== Malfunction Indicators ==
 
{| class="wikitable"
 
| NO.
 
| Malfunction description
 
| LED1
 
| LED2
 
| LED3
 
| LED4
 
|-
 
| 0
 
| Normal stop
 
| off
 
| off
 
| off
 
| off
 
|-
 
| 1
 
| Compressor run
 
| on
 
| off
 
| off
 
| off
 
|-
 
| 2
 
| Compressor overload protection
 
| blinking
 
| off
 
| off
 
| off
 
|-
 
| 3
 
| Discharge protection
 
| off
 
| on
 
| off
 
| off
 
|-
 
| 4
 
| Outdoor unit overload protection
 
| on
 
| on
 
| off
 
| off
 
|-
 
| 5
 
| High pressure protection
 
| blinking
 
| on
 
| off
 
| off
 
|-
 
| 6
 
| Over current protection
 
| off
 
| blinking
 
| off
 
| off
 
|-
 
| 7
 
| IMP protection
 
| on
 
| blinking
 
| off
 
| off
 
|-
 
| 8
 
| IMP overheating protection
 
| blinking
 
| blinking
 
| off
 
| off
 
|-
 
| 9
 
| PFC protection (including PFC overheating protection)
 
| off
 
| off
 
| on
 
| off
 
|-
 
| 10
 
| Phase current protection
 
| on
 
| off
 
| on
 
| off
 
|-
 
| 11
 
| Over voltage protection
 
| blinking
 
| off
 
| on
 
| off
 
|-
 
| 12
 
| Insufficient voltage protection
 
| off
 
| on
 
| on
 
| off
 
|-
 
| 13
 
| Start failure
 
| on
 
| on
 
| on
 
| off
 
|-
 
| 14
 
| Compressor desynchronizing
 
| blinking
 
| on
 
| on
 
| off
 
|-
 
| 15
 
| Compressor phase-lacking protection
 
| off
 
| blinking
 
| on
 
| off
 
|-
 
| 16
 
| Compressor phase current detection malfunction
 
| on
 
| blinking
 
| on
 
| off
 
|-
 
| 17
 
| Memory chip mistake
 
| blinking
 
| blinking
 
| on
 
| off
 
|-
 
| 18
 
| DC power supply short-circuit
 
| off
 
| off
 
| blinking
 
| off
 
|-
 
| 19
 
| Defrosting
 
| on
 
| off
 
| blinking
 
| off
 
|-
 
| 20
 
| Oil return
 
| blinking
 
| off
 
| blinking
 
| off
 
|-
 
| 21
 
| Complete unit frequency restriction protection
 
| off
 
| on
 
| blinking
 
| off
 
|-
 
| 22
 
| Complete unit frequency dropping protection
 
| on
 
| on
 
| blinking
 
| off
 
|-
 
| 23
 
| Unit A frequency restriction or frequency dropping protection
 
| blinking
 
| on
 
| blinking
 
| off
 
|-
 
| 24
 
| Unit B frequency restriction or frequency dropping protection
 
| off
 
| blinking
 
| blinking
 
| off
 
|-
 
| 25
 
| Unit C frequency restriction or frequency dropping protection
 
| on
 
| blinking
 
| blinking
 
| off
 
|-
 
| 26
 
| Unit D frequency restriction or frequency dropping protection
 
| blinking
 
| blinking
 
| blinking
 
| off
 
|-
 
| 27
 
| Outdoor ambient temperature sensor protection
 
| off
 
| off
 
| off
 
| on
 
|-
 
| 28
 
| Outdoor tube temperature sensor protection
 
| on
 
| off
 
| off
 
| on
 
|-
 
| 29
 
| Discharge temperature sensor protection
 
| blinking
 
| off
 
| off
 
| on
 
|-
 
| 30
 
| IPM thermal resistance malfunction
 
| off
 
| on
 
| off
 
| on
 
|-
 
| 31
 
| Unit A liquid pipe temperature sensor malfunction
 
| on
 
| on
 
| off
 
| on
 
|-
 
| 32
 
| Unit A gas pipe temperature sensor malfunction
 
| blinking
 
| on
 
| off
 
| on
 
|-
 
| 33
 
| Unit B liquid pipe temperature sensor malfunction
 
| off
 
| blinking
 
| off
 
| on
 
|-
 
| 34
 
| Unit B gas pipe temperature sensor malfunction
 
| on
 
| blinking
 
| off
 
| on
 
|-
 
| 35
 
| Unit C liquid pipe temperature sensor malfunction
 
| blinking
 
| blinking
 
| off
 
| on
 
|-
 
| 36
 
| Unit C gas pipe temperature sensor malfunction
 
| off
 
| off
 
| on
 
| on
 
|-
 
| 37
 
| Unit D liquid pipe temperature sensor malfunction
 
| on
 
| off
 
| on
 
| on
 
|-
 
| 38
 
| Unit D gas pipe temperature sensor malfunction
 
| blinking
 
| off
 
| on
 
| on
 
|-
 
| 39
 
| Unit A mode conflict
 
| off
 
| on
 
| on
 
| on
 
|-
 
| 40
 
| Unit B mode conflict
 
| on
 
| on
 
| on
 
| on
 
|-
 
| 41
 
| Unit C mode conflict
 
| blinking
 
| on
 
| on
 
| on
 
|-
 
| 42
 
| Unit D mode conflict
 
| off
 
| blinking
 
| on
 
| on
 
|-
 
| 43
 
| Communication failure with Unit A
 
| on
 
| blinking
 
| on
 
| on
 
|-
 
| 44
 
| Communication failure with Unit B
 
| blinking
 
| blinking
 
| on
 
| on
 
|-
 
| 45
 
| Communication failure with Unit C
 
| off
 
| off
 
| blinking
 
| on
 
|-
 
| 46
 
| Communication failure with Unit D
 
| on
 
| off
 
| blinking
 
| on
 
|-
 
| 47
 
| Unit A freeze protection
 
| blinking
 
| off
 
| blinking
 
| on
 
|-
 
| 48
 
| Unit B freeze protection
 
| off
 
| on
 
| blinking
 
| on
 
|-
 
| 49
 
| Unit C freeze protection
 
| on
 
| on
 
| blinking
 
| on
 
|-
 
| 50
 
| Unit D freeze protection
 
| blinking
 
| on
 
| blinking
 
| on
 
|-
 
| 51
 
| Unit A overheating prevention protection
 
| off
 
| blinking
 
| blinking
 
| on
 
|-
 
| 52
 
| Unit B overheating prevention protection
 
| on
 
| blinking
 
| blinking
 
| on
 
|-
 
| 53
 
| Unit C overheating prevention protection
 
| blinking
 
| blinking
 
| blinking
 
| on
 
|-
 
| 54
 
| Unit D overheating prevention protection
 
| off
 
| off
 
| off
 
| blinking
 
|-
 
| 55
 
| Unit A communication wire misconnection or expansion valve malfunction
 
| on
 
| off
 
| off
 
| blinking
 
|-
 
| 56
 
| Unit B communication wire misconnection or expansion valve malfunction
 
| blinking
 
| off
 
| off
 
| blinking
 
|-
 
| 57
 
| Unit C communication wire misconnection or expansion valve malfunction
 
| off
 
| on
 
| off
 
| blinking
 
|-
 
| 58
 
| Unit D communication wire misconnection or expansion valve malfunction
 
| on
 
| on
 
| off
 
| blinking
 
|}
 
 