Difference between revisions of "Multi Plus ODU Main Board Troubleshooting"
From Technical Support Wiki
Line 148: | Line 148: | ||
| Refer to "Overload in Cooling Mode addendum" | | Refer to "Overload in Cooling Mode addendum" | ||
|- | |- | ||
+ | | 17 | ||
+ | | Discharge temperature sensor fault | ||
+ | | | ||
+ | * The wiring of the discharge temperature sensor connection is loose | ||
+ | * The discharge temperature sensor has failed | ||
+ | * The sampling circuit is abnormal | ||
+ | | | ||
+ | * Reconnect the discharge temperature sensor | ||
+ | * Replace the discharge temperature sensor | ||
+ | * Replace the outdoor control board. | ||
+ | |- | ||
+ | | 18 | ||
+ | | AC voltage is abnormal | ||
+ | | | ||
+ | * The AC voltage > 275V or < 160V | ||
+ | * The AC voltage of sampling circuit on the driver board is abnormal | ||
+ | | | ||
+ | * Please check the power supply | ||
+ | * Replace the driver board | ||
+ | |- | ||
+ | | 19 | ||
+ | | Suction temperature sensor fault | ||
+ | | | ||
+ | * The wiring of the suction temperature sensor connection is loose | ||
+ | * The suction temperature sensor has failed | ||
+ | * The sampling circuit is abnormal | ||
+ | | | ||
+ | * Reconnect the suction temperature sensor | ||
+ | * Replace the suction temperature sensor | ||
+ | * Replace the outdoor control board | ||
+ | |- | ||
+ | | 22 | ||
+ | | Defrosting sensor fault | ||
+ | | | ||
+ | * The wiring of the defrosting sensor connection is loose | ||
+ | * The defrosting sensor has failed | ||
+ | * The sampling circuit is abnormal | ||
+ | | | ||
+ | * Reconnect the defrosting sensor | ||
+ | * Replace the defrosting sensor | ||
+ | * Replace the outdoor control board | ||
+ | |- | ||
+ | | 23 | ||
+ | | Expansion valve A tube (thin) sensor fault | ||
+ | | | ||
+ | * The wiring of the sensor for the expansion valve A(thin tube) connection is loose | ||
+ | * The sensor for the expansion A(thin tube) has failed | ||
+ | * The sampling circuit is abnormal | ||
+ | | | ||
+ | * Reconnect the sensor for the expansion valve A (thin tube) | ||
+ | * Replace the sensor for the expansion valve A (thin tube) | ||
+ | * Replace the outdoor control board | ||
+ | |- | ||
+ | | 24 | ||
+ | | Expansion valve B tube (thin) sensor fault | ||
+ | | | ||
+ | * The wiring of the sensor for the expansion valve B(thin tube) connection is loose | ||
+ | * The sensor for the expansion B(thin tube) has failed | ||
+ | * The sampling circuit is abnormal | ||
+ | | | ||
+ | * Reconnect the sensor for the expansion valve B (thin tube) | ||
+ | * Replace the sensor for the expansion valve B (thin tube) | ||
+ | * Replace the outdoor control board | ||
+ | |- | ||
+ | | 25 | ||
+ | | Expansion valve C tube (thin) sensor fault | ||
+ | | | ||
+ | * The wiring of the sensor for the expansion valve C(thin tube) connection is loose | ||
+ | * The sensor for the expansion C(thin tube) has failed | ||
+ | * The sampling circuit is abnormal | ||
+ | | | ||
+ | * Reconnect the sensor for the expansion valve C (thin tube) | ||
+ | * Replace the sensor for the expansion valve C (thin tube) | ||
+ | * Replace the outdoor control board | ||
+ | |- | ||
+ | | 26 | ||
+ | | Expansion valve D tube (thin) sensor fault | ||
+ | | | ||
+ | * The wiring of the sensor for the expansion valve D(thin tube) connection is loose | ||
+ | * The sensor for the expansion D(thin tube) has failed | ||
+ | * The sampling circuit is abnormal | ||
+ | | | ||
+ | * Reconnect the sensor for the expansion valve D (thin tube) | ||
+ | * Replace the sensor for the expansion valve D (thin tube) | ||
