Difference between revisions of "Multi Plus ODU Main Board Troubleshooting"
From Technical Support Wiki
(5 intermediate revisions by the same user not shown) | |||
Line 112: | Line 112: | ||
board | board | ||
|- | |- | ||
+ | | 14 | ||
+ | | The high pressure switch operates or the unit turns off for high pressure protection | ||
+ | | | ||
+ | * The wiring of the high pressure protector connection is loose; | ||
+ | * The high pressure protector has failed | ||
+ | * The outdoor control board is abnormal | ||
+ | * Overload in cooling | ||
+ | * Overload in heating | ||
+ | | | ||
+ | * Reconnect the high pressure protector | ||
+ | * Replace the high pressure protector | ||
+ | * Replace the outdoor control board | ||
+ | * Refer to "Overload in Cooling Mode addendum" | ||
+ | * Refer to "Overload in Heating Mode addendum" | ||
+ | |- | ||
+ | | 15 | ||
+ | | Low pressure switch protection or the unit turned off for low pressure protection | ||
+ | | | ||
+ | * The wiring of the low pressure switch is loose | ||
+ | * The low pressure switch has failed | ||
+ | * Insufficient amount of refrigerant | ||
+ | * Expansion valve failure in heating mode | ||
+ | * The outdoor control board is abnormal | ||
+ | | | ||
+ | * Reconnect the wiring of the low pressure switch | ||
+ | * Replace the low pressure switch | ||
+ | * Check for a refrigerant leak, fix it and re-add refrigerant | ||
+ | * Replace the expansion valve; | ||
+ | * Replace the outdoor control | ||
+ | board | ||
+ | |- | ||
+ | | 16 | ||
+ | | Overload protection in cooling mode | ||
+ | | System Overload | ||
+ | | Refer to "Overload in Cooling Mode addendum" | ||
+ | |- | ||
+ | | 17 | ||
+ | | Discharge temperature sensor fault | ||
+ | | | ||
+ | * The wiring of the discharge temperature sensor connection is loose | ||
+ | * The discharge temperature sensor has failed | ||
+ | * The sampling circuit is abnormal | ||
+ | | | ||
+ | * Reconnect the discharge temperature sensor | ||
+ | * Replace the discharge temperature sensor | ||
+ | * Replace the outdoor control board. | ||
+ | |- | ||
+ | | 18 | ||
+ | | AC voltage is abnormal | ||
+ | | | ||
+ | * The AC voltage > 275V or < 160V | ||
+ | * The AC voltage of sampling circuit on the driver board is abnormal | ||
+ | | | ||
+ | * Please check the power supply | ||
+ | * Replace the driver board | ||
+ | |- | ||
+ | | 19 | ||
+ | | Suction temperature sensor fault | ||
+ | | | ||
+ | * The wiring of the suction temperature sensor connection is loose | ||
+ | * The suction temperature sensor has failed | ||
+ | * The sampling circuit is abnormal | ||
+ | | | ||
+ | * Reconnect the suction temperature sensor | ||
+ | * Replace the suction temperature sensor | ||
+ | * Replace the outdoor control board | ||
+ | |- | ||
+ | | 22 | ||
+ | | Defrosting sensor fault | ||
+ | | | ||
+ | * The wiring of the defrosting sensor connection is loose | ||
+ | * The defrosting sensor has failed | ||
+ | * The sampling circuit is abnormal | ||
+ | | | ||
+ | * Reconnect the defrosting sensor | ||
+ | * Replace the defrosting sensor | ||
+ | * Replace the outdoor control board | ||
+ | |- | ||
+ | | 23 | ||
+ | | Expansion valve A tube (thin) sensor fault | ||
+ | | | ||
+ | * The wiring of the sensor for the expansion valve A(thin tube) connection is loose | ||
+ | * The sensor for the expansion A(thin tube) has failed | ||
+ | * The sampling circuit is abnormal | ||
+ | | | ||
