A16CI4H4R36 is the 16 SEER 36,000 Btu mini split condenser. [[File:36k-cond.png|right|thumb|36k Mini Split Evaporator]]
 
== Malfunction Information Table ==
 
== Malfunction Information Table ==
 
{| class="wikitable"
 
{| class="wikitable"
Line 12: Line 13:
 
| Reasons
 
| Reasons
 
|-
 
|-
 
+
| Compressor running (normal)
 +
|
 +
| blink 1 time
 +
|
 +
|
 +
| Part of normal operation
 +
|-
 +
| Automatic defrosting (normal)
 +
| H1
 +
| blink 2 times
 +
|
 +
|
 +
| Part of normal operation
 +
|-
 +
| Anti-freezing protection
 +
| E2
 +
| blink 3 times
 +
|
 +
|
 +
| Refrigerant leakage / indoor unit airflow blocked up / filter duty
 +
|-
 +
| Stop for IPM module protection (over current)
 +
| H5
 +
| blink 4 times
 +
|
 +
|
 +
| IPM model over current / outdoor unit air flow blocked up
 +
|-
 +
| Stop for over current protection
 +
| E5
 +
| blink 5 times
 +
|
 +
|
 +
| Outdoor unit over current / ambient temperature is abominable
 +
|-
 +
| Overload protection
 +
| H4
 +
| blink 6 times
 +
|
 +
|
 +
| Ambient temperature is abominable / heat exchanger is blocked up
 +
|-
 +
| Stop for exhaust protection
 +
| E4
 +
| blink 7 times
 +
|
 +
|
 +
| low refrigerant / capillary blocked up / ambient temperature is abominable
 +
|-
 +
| Stop for compressor overload protection
 +
| H3
 +
| blink 8 times
 +
|
 +
|
 +
| Compressor shell overheat / low refrigerant / capillary blocked up
 +
|-
 +
| Stop for overpower protection
 +
| L9
 +
| blink 9 times
 +
|
 +
|
 +
| Ambient temperature is abominable
 +
|-
 +
| Stop for IPM module protection (overheat)
 +
| H5
 +
| blink 10 times
 +
|
 +
|
 +
| IPM module overheat / outdoor unit airflow blocked up
 +
|-
 +
| Stop for EEPROM read-write function
 +
| EE
 +
| blink 11 times
 +
|
 +
|
 +
| The EEPROM on the outdoor PCB mainboard cannot read or write
 +
|-
 +
| Stop for low voltage protection
 +
| PL
 +
| blink 12 times
 +
|
 +
|
 +
| DC voltage is too low
 +
|-
 +
| Stop for high voltage protection
 +
| PH
 +
| blink 13 times
 +
|
 +
|
 +
| DC voltage is too high
 +
|-
 +
| Stop for PFC circuit over current protection
 +
| HC
 +
| blink 14 times
 +
|
 +
|
 +
| The PFC circuit over current
 +
|-
 +
| No feedback of indoor fan motor
 +
| H6
 +
| /
 +
| /
 +
| /
 +
| Indoor fan is abnormal
 +
|-
 +
| Stop for ID and OD doesn't match
 +
| LP
 +
| blink 16 times
 +
|
 +
|
 +
| The indoor unit and outdoor unit does not match
 +
|-
 +
| Compressor frequence limit by over current protection
 +
|
 +
|
 +
| blink 1 time
 +
|
 +
| Outdoor unit over current / ambient temperature is abominable
 +
|-
 +
| Compressor frequence limit by exhaust protection
 +
|
 +
|
 +
| blink 2 times
 +
|
 +
| low refrigerant / capillary blocked up / ambient temperature is abominable
 +
|-
 +
| Compressor frequence limit by overload protection
 +
|
 +
|
 +
| blink 3 times
 +
|
 +
| Ambient temperature is abominable / heat exchanger is blocked up
 +
|-
 +
| Compressor frequence limit by anti-freezing protection
 +
|
 +
|
 +
| blink 4 times
 +
|
 +
| Refrigerant leakage / indoor unit airflow blocked up / filter duty
 +
|-
 +
| Outdoor pipe temperature sensor malfunction
 +
| F4
 +
|
 +
| blink 5 times
 +
|
 +
| Open circuit or short circuit for outdoor condenser pipe temp. sensor
 +
|-
 +
| Outdoor ambient temperature sensor malfunction
 +
| F3
 +
|
 +
| blink 6 times
 +
|
 +
| Open circuit or short circuit for outdoor environment temp. sensor
 +
|-
 +
| Outdoor exhaust temperature sensor malfunction
 +
| F5
 +
|
 +
| blink 7 times
 +
|
 +
