+ | A16CI4H4R36 is the 16 SEER 36,000 Btu mini split condenser. [[File:36k-cond.png|right|thumb|36k Mini Split Evaporator]] | ||
== Malfunction Information Table == | == Malfunction Information Table == | ||
{| class="wikitable" | {| class="wikitable" | ||
Line 89: | Line 90: | ||
| The EEPROM on the outdoor PCB mainboard cannot read or write | | The EEPROM on the outdoor PCB mainboard cannot read or write | ||
|- | |- | ||
+ | | Stop for low voltage protection | ||
+ | | PL | ||
+ | | blink 12 times | ||
+ | | | ||
+ | | | ||
+ | | DC voltage is too low | ||
+ | |- | ||
+ | | Stop for high voltage protection | ||
+ | | PH | ||
+ | | blink 13 times | ||
+ | | | ||
+ | | | ||
+ | | DC voltage is too high | ||
+ | |- | ||
+ | | Stop for PFC circuit over current protection | ||
+ | | HC | ||
+ | | blink 14 times | ||
+ | | | ||
+ | | | ||
+ | | The PFC circuit over current | ||
+ | |- | ||
+ | | No feedback of indoor fan motor | ||
+ | | H6 | ||
+ | | / | ||
+ | | / | ||
+ | | / | ||
+ | | Indoor fan is abnormal | ||
+ | |- | ||
+ | | Stop for ID and OD doesn't match | ||
+ | | LP | ||
+ | | blink 16 times | ||
+ | | | ||
+ | | | ||
+ | | The indoor unit and outdoor unit does not match | ||
+ | |- | ||
+ | | Compressor frequence limit by over current protection | ||
+ | | | ||
+ | | | ||
+ | | blink 1 time | ||
+ | | | ||
+ | | Outdoor unit over current / ambient temperature is abominable | ||
+ | |- | ||
+ | | Compressor frequence limit by exhaust protection | ||
+ | | | ||
+ | | | ||
+ | | blink 2 times | ||
+ | | | ||
+ | | low refrigerant / capillary blocked up / ambient temperature is abominable | ||
+ | |- | ||
+ | | Compressor frequence limit by overload protection | ||
+ | | | ||
| | | | ||
− | + | | blink 3 times | |
− | + | | | |
− | + | | Ambient temperature is abominable / heat exchanger is blocked up | |
− | + | |- | |
+ | | Compressor frequence limit by anti-freezing protection | ||
+ | | | ||
+ | | | ||
+ | | blink 4 times | ||
+ | | | ||
+ | | Refrigerant leakage / indoor unit airflow blocked up / filter duty | ||
+ | |- | ||
+ | | Outdoor pipe temperature sensor malfunction | ||
+ | | F4 | ||
+ | | | ||
+ | | blink 5 times | ||
+ | | | ||
+ | | Open circuit or short circuit for outdoor condenser pipe temp. sensor | ||
+ | |- | ||
+ | | Outdoor ambient temperature sensor malfunction | ||
+ | | F3 | ||
+ | | | ||
+ | | blink 6 times | ||
+ | | | ||
+ | | Open circuit or short circuit for outdoor environment temp. sensor | ||
+ | |- | ||
+ | | Outdoor exhaust temperature sensor malfunction | ||
+ | | F5 | ||
+ | | | ||
+ | | blink 7 times | ||
+ | | | ||
+ | | Open circuit or short circuit for outdoor gas-discharge pipe temp. sensor | ||
+ | |- | ||
+ | | The indoor temp. reach to operate compressor (normal) | ||
+ | | | ||
+ | | | ||
+ | | blink 8 times | ||
+ | | | ||
+ | | Part of normal operation / Compressor preparing to run | ||
+ | |- | ||
+ | | Compressor frequence limit by IPM protection | ||
+ | | | ||
+ | | | ||
+ | | blink 11 times | ||
+ | | | ||
+ | | IPM module overheat / outdoor unit airflow blocked up | ||
+ | |- | ||
+ | | Compressor frequence limit by over power protection | ||