+ | * Reconnect the sensor for the expansion valve A (thin tube) | ||
+ | * Replace the sensor for the expansion valve A (thin tube) | ||
+ | * Replace the outdoor control board | ||
+ | |- | ||
+ | | 24 | ||
+ | | Expansion valve B tube (thin) sensor fault | ||
+ | | | ||
+ | * The wiring of the sensor for the expansion valve B(thin tube) connection is loose | ||
+ | * The sensor for the expansion B(thin tube) has failed | ||
+ | * The sampling circuit is abnormal | ||
+ | | | ||
+ | * Reconnect the sensor for the expansion valve B (thin tube) | ||
+ | * Replace the sensor for the expansion valve B (thin tube) | ||
+ | * Replace the outdoor control board | ||
+ | |- | ||
+ | | 25 | ||
+ | | Expansion valve C tube (thin) sensor fault | ||
+ | | | ||
+ | * The wiring of the sensor for the expansion valve C(thin tube) connection is loose | ||
+ | * The sensor for the expansion C(thin tube) has failed | ||
+ | * The sampling circuit is abnormal | ||
+ | | | ||
+ | * Reconnect the sensor for the expansion valve C (thin tube) | ||
+ | * Replace the sensor for the expansion valve C (thin tube) | ||
+ | * Replace the outdoor control board | ||
+ | |- | ||
+ | | 26 | ||
+ | | Expansion valve D tube (thin) sensor fault | ||
+ | | | ||
+ | * The wiring of the sensor for the expansion valve D(thin tube) connection is loose | ||
+ | * The sensor for the expansion D(thin tube) has failed | ||
+ | * The sampling circuit is abnormal | ||
+ | | | ||
+ | * Reconnect the sensor for the expansion valve D (thin tube) | ||
+ | * Replace the sensor for the expansion valve D (thin tube) | ||
+ | * Replace the outdoor control board | ||
+ | |- | ||
+ | | 27 | ||
+ | | Expansion valve A tube (thick) sensor fault | ||
+ | | | ||
+ | * The wiring of the sensor for the expansion valve A(thick tube) connection is loose | ||
+ | * The sensor for the expansion A(thick tube) has failed | ||
+ | * The sampling circuit is abnormal | ||
+ | | | ||
+ | * Reconnect the sensor for the expansion valve A (thick tube) | ||
+ | * Replace the sensor for the expansion valve A (thick tube) | ||
+ | * Replace the outdoor control board | ||
+ | |- | ||
+ | | 28 | ||
+ | | Expansion valve B tube (thick) sensor fault | ||
+ | | | ||
+ | * The wiring of the sensor for the expansion valve B(thick tube) connection is loose | ||
+ | * The sensor for the expansion B(thick tube) has failed | ||
+ | * The sampling circuit is abnormal | ||
+ | | | ||
+ | * Reconnect the sensor for the expansion valve B (thick tube) | ||
+ | * Replace the sensor for the expansion valve B (thick tube) | ||
+ | * Replace the outdoor control board | ||
+ | |- | ||
+ | | 29 | ||
+ | | Expansion valve C tube (thick) sensor fault | ||
+ | | | ||
+ | * The wiring of the sensor for the expansion valve C(thick tube) connection is loose | ||
+ | * The sensor for the expansion C(thick tube) has failed | ||
+ | * The sampling circuit is abnormal | ||
+ | | | ||
+ | * Reconnect the sensor for the expansion valve C (thick tube) | ||
+ | * Replace the sensor for the expansion valve C (thick tube) | ||
+ | * Replace the outdoor control board | ||
+ | |- | ||
+ | | 30 | ||
+ | | Expansion valve D tube (thick) sensor fault | ||
+ | | | ||
+ | * The wiring of the sensor for the expansion valve D(thick tube) connection is loose | ||
+ | * The sensor for the expansion D(thick tube) has failed | ||
+ | * The sampling circuit is abnormal | ||
+ | | | ||