| Open circuit or short circuit for outdoor gas-discharge pipe temp. sensor
 +
|-
 +
| The indoor temp. reach to operate compressor (normal)
 +
|
 +
|
 +
| blink 8 times
 +
|
 +
| Part of normal operation / Compressor preparing to run
 +
|-
 +
| Compressor frequence limit by IPM protection
 +
|
 +
|
 +
| blink 11 times
 +
|
 +
| IPM module overheat / outdoor unit airflow blocked up
 +
|-
 +
| Compressor frequence limit by over power protection
 +
|
 +
|
 +
| blink 13 times
 +
|
 +
| Ambient temperature is abominable
 +
|-
 +
| Indoor ambient temperature sensor malfunction
 +
| F1
 +
|
 +
|
 +
|
 +
| Open circuit or short circuit for indoor environment temp. sensor
 +
|-
 +
| Indoor tube temperature sensor malfunction
 +
| F2
 +
|
 +
|
 +
|
 +
| Open circuit or short circuit for indoor environment pipe temp. sensor
 +
|-
 +
| Stop for communication malfunction
 +
| E6
 +
|
 +
|
 +
| off
 +
| Communication line failure / main PCB failure / interfere source / connect line wrong
 +
|-
 +
| Communication is normal
 +
|
 +
|
 +
|
 +
| blink 1 time
 +
| Communication is normal
 +
|-
 +
| Jumper cap malfunction protection
 +
| C5
 +
|
 +
|
 +
|
 +
| The jumper misfit the main board
 +
|-
 +
| No feedback from outdoor fan motor
 +
|
 +
|
 +
| blink 14 times
 +
|
 +
|
 +
|-
 +
| High pressure protection
 +
| E1
 +
|
 +
| blink 16 times
 +
|
 +
|
 +
|-
 +
| colspan="6"|Note: The lamps blink 0.5s on, 0.5s off. There is a 2s off interval between error codes.
 +
|}
 +
== Wiring Diagram ==
 +
[[File:Mini-36K-ODU-WD.jpg|none|thumb|500px|A16CI4H4R36 Wiring Diagram]]
 +
== Exploded View and Parts List ==
 +
[[File:Mini-36K-ODU-EV.jpg|thumb|500px|A16CI4H4R36 Exploded View]]
 +
{| class="wikitable"
 +
! Number
 +
! Part Name
 +
|-
 +
| 1
 +
| Front Grill
 +
|-
 +
| 2
 +
| Cabinet
 +
|-
 +
| 3
 +
| Front Side Plate
 +
|-
 +
| 4
 +
| Axial Flow Fan
 +
|-
 +
| 5
 +
| Drainage Plug
 +
|-
 +
| 6
 +
| Chassis Sub-Assy
 +
|-
 +
| 7
 +
| Drainage Connector
 +
|-
 +
| 8
 +
| Compressor Gasket
 +
|-
 +
| 9
 +
| Compressor and Fittings
 +
|-
 +
| 10
 +
| Electrical Heater
 +
|-
 +
| 11
 +
| Magnet Coil
 +
|-
 +
| 12
 +
| 4-Way Valve Assy
 +
|-
 +
| 13
 +
| Right Side Plate
 +
|-
 +
| 14
 +
| Valve Support Assy
 +
|-
 +
| 15
 +
| Cut-Off Valve
 +
|-
 +
| 16
 +
| Valve Cover
 +
|-
 +
| 17
 +
| Retaining Plate
 +
|-
 +
| 18
 +
| Handle Assy
 +
|-
 +
| 19
 +
| Wiring Clamp
 +
|-
 +
| 20
 +
| Capillary Sub-Assy
 +
|-
 +
| 21
 +
| Temperature Sensor
 +
|-
 +
| 22
 +
| Rear Grill
 +
|-
 +
| 23
 +
| Condenser Assy
 +
|-
 +
| 24
 +
| Clapboard
 +
|-
 +
| 25
 +
| Condenser Support Plate
 +
|-
 +
| 26
 +
| Motor Support Sub-Assy
 +
|-
 +
| 27
 +
| Top Cover Sub-Assy
 +
|-
 +
| 28
 +
| Electric Box Cover
 +
|-
 +
| 29
 +
| Reactor
 +
|-
 +
| 30
 +
| Electric Box Sub-Assy
 +
|-
 +
| 31
 +
| Pass Wire Ring Sub-Assy
 +
|-
 +
| 32
 +
| Left Handle
 +
|-
 +
| 33
 +
| Left Side Plate
 +
|-
 +
| 34
 +
| Fan Motor
 +
|-
 +
| 35
 +
| Electric Box Cover
 +
|-
 +
| 36
 +
| Main Board
 +
|-
 +
| 37
 +
| Electric Box
 +
|-
 +
| 38
 +
| Radiator
 +
|-
 +
| 39
 +
| Terminal Board
 +
|-
 +
| 40
 +
| Electric Box Assy
 +
|-
 +
| 41
 +
| Capillary Sub-Assy (Oil Returning)
 +
|-
 +
| 42
 +
| Electrical Heater (Chassis)
 +
|}
 +
== Piping Sizes ==
 +
{| class="wikitable"
 +
! Liquid Side
 +
! Gas Side
 +
|-
 +
| 1/4"
 +
| 5/8"
 
|}
 
|}
 +
== Accessories ==
 +
*[[Wall Bracket (QBR-19.5)]]
 +
*[[Universal Remote (QTH-4000)]]

Latest revision as of 15:20, 16 December 2013

A16CI4H4R36 is the 16 SEER 36,000 Btu mini split condenser.

