Difference between revisions of "MHI KXZ ODU2"
From Technical Support Wiki
(Created page with "This is the support page for the Micro Model Heat Pump outdoor units for MHI VRF air conditioners. {{Infobox | | bodyclass = infobox | name = Mitsubishi Heavy Industries...") |
|||
Line 6: | Line 6: | ||
| title = Mitsubishi Heavy Industries VRF | | title = Mitsubishi Heavy Industries VRF | ||
| subheader = Micro Model Heat Pump Systems (FDC) | | subheader = Micro Model Heat Pump Systems (FDC) | ||
− | | image = [[File:MHI- | + | | image = [[File:MHI-FDC-ODU-2-Featured.png|center|300px]] |
| header1 = | | header1 = |
Latest revision as of 14:38, 4 December 2018
This is the support page for the Micro Model Heat Pump outdoor units for MHI VRF air conditioners.
Micro Model Heat Pump Systems (FDC) | |
Voltage | 220V-380V |
---|---|
Capacities (kW) | 22.4-33.5 |
Heat Pump? | Yes |
Model Numbers
- FDC224KXE6M
- FDC280KXE6M
- FDC335KXE6M
- FDC224KXE6G
- FDC280KXE6G
- FDC335KXE6G
Specifications
Item | Unit | FDC224KXE6M | FDC280KXE6M | FDC335KXE6M | FDC224KXE6G | FDC280KXE6G | FDC335KXE6G | |||
---|---|---|---|---|---|---|---|---|---|---|
Nominal Horse Power | 8HP | 10HP | 12HP | 8HP | 10HP | 12HP | ||||
Power Source | 3 Phase-3wire 220V, 60Hz / 3 Phase-4wire 220V, 60Hz | 3 Phase 380V, 60Hz | ||||||||
Starting Current | A | 5 | 6 | 5 | ||||||
Max Current | A | 33 | 35 | 36 | 20 | 20 | 23 | |||
Nominal Capacity | Cooling | kW | 22.4 | 28.0 | 33.5 | 22.4 | 28.0 | 33.5 | ||
Heating | 25.0 | 31.5 | 37.5 | 25.0 | 31.5 | 37.5 | ||||
Electrical Characteristics | Power Consumption | Cooling | kW | 5.85 | 8.57 | 9.82 | 5.60 | 8.09 | 9.82 | |
Heating | 6.38 | 8.70 | 10.12 | 6.03 | 8.21 | 10.12 | ||||
Exterior Dimensions | HxWxD | mm | 1675x1080x480 | |||||||
Net Weight | kg | 212 | 215 | 218 | ||||||
Sound Pressure Level | Cooling/Heating | dB(A) | 58/58 | 59/60 | 61/61 | 58/58 | 59/60 | 61/61 | ||
Refrigerant | Type/GWP | R410A/2088 | ||||||||
Charge | kg/TCO2Eq | 11.5/24.012 | ||||||||
Refrigerant Piping Size | Liquid Line | mm (in) | ⌀9.52 (3/8") | ⌀12.7 (1/2") | ⌀9.52 (3/8") | ⌀12.7 (1/2") | ||||
Gas Line | ⌀19.05 (3/4") | ⌀22.22 (7/8") | ⌀25.4 (1") [⌀28.58 (1 1/8")] | ⌀19.05 (3/4") | ⌀22.22 (7/8") | ⌀25.4 (1") [⌀28.58 (1 1/8")] | ||||
Capacity Connection | % | 50~150 | ||||||||
Number of Connectable Indoor Units | 22 | 24 | 24 | 22 | 24 | 24 |