+ | * Reconnect the sensor for the expansion valve D (thick tube) | ||
+ | * Replace the sensor for the expansion valve D (thick tube) | ||
+ | * Replace the outdoor control board | ||
+ | |- | ||
+ | | 45 | ||
+ | | IPM fault | ||
+ | | Please refer to "drive board fault codes" for more information | ||
+ | | Please refer to "drive board fault codes" for more information | ||
+ | |- | ||
+ | | 46 | ||
+ | | IPM and control board communication fault | ||
+ | | | ||
+ | * The cable between the control board and the driver board is loose | ||
+ | * The cable between the control board and the driver board has failed | ||
+ | * The driver board has failed | ||
+ | * The control board has failed | ||
+ | | | ||
+ | * Reconnect the cable between the control board and the driver board | ||
+ | * Replace the communication cable between the control board and the driver board | ||
+ | * Replace the driver board | ||
+ | * Replace the control board | ||
+ | |- | ||
+ | | 47 | ||
+ | | Discharge temperature too high fault | ||
+ | | | ||
+ | * Insufficient amount of refrigerant | ||
+ | * The refrigerant of the unit is not enough due to additional length of the installation pipe | ||
+ | * Throttling service has failed | ||
+ | * The outdoor ambient temperature is too high | ||
+ | | | ||
+ | * Check for refrigerant leaks. Fix leak and re-add refrigerant | ||
+ | * Add refrigerant according to additional installation pipe length | ||
+ | * Replace the throttling service (such as capillary, expansion valve) | ||
+ | |- | ||
+ | | 48 | ||
+ | | Outdoor DC fan motor fault (upper fan motor) | ||
+ | | | ||
+ | * The wiring of the upper DC fan motor is loose | ||
+ | * The cord of the upper DC fan motor has failed | ||
+ | * The upper DC fan motor has failed | ||
+ | * The drive circuit of the upper DC fan motor has failed | ||
+ | * The outdoor fan has been blocked | ||
+ | | | ||
+ | * Reconnect the wiring of the upper DC fan motor | ||
+ | * Replace the upper DC fan motor | ||
+ | * Replace the driver board of the fan motor | ||
+ | * Check the outdoor fan and ensure the outdoor fan can run normally | ||
+ | |- | ||
+ | | 49 | ||
+ | | Outdoor DC fan motor fault (lower fan motor) | ||
+ | | | ||
+ | * The wiring of the lower DC fan motor is loose | ||
+ | * The cord of the lower DC fan motor has failed | ||
+ | * The lower DC fan motor has failed | ||
+ | * The drive circuit of the lower DC fan motor has failed | ||
+ | * The outdoor fan has been blocked | ||
+ | | | ||
+ | * Reconnect the wiring of the lower DC fan motor | ||
+ | * Replace the lower DC fan motor | ||
+ | * Replace the driver board of the fan motor | ||
+ | * Check the outdoor fan and ensure the outdoor fan can run normally | ||
+ | |- | ||
+ | | 91 | ||
+ | | The unit turned off due to the IPM board over heating fault | ||
+ | | | ||
+ | * The outdoor ambient temperature is too high | ||
+ | * The speed of the outdoor fan motor is too low | ||
+ | * The outdoor unit has been installed incorrectly | ||
+ | * The supply power is too low | ||
+ | | | ||
+ | * Check the fan capacitor, and replace the fan capacitor if it has failed | ||
+ | * Reinstall the outdoor unit by referring to the installation user manual | ||
+ | |- | ||
+ | | 96 | ||
+ | | The refrigerant of the unit is not enough fault | ||
+ | | Insufficient amount of refrigerant | ||
+ | | | ||
+ | * Check for leaks | ||
+ | * Charge refrigerant to recommended levels | ||
+ | |- | ||