+ | | | ||
+ | | | ||
+ | | blink 13 times | ||
+ | | | ||
+ | | Ambient temperature is abominable | ||
+ | |- | ||
+ | | Indoor ambient temperature sensor malfunction | ||
+ | | F1 | ||
+ | | | ||
+ | | | ||
+ | | | ||
+ | | Open circuit or short circuit for indoor environment temp. sensor | ||
+ | |- | ||
+ | | Indoor tube temperature sensor malfunction | ||
+ | | F2 | ||
+ | | | ||
+ | | | ||
+ | | | ||
+ | | Open circuit or short circuit for indoor environment pipe temp. sensor | ||
+ | |- | ||
+ | | Stop for communication malfunction | ||
+ | | E6 | ||
+ | | | ||
+ | | | ||
+ | | off | ||
+ | | Communication line failure / main PCB failure / interfere source / connect line wrong | ||
+ | |- | ||
+ | | Communication is normal | ||
+ | | | ||
+ | | | ||
+ | | | ||
+ | | blink 1 time | ||
+ | | Communication is normal | ||
+ | |- | ||
+ | | Jumper cap malfunction protection | ||
+ | | C5 | ||
+ | | | ||
+ | | | ||
+ | | | ||
+ | | The jumper misfit the main board | ||
+ | |- | ||
+ | | No feedback from outdoor fan motor | ||
+ | | | ||
+ | | | ||
+ | | blink 14 times | ||
+ | | | ||
+ | | | ||
+ | |- | ||
+ | | High pressure protection | ||
+ | | E1 | ||
+ | | | ||
+ | | blink 16 times | ||
+ | | | ||
+ | | | ||
+ | |- | ||
+ | | colspan="6"|Note: The lamps blink 0.5s on, 0.5s off. There is a 2s off interval between error codes. | ||
+ | |} | ||
+ | == Wiring Diagram == | ||
+ | [[File:Mini-36K-ODU-WD.jpg|none|thumb|500px|A16CI4H4R36 Wiring Diagram]] | ||
+ | == Exploded View and Parts List == | ||
+ | [[File:Mini-36K-ODU-EV.jpg|thumb|500px|A16CI4H4R36 Exploded View]] | ||
+ | {| class="wikitable" | ||
+ | ! Number | ||
+ | ! Part Name | ||
+ | |- | ||
+ | | 1 | ||
+ | | Front Grill | ||
+ | |- | ||
+ | | 2 | ||
+ | | Cabinet | ||
+ | |- | ||
+ | | 3 | ||
+ | | Front Side Plate | ||
+ | |- | ||
+ | | 4 | ||
+ | | Axial Flow Fan | ||
+ | |- | ||
+ | | 5 | ||
+ | | Drainage Plug | ||
+ | |- | ||
+ | | 6 | ||
+ | | Chassis Sub-Assy | ||
+ | |- | ||
+ | | 7 | ||
+ | | Drainage Connector | ||
+ | |- | ||
+ | | 8 | ||
+ | | Compressor Gasket | ||
+ | |- | ||
+ | | 9 | ||
+ | | Compressor and Fittings | ||
+ | |- | ||
+ | | 10 | ||
+ | | Electrical Heater | ||
+ | |- | ||
+ | | 11 | ||
+ | | Magnet Coil | ||
+ | |- | ||
+ | | 12 | ||
+ | | 4-Way Valve Assy | ||
+ | |- | ||
+ | | 13 | ||
+ | | Right Side Plate | ||
+ | |- | ||
+ | | 14 | ||
+ | | Valve Support Assy | ||
+ | |- | ||
+ | | 15 | ||
+ | | Cut-Off Valve | ||
+ | |- | ||
+ | | 16 | ||
+ | | Valve Cover | ||
+ | |- | ||
+ | | 17 | ||
+ | | Retaining Plate | ||
+ | |- | ||
+ | | 18 | ||
+ | | Handle Assy | ||
+ | |- | ||
+ | | 19 | ||
+ | | Wiring Clamp | ||
+ | |- | ||
+ | | 20 | ||
+ | | Capillary Sub-Assy | ||
+ | |- | ||
+ | | 21 | ||
+ | | Temperature Sensor | ||
+ | |- | ||
+ | | 22 | ||
+ | | Rear Grill | ||
+ | |- | ||
+ | | 23 | ||
+ | | Condenser Assy | ||
+ | |- | ||
+ | | 24 | ||
+ | | Clapboard | ||
+ | |- | ||
+ | | 25 | ||
+ | | Condenser Support Plate | ||
+ | |- | ||
+ | | 26 | ||
+ | | Motor Support Sub-Assy | ||
+ | |- | ||
+ | | 27 | ||
+ | | Top Cover Sub-Assy | ||
+ | |- | ||
+ | | 28 | ||
