Difference between revisions of "Blue Series Troubleshooting (18K & 24K)"
From Technical Support Wiki
Line 26: | Line 26: | ||
| | | | ||
| off | | off | ||
− | | | + | | Blinking |
− | | | + | | Blinking |
− | | | + | | Blinking |
| During cooling and drying operation, all loads except the indoor fan stop operation. During heating operation, the entire unit stops. | | During cooling and drying operation, all loads except the indoor fan stop operation. During heating operation, the entire unit stops. | ||
| | | | ||
Line 60: | Line 60: | ||
| Off | | Off | ||
| On | | On | ||
− | | | + | | Blinking |
+ | | During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heating, all loads stop. | ||
+ | | Please refer to the [[:File:Service_Manual_Platinum.pdf|service manual]] | ||
+ | |- | ||
+ | | 4 | ||
+ | | Overcurrent protection | ||
+ | | E5 | ||
+ | | Off 3s and blink 5 times | ||
+ | | | ||
+ | | | ||
+ | | Off | ||
+ | | On | ||
+ | | Blinking | ||
+ | | Off | ||
+ | | During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heating, all loads stop. | ||
+ | | | ||
+ | * Supply voltage is unstable; | ||
+ | * Supply voltage is too low and load is too high; | ||
+ | * Evaporator is dirty; | ||
+ | |- | ||
+ | | 5 | ||
+ | | Communication malfunction | ||
+ | | E6 | ||
+ | | Off 3s and blink 6 times | ||
+ | | | ||
+ | | | ||
+ | | Off | ||
+ | | Off | ||
+ | | Off | ||
+ | | Blinking | ||
+ | | During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heating, all loads stop. | ||
+ | | Please refer to the [[:File:Service_Manual_Platinum.pdf|service manual]] | ||
+ | |- | ||
+ | | 7 | ||
+ | | High temperature resistant protection | ||
+ | | E8 | ||
+ | | Off 3s and blink 8 times | ||
+ | | | ||
+ | | | ||
+ | | On | ||
+ | | Off | ||
+ | | On | ||
+ | | On | ||
| During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heating, all loads stop. | | During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heating, all loads stop. | ||
| Please refer to the [[:File:Service_Manual_Platinum.pdf|service manual]] | | Please refer to the [[:File:Service_Manual_Platinum.pdf|service manual]] | ||
|- | |- |
Revision as of 17:44, 1 May 2014
NO. | Malfunction Name | Display Method of Indoor Unit | Display Method of Outdoor Unit | A/C Status | Possible Causes | ||||||
Dual-8 Code Display | Indicator Display | Indicator Display | |||||||||
Operation Indicator | Cooling Indicator | Heating Indicator | D40/D5 | D41/D6 | D42/D16 | D43/D30 | |||||
1 | System High Pressure Protection | E1 | Off 3s blink once | off | Blinking | Blinking | Blinking | During cooling and drying operation, all loads except the indoor fan stop operation. During heating operation, the entire unit stops. |
| ||
2 | Antifreezing protection | E2 | Off 3s and blink twice | On | Off | On | Off | During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. |
| ||
3 | High discharge temperature protection of compressor | E4 | Off 3s and blink 4 times | On | Off | On | Blinking | During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heating, all loads stop. | Please refer to the service manual | ||
4 | Overcurrent protection | E5 | Off 3s and blink 5 times | Off | On | Blinking | Off | During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heating, all loads stop. |
| ||
5 | Communication malfunction | E6 | Off 3s and blink 6 times | Off | Off | Off | Blinking | During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heating, all loads stop. | Please refer to the service manual | ||
7 | High temperature resistant protection | E8 | Off 3s and blink 8 times | On | Off | On | On | During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heating, all loads stop. | Please refer to the service manual |