Difference between revisions of "Multi Plus ODU Main Board Troubleshooting"
From Technical Support Wiki
| (2 intermediate revisions by the same user not shown) | |||
| Line 278: | Line 278: | ||
* Replace the outdoor control board | * Replace the outdoor control board | ||
|- | |- | ||
| − | + | | 45 | |
| + | | IPM fault | ||
| + | | Please refer to "drive board fault codes" for more information | ||
| + | | Please refer to "drive board fault codes" for more information | ||
| + | |- | ||
| + | | 46 | ||
| + | | IPM and control board communication fault | ||
| + | | | ||
| + | * The cable between the control board and the driver board is loose | ||
| + | * The cable between the control board and the driver board has failed | ||
| + | * The driver board has failed | ||
| + | * The control board has failed | ||
| + | | | ||
| + | * Reconnect the cable between the control board and the driver board | ||
| + | * Replace the communication cable between the control board and the driver board | ||
| + | * Replace the driver board | ||
| + | * Replace the control board | ||
| + | |- | ||
| + | | 47 | ||
| + | | Discharge temperature too high fault | ||
| + | | | ||
| + | * Insufficient amount of refrigerant | ||
| + | * The refrigerant of the unit is not enough due to additional length of the installation pipe | ||
| + | * Throttling service has failed | ||
| + | * The outdoor ambient temperature is too high | ||
| + | | | ||
| + | * Check for refrigerant leaks. Fix leak and re-add refrigerant | ||
| + | * Add refrigerant according to additional installation pipe length | ||
| + | * Replace the throttling service (such as capillary, expansion valve) | ||
| + | |- | ||
| + | | 48 | ||
| + | | Outdoor DC fan motor fault (upper fan motor) | ||
| + | | | ||
| + | * The wiring of the upper DC fan motor is loose | ||
| + | * The cord of the upper DC fan motor has failed | ||
| + | * The upper DC fan motor has failed | ||
| + | * The drive circuit of the upper DC fan motor has failed | ||
| + | * The outdoor fan has been blocked | ||
| + | | | ||
| + | * Reconnect the wiring of the upper DC fan motor | ||
| + | * Replace the upper DC fan motor | ||
| + | * Replace the driver board of the fan motor | ||
| + | * Check the outdoor fan and ensure the outdoor fan can run normally | ||
| + | |- | ||
| + | | 49 | ||
| + | | Outdoor DC fan motor fault (lower fan motor) | ||
| + | | | ||
| + | * The wiring of the lower DC fan motor is loose | ||
| + | * The cord of the lower DC fan motor has failed | ||
| + | * The lower DC fan motor has failed | ||
| + | * The drive circuit of the lower DC fan motor has failed | ||
| + | * The outdoor fan has been blocked | ||
| + | | | ||
| + | * Reconnect the wiring of the lower DC fan motor | ||
| + | * Replace the lower DC fan motor | ||
| + | * Replace the driver board of the fan motor | ||
| + | * Check the outdoor fan and ensure the outdoor fan can run normally | ||
| + | |- | ||
| + | | 91 | ||
| + | | The unit turned off due to the IPM board over heating fault | ||
| + | | | ||
| + | * The outdoor ambient temperature is too high | ||
| + | * The speed of the outdoor fan motor is too low | ||
| + | * The outdoor unit has been installed incorrectly | ||
| + | * The supply power is too low | ||
| + | | | ||
| + | * Check the fan capacitor, and replace the fan capacitor if it has failed | ||
| + | * Reinstall the outdoor unit by referring to the installation user manual | ||
| + | |- | ||
| + | | 96 | ||
| + | | The refrigerant of the unit is not enough fault | ||
| + | | Insufficient amount of refrigerant | ||
| + | | | ||
| + | * Check for leaks | ||
