Difference between revisions of "MHI KXZ ODU7"
From Technical Support Wiki
(Created page with "This is the support page for the Heat Pump outdoor units for MHI VRF air conditioners. {{Infobox | | bodyclass = infobox | name = Mitsubishi Heavy Industries VRF | title...") |
|||
Line 91: | Line 91: | ||
| colspan="4" style="text-align: center;" | 963 | | colspan="4" style="text-align: center;" | 963 | ||
|- | |- | ||
− | | | + | | colspan="2" | Refrigerant Charge |
| colspan="2" | R410A | | colspan="2" | R410A | ||
| kg | | kg |
Revision as of 14:12, 4 December 2018
This is the support page for the Heat Pump outdoor units for MHI VRF air conditioners.
Heat Pump Systems (FDC) | |
Voltage | 220V |
---|---|
Capacities (kW) | 120.0-135.0 |
Heat Pump? | Yes |
Model Numbers
- FDC1200KXZE1M (FDC400 + FDC400 + FDC400)
- FDC1250KXZE1M (FDC400 + FDC400 + FDC450)
- FDC1300KXZE1M (FDC400 + FDC450 + FDC450)
- FDC1350KXZE1M (FDC450 + FDC450 + FDC450)
Specifications
Item | Unit | FDC1200KXZE1M | FDC1250KXZE1M | FDC1300KXZE1M | FDC1350KXZE1M | |||
---|---|---|---|---|---|---|---|---|
Nominal Horse Power | 42HP | 44HP | 46HP | 48HP | ||||
Power Source | 3 Phase-3wire 220V, 60Hz | |||||||
Starting Current | A | 15 | ||||||
Max Current | A | 96 | ||||||
Nominal Capacity | Cooling | kW | 120.0 | 125.0 | 130.0 | 135.0 | ||
Heating | 135.0 | 140.0 | 145.0 | 150.0 | ||||
Electrical Characteristics | Power Consumption | Cooling | kW | 32.88 | 35.90 | 38.92 | 41.94 | |
Heating | 32.07 | 33.88 | 35.69 | 37.50 | ||||
Exterior Dimensions | HxWxD | mm | 2048x4050x720 | |||||
Net Weight | kg | 963 | ||||||
Refrigerant Charge | R410A | kg | 11.5x3 | |||||
Refrigerant Piping Size | Liquid Line | mm (in) | ⌀19.05 (3/4") | |||||
Gas Line | ⌀38.1 (1") [⌀34.92 (1 3/8")] | |||||||
Capacity Connection | % | 50~130 | ||||||
Number of Connectable Indoor Units | 80 |