+ | | 97 | ||
+ | | 4-way valve communication failure fault | ||
+ | | | ||
+ | * The wiring of the 4-way valve coil is loose | ||
+ | * The 4-way valve coil has failed | ||
+ | * The 4-way valve has failed | ||
+ | * The driver board of the 4-way valve has failed | ||
+ | | | ||
+ | * Reconnect the wiring of the 4-way valve | ||
+ | * Replace the 4-way valve coil | ||
+ | * Replace the 4-way valve | ||
+ | * Replace the driver board of the 4-way valve | ||
|} | |} | ||
+ | {| class="wikitable" | ||
+ | ! colspan="3" | Overload in Cooling Mode Addendum | ||
+ | |- | ||
+ | ! Number | ||
+ | ! Cause | ||
+ | ! Corrective Measures | ||
+ | |- | ||
+ | | 1 | ||
+ | | Too much refrigerant | ||
+ | | Discharge refrigerant and refill to the appropriate level | ||
+ | |- | ||
+ | | 2 | ||
+ | | The outdoor ambient temperature is too high | ||
+ | | Please use within the rated ambient temperature range | ||
+ | |- | ||
+ | | 3 | ||
+ | | The air outlet and the air inlet of the outdoor unit has short circuited | ||
+ | | Adjust the installation according to the installation manual | ||
+ | |- | ||
+ | | 4 | ||
+ | | The outdoor heat exchanger is dirty | ||
+ | | Clean the heat exchanger of the outdoor unit | ||
+ | |- | ||
+ | | 5 | ||
+ | | The speed of the outdoor fan motor is too low | ||
+ | | Check the outdoor fan motor or fan capacitor | ||
+ | |- | ||
+ | | 6 | ||
+ | | The outdoor fan is broken or the outdoor fan is blocked | ||
+ | | Check the outdoor fan | ||
+ | |- | ||
+ | | 7 | ||
+ | | The air inlet and outlet and been blocked | ||
+ | | Remove the blockage | ||
+ | |- | ||
+ | | 8 | ||
+ | | The expansion valve or the capillary has failed | ||
+ | | Replace the expansion valve or the capillary | ||
+ | |- | ||
+ | |} | ||
+ | {| class="wikitable" | ||
+ | ! colspan="3" | Overload in Heating Mode Addendum | ||
+ | |- | ||
+ | ! Number | ||
+ | ! Cause | ||
+ | ! Corrective Measures | ||
+ | |- | ||
+ | | 1 | ||
+ | | Too much refrigerant | ||
+ | | Discharge refrigerant and refill to the appropriate level | ||
+ | |- | ||
+ | | 2 | ||
+ | | The indoor ambient temperature is too high | ||
+ | | Please use within the rated ambient temperature range | ||
+ | |- | ||
+ | | 3 | ||
+ | | The air outlet and the air inlet of the indoor unit has short circuited | ||
+ | | Adjust the installation according to the installation manual | ||
+ | |- | ||
+ | | 4 | ||
+ | | The indoor filter is dirty | ||
+ | | Clean the indoor filter | ||
+ | |- | ||
+ | | 5 | ||
+ | | The speed of the indoor fan motor is too low | ||
+ | | Check the indoor fan motor or fan capacitor | ||
+ | |- | ||
+ | | 6 | ||
+ | | The indoor fan is broken or the outdoor fan is blocked | ||
+ | | Check the indoor fan | ||
+ | |- | ||
+ | | 7 | ||
+ | | The air inlet and outlet and been blocked | ||
+ | | Remove the blockage | ||
+ | |- | ||
+ | | 8 | ||
+ | | The expansion valve or the capillary has failed | ||
+ | | Replace the expansion valve or the capillary | ||
+ | |- | ||
+ | |} | ||
+ | Go back to [[Multi Plus]] page |
Latest revision as of 12:59, 27 September 2019
Fault Code | Fault Description | Possible Reason for Fault | Potential Fixes |
---|---|---|---|
1 | Outdoor Ambient Temperature Sensor Fault |
|
|
2 | Outdoor Coil Temperature Sensor Fault |
|
|
3 | The Unit Over-Current Turn Off Fault |
|
|
4 | EEprom Data Error |
|
|
5 | Cooling Freezing
Protection (the indoor coil temperature is too low) or Heating Overload (indoor coil temperature is too high) |