+ | | Electric Box Cover | ||
+ | |- | ||
+ | | 29 | ||
+ | | Reactor | ||
+ | |- | ||
+ | | 30 | ||
+ | | Electric Box Sub-Assy | ||
+ | |- | ||
+ | | 31 | ||
+ | | Pass Wire Ring Sub-Assy | ||
+ | |- | ||
+ | | 32 | ||
+ | | Left Handle | ||
+ | |- | ||
+ | | 33 | ||
+ | | Left Side Plate | ||
+ | |- | ||
+ | | 34 | ||
+ | | Fan Motor | ||
+ | |- | ||
+ | | 35 | ||
+ | | Electric Box Cover | ||
+ | |- | ||
+ | | 36 | ||
+ | | Main Board | ||
+ | |- | ||
+ | | 37 | ||
+ | | Electric Box | ||
+ | |- | ||
+ | | 38 | ||
+ | | Radiator | ||
+ | |- | ||
+ | | 39 | ||
+ | | Terminal Board | ||
+ | |- | ||
+ | | 40 | ||
+ | | Electric Box Assy | ||
+ | |- | ||
+ | | 41 | ||
+ | | Capillary Sub-Assy (Oil Returning) | ||
+ | |- | ||
+ | | 42 | ||
+ | | Electrical Heater (Chassis) | ||
+ | |} | ||
+ | == Piping Sizes == | ||
+ | {| class="wikitable" | ||
+ | ! Liquid Side | ||
+ | ! Gas Side | ||
+ | |- | ||
+ | | 1/4" | ||
+ | | 5/8" | ||
|} | |} | ||
+ | == Accessories == | ||
+ | *[[Wall Bracket (QBR-19.5)]] | ||
+ | *[[Universal Remote (QTH-4000)]] |
Latest revision as of 15:20, 16 December 2013
A16CI4H4R36 is the 16 SEER 36,000 Btu mini split condenser.
Malfunction Information Table
Name of Malfunction | Display of indoor unit | State of the lamps on the outdoor unit PCB | |||
Error Code | Yellow | Red | Green | Reasons | |
Compressor running (normal) | blink 1 time | Part of normal operation | |||
Automatic defrosting (normal) | H1 | blink 2 times | Part of normal operation | ||
Anti-freezing protection | E2 | blink 3 times | Refrigerant leakage / indoor unit airflow blocked up / filter duty | ||
Stop for IPM module protection (over current) | H5 | blink 4 times | IPM model over current / outdoor unit air flow blocked up | ||
Stop for over current protection | E5 | blink 5 times | Outdoor unit over current / ambient temperature is abominable | ||
Overload protection | H4 | blink 6 times | Ambient temperature is abominable / heat exchanger is blocked up | ||
Stop for exhaust protection | E4 | blink 7 times | low refrigerant / capillary blocked up / ambient temperature is abominable | ||
Stop for compressor overload protection | H3 | blink 8 times | Compressor shell overheat / low refrigerant / capillary blocked up | ||
Stop for overpower protection | L9 | blink 9 times | Ambient temperature is abominable | ||
Stop for IPM module protection (overheat) | H5 | blink 10 times | IPM module overheat / outdoor unit airflow blocked up | ||
Stop for EEPROM read-write function | EE | blink 11 times | The EEPROM on the outdoor PCB mainboard cannot read or write | ||
Stop for low voltage protection | PL | blink 12 times | DC voltage is too low | ||
Stop for high voltage protection | PH | blink 13 times | DC voltage is too high | ||
Stop for PFC circuit over current protection | HC | blink 14 times | The PFC circuit over current | ||
No feedback of indoor fan motor | H6 | / | / | / | Indoor fan is abnormal |
Stop for ID and OD doesn't match | LP | blink 16 times | The indoor unit and outdoor unit does not match | ||
Compressor frequence limit by over current protection | blink 1 time | Outdoor unit over current / ambient temperature is abominable | |||