| + | * Charge refrigerant to recommended levels | ||
| + | |- | ||
| + | | 97 | ||
| + | | 4-way valve communication failure fault | ||
| + | | | ||
| + | * The wiring of the 4-way valve coil is loose | ||
| + | * The 4-way valve coil has failed | ||
| + | * The 4-way valve has failed | ||
| + | * The driver board of the 4-way valve has failed | ||
| + | | | ||
| + | * Reconnect the wiring of the 4-way valve | ||
| + | * Replace the 4-way valve coil | ||
| + | * Replace the 4-way valve | ||
| + | * Replace the driver board of the 4-way valve | ||
| + | |} | ||
| + | {| class="wikitable" | ||
| + | ! colspan="3" | Overload in Cooling Mode Addendum | ||
| + | |- | ||
| + | ! Number | ||
| + | ! Cause | ||
| + | ! Corrective Measures | ||
| + | |- | ||
| + | | 1 | ||
| + | | Too much refrigerant | ||
| + | | Discharge refrigerant and refill to the appropriate level | ||
| + | |- | ||
| + | | 2 | ||
| + | | The outdoor ambient temperature is too high | ||
| + | | Please use within the rated ambient temperature range | ||
| + | |- | ||
| + | | 3 | ||
| + | | The air outlet and the air inlet of the outdoor unit has short circuited | ||
| + | | Adjust the installation according to the installation manual | ||
| + | |- | ||
| + | | 4 | ||
| + | | The outdoor heat exchanger is dirty | ||
| + | | Clean the heat exchanger of the outdoor unit | ||
| + | |- | ||
| + | | 5 | ||
| + | | The speed of the outdoor fan motor is too low | ||
| + | | Check the outdoor fan motor or fan capacitor | ||
| + | |- | ||
| + | | 6 | ||
| + | | The outdoor fan is broken or the outdoor fan is blocked | ||
| + | | Check the outdoor fan | ||
| + | |- | ||
| + | | 7 | ||
| + | | The air inlet and outlet and been blocked | ||
| + | | Remove the blockage | ||
| + | |- | ||
| + | | 8 | ||
| + | | The expansion valve or the capillary has failed | ||
| + | | Replace the expansion valve or the capillary | ||
| + | |- | ||
| + | |} | ||
| + | {| class="wikitable" | ||
| + | ! colspan="3" | Overload in Heating Mode Addendum | ||
| + | |- | ||
| + | ! Number | ||
| + | ! Cause | ||
| + | ! Corrective Measures | ||
| + | |- | ||
| + | | 1 | ||
| + | | Too much refrigerant | ||
| + | | Discharge refrigerant and refill to the appropriate level | ||
| + | |- | ||
| + | | 2 | ||
| + | | The indoor ambient temperature is too high | ||
| + | | Please use within the rated ambient temperature range | ||
| + | |- | ||
| + | | 3 | ||
| + | | The air outlet and the air inlet of the indoor unit has short circuited | ||
| + | | Adjust the installation according to the installation manual | ||
| + | |- | ||
| + | | 4 | ||
| + | | The indoor filter is dirty | ||
| + | | Clean the indoor filter | ||
| + | |- | ||
| + | | 5 | ||
| + | | The speed of the indoor fan motor is too low | ||
| + | | Check the indoor fan motor or fan capacitor | ||
| + | |- | ||
| + | | 6 | ||
| + | | The indoor fan is broken or the outdoor fan is blocked | ||
| + | | Check the indoor fan | ||
| + | |- | ||
| + | | 7 | ||
| + | | The air inlet and outlet and been blocked | ||
| + | | Remove the blockage | ||
| + | |- | ||
| + | | 8 | ||
| + | | The expansion valve or the capillary has failed | ||
| + | | Replace the expansion valve or the capillary | ||
| + | |- | ||
|} | |} | ||
Go back to [[Multi Plus]] page | Go back to [[Multi Plus]] page | ||
Latest revision as of 12:59, 27 September 2019
| Fault Code | Fault Description | Possible Reason for Fault | Potential Fixes |
|---|---|---|---|
| 1 | Outdoor Ambient Temperature Sensor Fault |
|
|
| 2 | Outdoor Coil Temperature Sensor Fault |
|
|
| 3 | The Unit Over-Current Turn Off Fault |
|
|