|
|
7 | Communication fault between the indoor unit and outdoor unit |
outdoor unit is poor
|
|
13 | Compressor overheat protector device |
|
overload protector
protector
board |
14 | The high pressure switch operates or the unit turns off for high pressure protection |
|
|
15 | Low pressure switch protection or the unit turned off for low pressure protection |
|
board |
16 | Overload protection in cooling mode | System Overload | Refer to "Overload in Cooling Mode addendum" |
17 | Discharge temperature sensor fault |
|
|
18 | AC voltage is abnormal |
|
|
19 | Suction temperature sensor fault |
|
|
22 | Defrosting sensor fault |
|
|
23 | Expansion valve A tube (thin) sensor fault |
|
|
24 | Expansion valve B tube (thin) sensor fault |
|
|
25 | Expansion valve C tube (thin) sensor fault |
|
|
26 | Expansion valve D tube (thin) sensor fault |
|
|
27 | Expansion valve A tube (thick) sensor fault |
|
|
28 | Expansion valve B tube (thick) sensor fault |
|
|
29 | Expansion valve C tube (thick) sensor fault |
|
|
30 | Expansion valve D tube (thick) sensor fault |
|
|
45 | IPM fault | Please refer to "drive board fault codes" for more information | Please refer to "drive board fault codes" for more information |
46 | IPM and control board communication fault |
|
|
47 | Discharge temperature too high fault |
|
|
48 | Outdoor DC fan motor fault (upper fan motor) |
|
|
49 | Outdoor DC fan motor fault (lower fan motor) |
|
|
91 | The unit turned off due to the IPM board over heating fault |
|
|
96 | The refrigerant of the unit is not enough fault | Insufficient amount of refrigerant |
|
97 | 4-way valve communication failure fault |
|
|
Overload in Cooling Mode Addendum | ||
---|---|---|
Number | Cause | Corrective Measures |
1 | Too much refrigerant | Discharge refrigerant and refill to the appropriate level |
2 | The outdoor ambient temperature is too high | Please use within the rated ambient temperature range |
3 | The air outlet and the air inlet of the outdoor unit has short circuited | Adjust the installation according to the installation manual |
4 | The outdoor heat exchanger is dirty | Clean the heat exchanger of the outdoor unit |
5 | The speed of the outdoor fan motor is too low | Check the outdoor fan motor or fan capacitor |
6 | The outdoor fan is broken or the outdoor fan is blocked | Check the outdoor fan |
7 | The air inlet and outlet and been blocked | Remove the blockage |
8 | The expansion valve or the capillary has failed | Replace the expansion valve or the capillary |
Overload in Heating Mode Addendum | ||
---|---|---|
Number | Cause | Corrective Measures |
1 | Too much refrigerant | Discharge refrigerant and refill to the appropriate level |
2 | The indoor ambient temperature is too high | Please use within the rated ambient temperature range |
3 | The air outlet and the air inlet of the indoor unit has short circuited | Adjust the installation according to the installation manual |
4 | The indoor filter is dirty | Clean the indoor filter |
5 | The speed of the indoor fan motor is too low | Check the indoor fan motor or fan capacitor |
6 | The indoor fan is broken or the outdoor fan is blocked | Check the indoor fan |
7 | The air inlet and outlet and been blocked | Remove the blockage |
8 | The expansion valve or the capillary has failed | Replace the expansion valve or the capillary |
Go back to Multi Plus page