Compressor frequence limit by exhaust protection | blink 2 times | low refrigerant / capillary blocked up / ambient temperature is abominable | |||
Compressor frequence limit by overload protection | blink 3 times | Ambient temperature is abominable / heat exchanger is blocked up | |||
Compressor frequence limit by anti-freezing protection | blink 4 times | Refrigerant leakage / indoor unit airflow blocked up / filter duty | |||
Outdoor pipe temperature sensor malfunction | F4 | blink 5 times | Open circuit or short circuit for outdoor condenser pipe temp. sensor | ||
Outdoor ambient temperature sensor malfunction | F3 | blink 6 times | Open circuit or short circuit for outdoor environment temp. sensor | ||
Outdoor exhaust temperature sensor malfunction | F5 | blink 7 times | Open circuit or short circuit for outdoor gas-discharge pipe temp. sensor | ||
The indoor temp. reach to operate compressor (normal) | blink 8 times | Part of normal operation / Compressor preparing to run | |||
Compressor frequence limit by IPM protection | blink 11 times | IPM module overheat / outdoor unit airflow blocked up | |||
Compressor frequence limit by over power protection | blink 13 times | Ambient temperature is abominable | |||
Indoor ambient temperature sensor malfunction | F1 | Open circuit or short circuit for indoor environment temp. sensor | |||
Indoor tube temperature sensor malfunction | F2 | Open circuit or short circuit for indoor environment pipe temp. sensor | |||
Stop for communication malfunction | E6 | off | Communication line failure / main PCB failure / interfere source / connect line wrong | ||
Communication is normal | blink 1 time | Communication is normal | |||
Jumper cap malfunction protection | C5 | The jumper misfit the main board | |||
No feedback from outdoor fan motor | blink 14 times | ||||
High pressure protection | E1 | blink 16 times | |||
Note: The lamps blink 0.5s on, 0.5s off. There is a 2s off interval between error codes. |
Wiring Diagram
Exploded View and Parts List
Number | Part Name |
---|---|
1 | Front Grill |
2 | Cabinet |
3 | Front Side Plate |
4 | Axial Flow Fan |
5 | Drainage Plug |
6 | Chassis Sub-Assy |
7 | Drainage Connector |
8 | Compressor Gasket |
9 | Compressor and Fittings |
10 | Electrical Heater |
11 | Magnet Coil |
12 | 4-Way Valve Assy |
13 | Right Side Plate |
14 | Valve Support Assy |
15 | Cut-Off Valve |
16 | Valve Cover |
17 | Retaining Plate |
18 | Handle Assy |
19 | Wiring Clamp |
20 | Capillary Sub-Assy |
21 | Temperature Sensor |
22 | Rear Grill |
23 | Condenser Assy |
24 | Clapboard |
25 | Condenser Support Plate |
26 | Motor Support Sub-Assy |
27 | Top Cover Sub-Assy |
28 | Electric Box Cover |
29 | Reactor |
30 | Electric Box Sub-Assy |
31 | Pass Wire Ring Sub-Assy |
32 | Left Handle |
33 | Left Side Plate |
34 | Fan Motor |
35 | Electric Box Cover |
36 | Main Board |
37 | Electric Box |
38 | Radiator |
39 | Terminal Board |
40 | Electric Box Assy |
41 | Capillary Sub-Assy (Oil Returning) |
42 | Electrical Heater (Chassis) |
Piping Sizes
Liquid Side | Gas Side |
---|---|
1/4" | 5/8" |