | FDC1620KXZE1M | FDC1680KXZE1M | |||
---|---|---|---|---|---|---|---|---|---|---|
Nominal Horse Power | 50HP | 52HP | 54HP | 56HP | 58HP | 60HP | ||||
Power Source | 3 Phase-3wire 220V, 60Hz | |||||||||
Starting Current | A | 24 | ||||||||
Max Current | A | 127.2 | ||||||||
Nominal Capacity | Cooling | kW | 142.5 | 145.0 | 150.0 | 156.0 | 162.0 | 168.0 | ||
Heating | 159.0 | 162.0 | 168.0 | 175.0 | 182.0 | 189.0 | ||||
Electrical Characteristics | Power Consumption | Cooling | kW | 41.94 | 41.93 | 41.91 | 44.56 | 47.21 | 49.86 | |
Heating | 39.00 | 39.49 | 40.47 | 42.93 | 45.39 | 47.85 | ||||
Exterior Dimensions | HxWxD | mm | 2048x4050x720 | |||||||
Net Weight | kg | 1101 | ||||||||
Refrigerant Charge | R410A | kg | 11.5x3 | |||||||
Refrigerant Piping Size | Liquid Line | mm (in) | ⌀19.05 (3/4") | |||||||
Gas Line | ⌀38.1 (1 1/2") [⌀34.92 (1 3/8")] | |||||||||
Capacity Connection | % | 50~130 | ||||||||
Number of Connectable Indoor Units | 80 |