Line 221: | Line 221: | ||
| During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heating, all loads stop. | | During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heating, all loads stop. | ||
| Outdoor temperature sensor hasn't been connected well or is damaged. | | Outdoor temperature sensor hasn't been connected well or is damaged. | ||
+ | |16 | ||
+ | | Outdoor discharge temperature sensor is open/short circuited | ||
+ | | F5 | ||
+ | | | ||
+ | | Off 3s and blink 5 times | ||
+ | | | ||
+ | | | ||
+ | | Off 3s and blink 7 times | ||
+ | | | ||
+ | | During cooling and drying operation, compressor will stop after operating for about 3 mins while indoor fan will operate. During heating operation, the complete unit will stop after operating for about 3 minutes. | ||
+ | | | ||
+ | * Outdoor temperature sensor hasn't been connected well or is damaged; | ||
+ | * The head of temperature sensor hasn't been inserted in to the copper tube; | ||
+ | |- | ||
+ | | 17 | ||
+ | | Limit/decrease frequency due to overload | ||
+ | | F6 | ||
+ | | | ||
+ | | Off 3s and blink 6 times | ||
+ | | | ||
+ | | | ||
+ | | Off 3s and blink 3 times | ||
+ | | | ||
+ | | All loads operate normally, while operation frequency for compressor is decreased. | ||
+ | | Please refer to malfunction analysis below. | ||
+ | |- | ||
+ | | 18 | ||
+ | | Decrease frequency due to overcurrent | ||
+ | | F8 | ||
+ | | | ||
+ | | Off 3s and blink 8 times | ||
+ | | | ||
+ | | | ||
+ | | Off 3s and blink once | ||
+ | | | ||
+ | | All loads operate normally, while operation frequency for compressor is decreased. | ||
+ | | The input supply voltage is too low; System pressure is too high and overload; | ||
+ | |- | ||
+ | | 19 | ||
+ | | Decrease frequency due to high air discharge | ||
+ | | F9 | ||
+ | | | ||
+ | | Off 3s and blink 9 times | ||
+ | | | ||
+ | | | ||
+ | | Off 3s and blink twice | ||
+ | | | ||
+ | | All loads operate normally, while operation frequency for compressor is decreased. | ||
+ | | | ||
+ | * Overload or temperature is too high; | ||
+ | * Refrigerant is insufficient; | ||
+ | * Malfunction of electric expansion valve (EKV); | ||
+ | |- | ||
+ | | 20 | ||
+ | | Limit/decrease frequency due to antifreezing | ||
+ | | FH | ||
+ | | | ||
+ | | Off 3s and blink twice | ||
+ | | Off 3s and blink twice | ||
+ | | | ||
+ | | Off 3s and blink 4 times | ||
+ | | | ||
+ | | All loads operate normally, while operation frequency for compressor is decreased. | ||
+ | | Poor air-return in indoor unit or fan speed is too low | ||
+ | |- | ||
+ | | 21 | ||
+ | | Voltage for DC bus-bar is too high | ||
+ | | PH | ||
+ | | | ||
+ | | Off 3s and blink 11 times | ||
+ | | | ||
+ | | Off 3s and blink 13 times | ||
+ | | | ||
+ | | | ||
+ | | During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heating, all loads stop. | ||
+ | | | ||
+ | * Measure the voltage of position L and N on the wiring board (XT). If the voltage is higher than 265V AC, turn on the units after the supply voltage is increased to the normal range. | ||
+ | * If the AC input is normal, measure the voltage of electrolytic capacitor C on control panel (AP1), if it is normal, there's a malfunction on the circuit. Please replace the control panel (AP1). | ||
+ | |- | ||
+ | | 22 | ||
+ | | Voltage of DC bus-bar is too low | ||
+ | | PL | ||
+ | | | ||
+ | | | ||
+ | | Off 3s and blink 21 times | ||
+ | | Off 3s and blink 12 times | ||
+ | | | ||
+ | | | ||
+ | | During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heating, all loads stop. | ||
+ | | | ||
+ | * Measure the voltage of position L and N on the wiring board (XT). If the voltage is higher than 150V AC, turn on the units after the supply voltage is increased to the normal range. | ||
+ | * If the AC input is normal, measure the voltage of electrolytic capacitor C on control panel (AP1), if it is normal, there's a malfunction on the circuit. Please replace the control panel (AP1). | ||