36k Mini Split Evaporator

Malfunction Information Table

Name of Malfunction Display of indoor unit State of the lamps on the outdoor unit PCB
Error Code Yellow Red Green Reasons
Compressor running (normal) blink 1 time Part of normal operation
Automatic defrosting (normal) H1 blink 2 times Part of normal operation
Anti-freezing protection E2 blink 3 times Refrigerant leakage / indoor unit airflow blocked up / filter duty
Stop for IPM module protection (over current) H5 blink 4 times IPM model over current / outdoor unit air flow blocked up
Stop for over current protection E5 blink 5 times Outdoor unit over current / ambient temperature is abominable
Overload protection H4 blink 6 times Ambient temperature is abominable / heat exchanger is blocked up
Stop for exhaust protection E4 blink 7 times low refrigerant / capillary blocked up / ambient temperature is abominable
Stop for compressor overload protection H3 blink 8 times Compressor shell overheat / low refrigerant / capillary blocked up
Stop for overpower protection L9 blink 9 times Ambient temperature is abominable
Stop for IPM module protection (overheat) H5 blink 10 times IPM module overheat / outdoor unit airflow blocked up
Stop for EEPROM read-write function EE blink 11 times The EEPROM on the outdoor PCB mainboard cannot read or write
Stop for low voltage protection PL blink 12 times DC voltage is too low
Stop for high voltage protection PH blink 13 times DC voltage is too high
Stop for PFC circuit over current protection HC blink 14 times The PFC circuit over current
No feedback of indoor fan motor H6 / / / Indoor fan is abnormal
Stop for ID and OD doesn't match LP blink 16 times The indoor unit and outdoor unit does not match
Compressor frequence limit by over current protection blink 1 time Outdoor unit over current / ambient temperature is abominable
Compressor frequence limit by exhaust protection blink 2 times low refrigerant / capillary blocked up / ambient temperature is abominable
Compressor frequence limit by overload protection blink 3 times Ambient temperature is abominable / heat exchanger is blocked up
Compressor frequence limit by anti-freezing protection blink 4 times Refrigerant leakage / indoor unit airflow blocked up / filter duty
Outdoor pipe temperature sensor malfunction F4 blink 5 times Open circuit or short circuit for outdoor condenser pipe temp. sensor
Outdoor ambient temperature sensor malfunction F3 blink 6 times Open circuit or short circuit for outdoor environment temp. sensor
Outdoor exhaust temperature sensor malfunction F5 blink 7 times Open circuit or short circuit for outdoor gas-discharge pipe temp. sensor
The indoor temp. reach to operate compressor (normal) blink 8 times Part of normal operation / Compressor preparing to run
Compressor frequence limit by IPM protection blink 11 times IPM module overheat / outdoor unit airflow blocked up
Compressor frequence limit by over power protection blink 13 times Ambient temperature is abominable
Indoor ambient temperature sensor malfunction F1 Open circuit or short circuit for indoor environment temp. sensor
Indoor tube temperature sensor malfunction F2 Open circuit or short circuit for indoor environment pipe temp. sensor
Stop for communication malfunction E6 off Communication line failure / main PCB failure / interfere source / connect line wrong
Communication is normal blink 1 time Communication is normal
Jumper cap malfunction protection C5 The jumper misfit the main board
No feedback from outdoor fan motor blink 14 times
High pressure protection E1 blink 16 times
Note: The lamps blink 0.5s on, 0.5s off. There is a 2s off interval between error codes.

Wiring Diagram

A16CI4H4R36 Wiring Diagram

Exploded View and Parts List

A16CI4H4R36 Exploded View
Number Part Name
1 Front Grill
2 Cabinet
3 Front Side Plate
4 Axial Flow Fan
5 Drainage Plug
6 Chassis Sub-Assy
7 Drainage Connector
8 Compressor Gasket
9 Compressor and Fittings
10 Electrical Heater
11 Magnet Coil
12 4-Way Valve Assy
13 Right Side Plate
14 Valve Support Assy
15 Cut-Off Valve
16 Valve Cover
17 Retaining Plate
18 Handle Assy
19 Wiring Clamp
20 Capillary Sub-Assy
21 Temperature Sensor
22 Rear Grill
23 Condenser Assy
24 Clapboard
25 Condenser Support Plate
26 Motor Support Sub-Assy
27 Top Cover Sub-Assy
28 Electric Box Cover
29 Reactor
30 Electric Box Sub-Assy
31 Pass Wire Ring Sub-Assy
32 Left Handle
33 Left Side Plate
34 Fan Motor
35 Electric Box Cover
36 Main Board
37 Electric Box
38 Radiator
39 Terminal Board
40 Electric Box Assy
41 Capillary Sub-Assy (Oil Returning)
42 Electrical Heater (Chassis)

Piping Sizes

Liquid Side Gas Side
1/4" 5/8"

Accessories