| Line 130: | Line 130: | ||
* The refrigerant system is abnormal. | * The refrigerant system is abnormal. | ||
|- | |- | ||
| + | | | ||
| + | | ○ | ||
| + | | ` | ||
| + | | ○ | ||
| + | | Check Compressor Drive | ||
| + | | | ||
| + | * The outdoor drive board might have failed. | ||
| + | * The compressor might have failed. | ||
| + | * The outdoor control board might have failed. | ||
| + | |- | ||
| + | | | ||
| + | | ○ | ||
| + | | ○ | ||
| + | | ★ | ||
| + | | Outdoor Fan Motor Locked Rotor Protection | ||
| + | | | ||
| + | * The connection of the outdoor fan motor might be loose. | ||
| + | * There might be something obstructing the outdoor fan motor. | ||
| + | * The fan motor might have failed. | ||
| + | * The outdoor control board might have failed. | ||
| + | |- | ||
| + | | | ||
| + | | ` | ||
| + | | ★ | ||
| + | | ` | ||
| + | | Outdoor Coil Anti-Overload Protection With Cooling | ||
| + | | | ||
| + | * There might be too much refrigerant. | ||
| + | * The outdoor fan motor might have failed. | ||
| + | * The outdoor fan might be broken. | ||
| + | * The condensor might be dirty. | ||
| + | * The air inlet and outlet of the indoor and outdoor unit is abnormal. | ||
| + | |- | ||
| + | | | ||
| + | | ` | ||
| + | | ○ | ||
| + | | ` | ||
| + | | IPM Module Protection | ||
| + | | | ||
| + | * The IPM board might have failed. | ||
| + | * The outdoor fan might be broken. | ||
| + | * The outdoor fan motor might have failed. | ||
| + | * The outdoor fan might be obstructed. | ||
| + | * The condenser might be dirty. | ||
| + | * The outdoor unit might have been installed incorrectly. | ||
| + | |- | ||
| + | | | ||
| + | | ○ | ||
| + | | ` | ||
| + | | ` | ||
| + | | PFC Protection | ||
| + | | | ||
| + | * The PFC might have failed. | ||
| + | * The outdoor drive board might have failed. | ||
| + | |- | ||
| + | | | ||
| + | | ○ | ||
| + | | ★ | ||
| + | | ○ | ||
| + | | Compressor Pre-Heating Process | ||
| + | | | ||
| + | * This is a normal operation mode in cold weather. | ||
| + | |- | ||
| + | | | ||
| + | | ★ | ||
| + | | ` | ||
| + | | ○ | ||
| + | | Check Outdoor Board Chip | ||
| + | | | ||
| + | * The drive board might not be compatible with this unit. | ||
| + | * The compressor might not be compatible with this unit. | ||
| + | |- | ||
| + | | | ||
| + | | ★ | ||
| + | | ★ | ||
| + | | ○ | ||
| + | | AC Voltage Higher or Lower Protection | ||
| + | | | ||
| + | * The supply voltage is higher or lower than normal. | ||
| + | * The inner supply voltage of the unit is higher or lower than normal. | ||
| + | |- | ||
| + | | | ||
| + | | ○ | ||
| + | | ○ | ||
| + | | ` | ||
| + | | DC Compressor Start Failure | ||
| + | | | ||
| + | * The outdoor drive board might have failed. | ||
| + | * The compressor might have failed. | ||
| + | |- | ||
| + | | | ||
| + | | ★ | ||
| + | | ○ | ||
| + | | ○ | ||
| + | | Outdoor Ambient Temperature Too Low Protection | ||
| + | | | ||
| + | * Outdoor ambient temperature too low for operation. | ||
Revision as of 15:40, 19 April 2017
Note: ★ - Solid Light, ○ - Flashing Light, ` - Light is Off
| Error Code | Outdoor PCB LED lights | Error Description | Troubleshooting | ||
| LED1 | LED2 | LED3 | |||
| ` | ` | ` | Normal Operation | ||
| ★ | ` | ★ | Check Outdoor Coil Temperature Sensor |
| |
| ★ | ` | ` | Check Compressor Exhaust Temperature Sensor |
| |
| ` | ` | ○ | Communication Failure Between Indoor and Outdoor Unit |
| |
| ★ | ○ | ` | Current Overload Protection |
| |
| ★ | ○ | ★ | Maximum Current Protection |
| |
| ` | ★ | ★ | Communication Error Between Outdoor Unit Control Board and Driver Board |
| |
| ★ | ★ | ★ | Check Outdoor EEPROM |
| |
| ` | ○ | ★ | Compressor Exhaust Temperature Too High Protection |
| |
| ★ | ★ | ` | Check Outdoor Ambient Temperature Sensor |
| |
| ` | ★ | ○ | Compressor Shell Temperature Too High Protection |
| |
| ` | ○ | ○ | Anti-Freeze Protection (Cooling) or Overload Protection (Heating) in Indoor Unit |
| |
| ○ | ` | ○ | Check Compressor Drive |
| |
| ○ | ○ | ★ | Outdoor Fan Motor Locked Rotor Protection |
| |
| ` | ★ | ` | Outdoor Coil Anti-Overload Protection With Cooling |
| |
| ` | ○ | ` | IPM Module Protection |
| |
| ○ | ` | ` | PFC Protection |
| |
| ○ | ★ | ○ | Compressor Pre-Heating Process |
| |
| ★ | ` | ○ | Check Outdoor Board Chip |
| |
| ★ | ★ | ○ | AC Voltage Higher or Lower Protection |
| |
| ○ | ○ | ` | DC Compressor Start Failure |
| |
| ★ | ○ | ○ | Outdoor Ambient Temperature Too Low Protection |
|
|