+ | * Replace the outdoor control board | ||
+ | |- | ||
+ | | 27 | ||
+ | | Expansion valve A tube (thick) sensor fault | ||
+ | | | ||
+ | * The wiring of the sensor for the expansion valve A(thick tube) connection is loose | ||
+ | * The sensor for the expansion A(thick tube) has failed | ||
+ | * The sampling circuit is abnormal | ||
+ | | | ||
+ | * Reconnect the sensor for the expansion valve A (thick tube) | ||
+ | * Replace the sensor for the expansion valve A (thick tube) | ||
+ | * Replace the outdoor control board | ||
+ | |- | ||
+ | | 28 | ||
+ | | Expansion valve B tube (thick) sensor fault | ||
+ | | | ||
+ | * The wiring of the sensor for the expansion valve B(thick tube) connection is loose | ||
+ | * The sensor for the expansion B(thick tube) has failed | ||
+ | * The sampling circuit is abnormal | ||
+ | | | ||
+ | * Reconnect the sensor for the expansion valve B (thick tube) | ||
+ | * Replace the sensor for the expansion valve B (thick tube) | ||
+ | * Replace the outdoor control board | ||
+ | |- | ||
+ | | 29 | ||
+ | | Expansion valve C tube (thick) sensor fault | ||
+ | | | ||
+ | * The wiring of the sensor for the expansion valve C(thick tube) connection is loose | ||
+ | * The sensor for the expansion C(thick tube) has failed | ||
+ | * The sampling circuit is abnormal | ||
+ | | | ||
+ | * Reconnect the sensor for the expansion valve C (thick tube) | ||
+ | * Replace the sensor for the expansion valve C (thick tube) | ||
+ | * Replace the outdoor control board | ||
+ | |- | ||
+ | | 30 | ||
+ | | Expansion valve D tube (thick) sensor fault | ||
+ | | | ||
+ | * The wiring of the sensor for the expansion valve D(thick tube) connection is loose | ||
+ | * The sensor for the expansion D(thick tube) has failed | ||
+ | * The sampling circuit is abnormal | ||
+ | | | ||
+ | * Reconnect the sensor for the expansion valve D (thick tube) | ||
+ | * Replace the sensor for the expansion valve D (thick tube) | ||
+ | * Replace the outdoor control board | ||
+ | |- | ||
+ | |||
|} | |} | ||
Go back to [[Multi Plus]] page | Go back to [[Multi Plus]] page |
Revision as of 12:40, 26 September 2019
Fault Code | Fault Description | Possible Reason for Fault | Potential Fixes |
---|---|---|---|
1 | Outdoor Ambient Temperature Sensor Fault |
|
|
2 | Outdoor Coil Temperature Sensor Fault |
|
|
3 | The Unit Over-Current Turn Off Fault |
|
|
4 | EEprom Data Error |
|
|
5 | Cooling Freezing
Protection (the indoor coil temperature is too low) or Heating Overload (indoor coil temperature is too high) |
|
|
7 | Communication fault between the indoor unit and outdoor unit |
outdoor unit is poor
|
|
13 | Compressor overheat protector device |
|
overload protector
protector
board |
14 | The high pressure switch operates or the unit turns off for high pressure protection |
|
|
15 | Low pressure switch protection or the unit turned off for low pressure protection |
|
board |
16 | Overload protection in cooling mode | System Overload | Refer to "Overload in Cooling Mode addendum" |
17 | Discharge temperature sensor fault |
|
|
18 | AC voltage is abnormal |
|
|
19 | Suction temperature sensor fault |
|
|
22 | Defrosting sensor fault |
|
|
23 | Expansion valve A tube (thin) sensor fault |
|
|
24 | Expansion valve B tube (thin) sensor fault |
|
|
25 | Expansion valve C tube (thin) sensor fault |
|
|
26 | Expansion valve D tube (thin) sensor fault |
|
|
27 | Expansion valve A tube (thick) sensor fault |
|
|
28 | Expansion valve B tube (thick) sensor fault |
|
|
29 | Expansion valve C tube (thick) sensor fault |
|
|
30 | Expansion valve D tube (thick) sensor fault |
|
|
Go back to Multi Plus page