| 4 | EEprom Data Error |
|
|
| 5 | Cooling Freezing
Protection (the indoor coil temperature is too low) or Heating Overload (indoor coil temperature is too high) |
|
|
| 7 | Communication fault between the indoor unit and outdoor unit |
outdoor unit is poor
|
|
| 13 | Compressor overheat protector device |
|
overload protector
protector
board |
| 14 | The high pressure switch operates or the unit turns off for high pressure protection |
|
|
| 15 | Low pressure switch protection or the unit turned off for low pressure protection |
|
board |
| 16 | Overload protection in cooling mode | System Overload | Refer to "Overload in Cooling Mode addendum" |
| 17 | Discharge temperature sensor fault |
|
|
| 18 | AC voltage is abnormal |
|
|
| 19 | Suction temperature sensor fault |
|
|
| 22 | Defrosting sensor fault |
|
|
| 23 | Expansion valve A tube (thin) sensor fault |
|
|
| 24 | Expansion valve B tube (thin) sensor fault |
|
|
| 25 | Expansion valve C tube (thin) sensor fault |
|
|
| 26 | Expansion valve D tube (thin) sensor fault |
|
|
| 27 | Expansion valve A tube (thick) sensor fault |
|
|
| 28 | Expansion valve B tube (thick) sensor fault |
|
|
| 29 | Expansion valve C tube (thick) sensor fault |
|
|
| 30 | Expansion valve D tube (thick) sensor fault |
|
|
| 45 | IPM fault | Please refer to "drive board fault codes" for more information | Please refer to "drive board fault codes" for more information |
| 46 | IPM and control board communication fault |
|
|
| 47 | Discharge temperature too high fault |
|
|
| 48 | Outdoor DC fan motor fault (upper fan motor) |
|
|
| 49 | Outdoor DC fan motor fault (lower fan motor) |
|
|
| 91 | The unit turned off due to the IPM board over heating fault |
|
|
| 96 | The refrigerant of the unit is not enough fault | Insufficient amount of refrigerant |
|
| 97 | 4-way valve communication failure fault |
|
|
| Overload in Cooling Mode Addendum | ||
|---|---|---|
| Number | Cause | Corrective Measures |
| 1 | Too much refrigerant | Discharge refrigerant and refill to the appropriate level |
| 2 | The outdoor ambient temperature is too high | Please use within the rated ambient temperature range |
| 3 | The air outlet and the air inlet of the outdoor unit has short circuited | Adjust the installation according to the installation manual |
| 4 | The outdoor heat exchanger is dirty | Clean the heat exchanger of the outdoor unit |
| 5 | The speed of the outdoor fan motor is too low | Check the outdoor fan motor or fan capacitor |
| 6 | The outdoor fan is broken or the outdoor fan is blocked | Check the outdoor fan |
| 7 | The air inlet and outlet and been blocked | Remove the blockage |
| 8 | The expansion valve or the capillary has failed | Replace the expansion valve or the capillary |
| Overload in Heating Mode Addendum | ||
|---|---|---|
| Number | Cause | Corrective Measures |
| 1 | Too much refrigerant | Discharge refrigerant and refill to the appropriate level |
| 2 | The indoor ambient temperature is too high | Please use within the rated ambient temperature range |
| 3 | The air outlet and the air inlet of the indoor unit has short circuited | Adjust the installation according to the installation manual |
| 4 | The indoor filter is dirty | Clean the indoor filter |
| 5 | The speed of the indoor fan motor is too low | Check the indoor fan motor or fan capacitor |
| 6 | The indoor fan is broken or the outdoor fan is blocked | Check the indoor fan |
| 7 | The air inlet and outlet and been blocked | Remove the blockage |
| 8 | The expansion valve or the capillary has failed | Replace the expansion valve or the capillary |
Go back to Multi Plus page