Latest revision as of 14:40, 4 December 2018
This is the support page for the Heat Pump outdoor units for MHI VRF air conditioners.
| Heat Pump Systems (FDC) | |
| Voltage | 220V |
|---|---|
| Capacities (kW) | 40.0-56.0 |
| Heat Pump? | Yes |
Model Numbers
- FDC400KXZE1M
- FDC450KXZE1M
- FDC475KXZE1M
- FDC500KXZE1M
- FDC560KXZE1M
Specifications
| Item | Unit | FDC400KXZE1M | FDC450KXZE1M | FDC475KXZE1M | FDC500KXZE1M | FDC560KXZE1M | ||||
|---|---|---|---|---|---|---|---|---|---|---|
| Nominal Horse Power | 14HP | 16HP | 17HP | 18HP | 20HP | |||||
| Power Source | 3 Phase-3wire 220V, 60Hz | |||||||||
| Starting Current | A | 5 | 8 | |||||||
| Max Current | A | 52 | 59 | 62 | 66 | |||||
| Nominal Capacity | Cooling | kW | 40.0 | 45.0 | 47.5 | 50.0 | 56.0 | |||
| Heating | 45.0 | 50.0 | 53.0 | 56.0 | 63.0 | |||||
| Electrical Characteristics | Power Consumption | Cooling | kW | 10.96 | 13.98 | 13.98 | 13.97 | 16.62 | ||
| Heating | 10.69 | 12.50 | 13.00 | 13.49 | 15.95 | |||||
| Exterior Dimensions | HxWxD | mm | 2048x1350x720 | |||||||
| Net Weight | kg | 321 | 367 | |||||||
| Sound Pressure Level | Cooling/Heating | dB(A) | 61/62 | 61/62 | 61/62 | 61/62 | 61/62 | |||
| Refrigerant | Type/GWP | R410A/2088 | ||||||||
| Charge | kg/TCO2Eq | 11.5/24.012 | ||||||||
| Refrigerant Piping Size | Liquid Line | mm (in) | ⌀12.7 (1/2") | |||||||
| Gas Line | ⌀25.4 (1") [⌀28.58 (1 1/8")] | ⌀28.58 (1 1/8") | ||||||||
| Capacity Connection | % | 50~130 | ||||||||
| Number of Connectable Indoor Units | 34 | 39 | 41 | 43 | 48 | |||||