Difference between revisions of "Mutli Plus ODU Drive Board Troubleshooting"
From Technical Support Wiki
(Created page with "{| class="wikitable" ! Fault Code ! Fault Description ! Possible Reason for Fault ! Possible Remedies |- | 1 | Q axis current detection fault | * Compressor wire connection i...") |
|||
| Line 109: | Line 109: | ||
|- | |- | ||
| 12 | | 12 | ||
| + | | PFC Over-current FO output low level | ||
| | | | ||
| + | * System overload, current too large | ||
| + | * Driver board fault | ||
| + | * PFC fault | ||
| + | | | ||
| + | * Check the system | ||
| + | * Change the driver board | ||
| + | * Change PFC | ||
| + | |- | ||
| + | | 13 | ||
| + | | Inverter over current | ||
| + | | | ||
| + | * System overload; current too large | ||
| + | * Driver board fault | ||
| + | * Compressor oil shortage; weakened crankshaft | ||
| + | * Compressor insulation fault | ||
| + | | | ||
| + | * Check the system | ||
| + | * Change the driver board | ||
| + | * Change the compressor | ||
| + | |- | ||
| + | | 14 | ||
| + | | PFC over current | ||
| + | | | ||
| + | * System overload; current too large | ||
| + | * Driver board fault | ||
| + | * PFC fault | ||
| + | | | ||
| + | * Check the system | ||
| + | * Change the driver board | ||
| + | * Change PFC | ||
| + | |- | ||
| + | | 15 | ||
| + | | Instantaneous power failure detection | ||
| + | | | ||
| + | * The power supply is not stable | ||
| + | * Instantaneous power failure | ||
| + | * Driver board fault | ||
| + | | | ||
| + | * Check the power supply | ||
| + | * Change the driver board | ||
| + | |- | ||
| + | | 16 | ||
| + | | DC voltage is too low | ||
| + | | | ||
| + | * Voltage input too low | ||
| + | * Driver board fault | ||
| + | | | ||
| + | * Check the power supply | ||
| + | * Change the driver board | ||
| + | |- | ||
| + | | 18 | ||
| + | | Driver board read EE data error | ||
| + | | | ||
| + | * EEPROM has no data or data error | ||
| + | * EEPROM circuit fault | ||
| + | | | ||
| + | * Change the EEPROM component | ||
| + | * Change the driver board | ||
| + | |- | ||
| + | | 19 | ||
| + | | PFC chip receive data fault | ||
| + | | Abnormal communication loop | ||
| + | | Change the driver board | ||
| + | |- | ||
| + | | 20 | ||
| + | | PFC soft start fault | ||
| + | | Abnormal PFC drive loop | ||
| + | | Change the driver board | ||
| + | |- | ||
| + | | 21 | ||
| + | | The compressor drive chip could not receive data from the PFC chip | ||
| + | | Communication loop fault | ||
| + | | Change the driver board | ||
| + | |- | ||
|} | |} | ||
Revision as of 13:54, 27 September 2019
| Fault Code | Fault Description | Possible Reason for Fault | Possible Remedies |
|---|---|---|---|
| 1 | Q axis current detection fault |
|
|
| 2 | Phase current detection fault |
|
|
| 3 | Initialization phase current imbalance |
|
|
| 4 | Speed estimation fault |
|
|
| 5 | IPM FO output fault |
|
|
| 6 | Communication between driver board and control board fault |
|
|
| 7 | AC voltage overload |
|
|
| 8 | DC voltage overload |
|
|
| 9 | AC voltage imbalance | Driver board fault | Replace the driver board |
| 10 | The PFC current detection circuit fault before the compressor is on | Bad driver board components | Replace the driver board |
| 11 | AC voltage supply in outrange |
|
|
| 12 | PFC Over-current FO output low level |
|
|
| 13 | Inverter over current |
|
|
| 14 | PFC over current |
|
|
| 15 | Instantaneous power failure detection |
|
|
| 16 | DC voltage is too low |
|
|
| 18 | Driver board read EE data error |
|
|
| 19 | PFC chip receive data fault | Abnormal communication loop | Change the driver board |
| 20 | PFC soft start fault | Abnormal PFC drive loop | Change the driver board |
| 21 | The compressor drive chip could not receive data from the PFC chip | Communication loop fault | Change the driver board |