Difference between revisions of "Blue Series 2 Outdoor Unit Troubleshooting"
From Technical Support Wiki
Line 26: | Line 26: | ||
* The outdoor coil temperature sensor might have failed. | * The outdoor coil temperature sensor might have failed. | ||
* The outdoor unit's main control board might have failed. | * The outdoor unit's main control board might have failed. | ||
+ | |- | ||
+ | | | ||
+ | | ★ | ||
+ | | ` | ||
+ | | ` | ||
+ | | Check Compressor Exhaust Temperature Sensor | ||
+ | | | ||
+ | * The compressor exhaust temperature sensor might be loose. | ||
+ | * The compressor exhaust temperature sensor might have failed. | ||
+ | * The outdoor unit's main control board might have failed. | ||
+ | |- | ||
+ | | | ||
+ | | ` | ||
+ | | ` | ||
+ | | ○ | ||
+ | | Communication Failure Between Indoor and Outdoor Unit | ||
+ | | | ||
+ | * The communication cable connection might be loose. | ||
+ | * The communication cable might have failed. | ||
+ | * The connection between the filter board and the outdoor control board might be incorrect or loose. | ||
+ | * The connection between the filter board and the terminal might be incorrect or loose. | ||
+ | * The indoor unit control board might have failed. | ||
+ | * The PFC board might have failed. | ||
+ | * The power board might have failed. | ||
+ | * The outdoor unit control board might have failed. | ||
+ | |- | ||
+ | | | ||
+ | | ★ | ||
+ | | ○ | ||
+ | | ` | ||
+ | | Current Overload Protection | ||
+ | | | ||
+ | * The fan motor might have run abnormally. | ||
+ | * The condenser and/or evaporator might be dirty. | ||
+ | * The air inlet and outlet might be abnormal. | ||
+ | |- | ||
+ | | | ||
+ | | ★ | ||
+ | | ○ | ||
+ | | ★ | ||
+ | | Maximum Current Protection | ||
+ | | | ||
+ | * The outdoor control board might have short-circuited. | ||
+ | * The drive board might have short-circuited. | ||
+ | * Other electrical components might have short-circuited. | ||
+ | |- | ||
+ | | | ||
+ | | ` | ||
+ | | ★ | ||
+ | | ★ | ||
+ | | Communication Error Between Outdoor Unit Control Board and Driver Board | ||
+ | | | ||
+ | * The connection between control board and driver board might be loose. | ||
+ | * Either the control or driver board might have failed. | ||
+ | |- | ||
+ | | | ||
+ | | ★ | ||
+ | | ★ | ||
+ | | ★ | ||
+ | | Check Outdoor EEPROM | ||
+ | | | ||
+ | * The EEPROM chip might be loose. | ||
+ | * The EEPROM chip might be inserted improperly. | ||
+ | * The EEPROM chip might have failed. | ||
+ | |- | ||
+ | | | ||
+ | | ` | ||
+ | | ○ | ||
+ | | ★ | ||
+ | | Compressor Exhaust Temperature Too High Protection | ||
+ | | | ||
+ | * The compressor exhaust temperature sensor might have failed. | ||
+ | * The unit has insufficient refrigerant. | ||
+ | |- | ||
+ | | | ||
+ | | ★ | ||
+ | | ★ | ||
+ | | ` | ||
+ | | Check Outdoor Ambient Temperature Sensor | ||
+ | | | ||
+ | * The outdoor ambient temperature sensor's connection might be loose. | ||
+ | * The outdoor ambient temperature sensor might have failed. | ||
+ | * The outdoor control board might have failed. | ||
+ | |- | ||
+ | | | ||
+ | | ` | ||
+ | | ★ | ||
+ | | ○ | ||
+ | | Compressor Shell Temperature Too High Protection | ||
+ | | | ||
+ | * The compressor exhaust temperature sensor might be loose. | ||
+ | * The unit has insufficient refrigerant. | ||
+ | |- | ||
+ | | | ||
+ | | ` | ||
+ | | ○ | ||
+ | | ○ | ||
+ | | Anti-Freeze Protection (Cooling) or Overload Protection (Heating) in Indoor Unit | ||
+ | | | ||
+ | * The indoor coil temperature sensor might be loose. | ||
+ | * The indoor coil temperature sensor might have failed. | ||
+ | * The indoor control board might have failed. | ||
+ | * The refrigerant system is abnormal. | ||
|- | |- |
Revision as of 15:19, 19 April 2017
Note: ★ - Solid Light, ○ - Flashing Light, ` - Light is Off
Error Code | Outdoor PCB LED lights | Error Description | Troubleshooting | ||
LED1 | LED2 | LED3 | |||
` | ` | ` | Normal Operation | ||
★ | ` | ★ | Check Outdoor Coil Temperature Sensor |
| |
★ | ` | ` | Check Compressor Exhaust Temperature Sensor |
| |
` | ` | ○ | Communication Failure Between Indoor and Outdoor Unit |
| |
★ | ○ | ` | Current Overload Protection |
| |
★ | ○ | ★ | Maximum Current Protection |
| |
` | ★ | ★ | Communication Error Between Outdoor Unit Control Board and Driver Board |
| |
★ | ★ | ★ | Check Outdoor EEPROM |
| |
` | ○ | ★ | Compressor Exhaust Temperature Too High Protection |
| |
★ | ★ | ` | Check Outdoor Ambient Temperature Sensor |
| |
` | ★ | ○ | Compressor Shell Temperature Too High Protection |
| |
` | ○ | ○ | Anti-Freeze Protection (Cooling) or Overload Protection (Heating) in Indoor Unit |
|