+ | |- | ||
+ | | 23 | ||
+ | | Compressor min frequence in test state | ||
+ | | P0 | ||
+ | | | ||
+ | | | ||
+ | | | ||
+ | | | ||
+ | | | ||
+ | | | ||
+ | | | ||
+ | | Shown during min. cooling or min. heating test | ||
+ | |- | ||
+ | | 24 | ||
+ | | Compressor rated frequence in test state | ||
+ | | P1 | ||
+ | | | ||
+ | | | ||
+ | | | ||
+ | | | ||
+ | | | ||
+ | | | ||
+ | | | ||
+ | | Shown during nominal cooling or nominal heating test | ||
+ | |- | ||
+ | | 25 | ||
+ | | Compressor max frequence in test state | ||
+ | | P2 | ||
+ | | | ||
+ | | | ||
+ | | | ||
+ | | | ||
+ | | | ||
+ | | | ||
+ | | | ||
+ | | Shown during max. cooling or max. heating test | ||
+ | |- | ||
+ | | 26 | ||
+ | | Compressor intermediate frequence in test state | ||
+ | | P3 | ||
+ | | | ||
+ | | | ||
+ | | | ||
+ | | | ||
+ | | | ||
+ | | | ||
+ | | | ||
+ | | Shown during middle cooling or middle heating test | ||
+ | |- | ||
+ | | 27 | ||
+ | | Compressor min frequence in test state | ||
+ | | P0 | ||
+ | | | ||
+ | | | ||
+ | | | ||
+ | | | ||
+ | | | ||
+ | | | ||
+ | | | ||
+ | | Shown during min. cooling or min. heating test | ||
+ | |- | ||
|} | |} |
Revision as of 18:13, 13 November 2013
NO. | Malfunction Name | Display Method of Indoor Unit | Display Method of Outdoor Unit | A/C Status | Possible Causes | ||||||||||||||||
Dual-8 Code Display | Indicator Display | Indicator Display | |||||||||||||||||||
Operation Indicator | Cooling Indicator | Heating Indicator | Yellow Indicator | Red Indicator | Green Indicator | ||||||||||||||||
1 | High pressure protection of system | E1 | Off 3s and blink once | During cooling and drying operation, all loads except the indoor fan stop operation. During heating operation, the entire unit stops. |
| ||||||||||||||||
2 | Antifreezing protection | E2 | Off 3s and blink twice | Off 3s and blink 3 times | During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. |
| |||||||||||||||
3 | System block or refrigerant leakage | E3 | Off 3s and blink 3 times | Off 3s and blink 9 times | Dual-8 code display will show E3 until the low pressure switch stops operation. |
| |||||||||||||||
4 | High discharge temperature protection of compressor | E4 | Off 3s and blink 4 times | Off 3s and blink 7 times | During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heating, all loads stop. | Please refer to malfunction analysis below. | |||||||||||||||
5 | Overcurrent protection | E5 | Off 3s and blink 5 times | Off 3s and blink 5 times | During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heating, all loads stop. |
| |||||||||||||||
6 | Communication malfunction | E6 | Off 3s and blink 6 times | Off | During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heating, all loads stop. | Please refer to malfunction analysis below. | |||||||||||||||
7 | High temperature resistant protection | E8 | Off 3s and blink 8 times | Off 3s and blink 6 times | During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heating, all loads stop. | Please refer to malfunction analysis below. | |||||||||||||||
8 | EEPROM malfunction | EE | Off 3s and blink 15 times | Off 3s and blink 11 times | During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heating, all loads stop. | Replace outdoor control panel AP1 | |||||||||||||||
9 | Limit/decrease frequency due to high temperature of module | EU | Off 3s and blink 6 times | Off 3s and blink 6 times | All loads operate normally, while operation frequency for compressor is decreased. | Discharging after the complete unit is de-energized for 20mins, check whether the thermal grease on IPM module of outdoor control panel AP1 is sufficient and whether the radiator is inserted tightly. If it is no use, please replace control panel AP1. | |||||||||||||||
10 | Malfunction protection of jumper cap | C5 | Off 3s and blink 15 times | Indoor unit does not respond to the wireless remote commands. |
