Difference between revisions of "Multi Plus ODU Main Board Troubleshooting"

From Technical Support Wiki
Jump to: navigation, search
Line 27: Line 27:
 
* Replace the outdoor board
 
* Replace the outdoor board
 
|-
 
|-
 +
| 3
 +
| The Unit Over-Current Turn Off Fault
 +
|
 +
* Control board current sampling circuit has failed
 +
* The current is too high because the supply voltage is too low
 +
* The compressor is blocked
 +
* Overload in heating mode
 +
* Overload in cooling mode
 +
|-
 +
| 4
 +
| EEprom Data Error
 +
|
 +
* EE components have failed
 +
* EE components control circuit failed
 +
* EE components have been inserted incorrectly
 +
|
 +
* Replace the EE components
 +
* Replace the outdoor control board
 +
* Reassemble the EE components
 +
|-
 +
| 5
 +
|
 
|}
 
|}

Revision as of 18:07, 25 September 2019

Fault Code Fault Description Possible Reason for Fault Potential Fixes
1 Outdoor Ambient Temperature Sensor Fault
  • The outdoor ambient temperature sensor connection is loose
  • The outdoor ambient temperature sensor has failed
  • The sampling circuit has failed
  • Reconnect the outdoor ambient temperature sensor
  • Replace the outdoor ambient temperature sensor
  • Replace the outdoor board
2 Outdoor Coil Temperature Sensor Fault
  • The outdoor coil temperature sensor connection is loose
  • The outdoor coil temperature sensor has failed
  • The sampling circuit has failed
  • Reconnect the outdoor coil temperature sensor
  • Replace the outdoor coil temperature sensor
  • Replace the outdoor board
3 The Unit Over-Current Turn Off Fault
  • Control board current sampling circuit has failed
  • The current is too high because the supply voltage is too low
  • The compressor is blocked
  • Overload in heating mode
  • Overload in cooling mode
4 EEprom Data Error
  • EE components have failed
  • EE components control circuit failed
  • EE components have been inserted incorrectly
  • Replace the EE components
  • Replace the outdoor control board
  • Reassemble the EE components
5