| ||||||||||||||||
11 | Gathering refrigerant | F0 | Off 3s and blink once | Off 3s and blink once | When the outdoor unit receives the F0 signal, the system will be forced to run under cooling mode for gathering refrigerant. | Nominal cooling mode | |||||||||||||||
12 | Indoor ambient temperature sensor is open/short circuited | F1 | Off 3s and blink once | During cooling and drying operation, indoor unit operates while other loads will stop. During heating operation the complete unit will stop operation. |
| ||||||||||||||||
13 | Indoor evaporator temperature sensor is open/short circuited | F2 | Off 3s and blink twice | AC stops operation once it reaches the set temperature. Cooling/drying: internal fan motor stops operation while other loads stop operation. Heating: AC stops operation. |
| ||||||||||||||||
14 | Outdoor ambient temperature sensor is open/short circuited | F3 | Off 3s and blink 3 times | Off 3s and blink 6 times | During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heating, all loads stop. | Outdoor temperature sensor hasn't been connected well or is damaged. | |||||||||||||||
15 | Outdoor condenser temperature sensor is open/short circuited | F4 | Off 3s and blink 4 times | Off 3s and blink 5 times | During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heating, all loads stop. | Outdoor temperature sensor hasn't been connected well or is damaged. | 16 | Outdoor discharge temperature sensor is open/short circuited | F5 | Off 3s and blink 5 times | Off 3s and blink 7 times | During cooling and drying operation, compressor will stop after operating for about 3 mins while indoor fan will operate. During heating operation, the complete unit will stop after operating for about 3 minutes. |
| ||||||||
17 | Limit/decrease frequency due to overload | F6 | Off 3s and blink 6 times | Off 3s and blink 3 times | All loads operate normally, while operation frequency for compressor is decreased. | Please refer to malfunction analysis below. | |||||||||||||||
18 | Decrease frequency due to overcurrent | F8 | Off 3s and blink 8 times | Off 3s and blink once | All loads operate normally, while operation frequency for compressor is decreased. | The input supply voltage is too low; System pressure is too high and overload; | |||||||||||||||
19 | Decrease frequency due to high air discharge | F9 | Off 3s and blink 9 times | Off 3s and blink twice | All loads operate normally, while operation frequency for compressor is decreased. |
| |||||||||||||||
20 | Limit/decrease frequency due to antifreezing | FH | Off 3s and blink twice | Off 3s and blink twice | Off 3s and blink 4 times | All loads operate normally, while operation frequency for compressor is decreased. | Poor air-return in indoor unit or fan speed is too low | ||||||||||||||
21 | Voltage for DC bus-bar is too high | PH | Off 3s and blink 11 times | Off 3s and blink 13 times | During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heating, all loads stop. |
| |||||||||||||||
22 | Voltage of DC bus-bar is too low | PL | Off 3s and blink 21 times | Off 3s and blink 12 times | During cooling and drying operation, compressor and outdoor fan stop while indoor fan operates. During heating, all loads stop. |
| |||||||||||||||
23 | Compressor min frequence in test state | P0 | Shown during min. cooling or min. heating test | ||||||||||||||||||
24 | Compressor rated frequence in test state | P1 | Shown during nominal cooling or nominal heating test | ||||||||||||||||||
25 | Compressor max frequence in test state | P2 | Shown during max. cooling or max. heating test | ||||||||||||||||||
26 | Compressor intermediate frequence in test state | P3 | Shown during middle cooling or middle heating test | ||||||||||||||||||
27 | Compressor min frequence in test state | P0 | Shown during min. cooling or min. heating test |