Difference between revisions of "MHI KXZ ODU5"
From Technical Support Wiki
(One intermediate revision by the same user not shown) | |||
Line 6: | Line 6: | ||
| title = Mitsubishi Heavy Industries VRF | | title = Mitsubishi Heavy Industries VRF | ||
| subheader = Heat Pump Systems (FDC) | | subheader = Heat Pump Systems (FDC) | ||
− | | image = [[File:MHI- | + | | image = [[File:MHI-FDC-ODU-5-Featured.png|center|300px]] |
| header1 = | | header1 = | ||
Line 78: | Line 78: | ||
|- | |- | ||
| colspan="2" | Refrigerant Charge | | colspan="2" | Refrigerant Charge | ||
− | | R410A | + | | colspan="2" | R410A |
| kg | | kg | ||
| colspan="2" style="text-align: center;" | 11.0x2 | | colspan="2" style="text-align: center;" | 11.0x2 |
Latest revision as of 14:41, 4 December 2018
This is the support page for the Heat Pump outdoor units for MHI VRF air conditioners.
Heat Pump Systems (FDC) | |
Voltage | 220V |
---|---|
Capacities (kW) | 61.5-67.0 |
Heat Pump? | Yes |
Model Numbers
- FDC615KXZE1M (FDC280 + FDC335)
- FDC670KXZE1M (FDC335 + FDC335)
Specifications
Item | Unit | FDC615KXZE1M | FDC670KXZE1M | |||
---|---|---|---|---|---|---|
Nominal Horse Power | 22HP | 24HP | ||||
Power Source | 3 Phase 3 wiring 220V, 60Hz | |||||
Starting Current | A | 10 | ||||
Max Current | A | 42.4 | ||||
Nominal Capacity | Cooling | kW | 61.5 | 67.0 | ||
Heating | 69.0 | 75.0 | ||||
Electrical Characteristics | Power Consumption | Cooling | kW | 16.20 | 17.92 | |
Heating | 16.32 | 18.08 | ||||
Exterior Dimensions | HxWxD | mm | 1690x2700x720 | |||
Net Weight | kg | 532 | ||||
Refrigerant Charge | R410A | kg | 11.0x2 | |||
Refrigerant Piping Size | Liquid Line | mm (in) | ⌀12.7 (1/2") | |||
Gas Line | ⌀28.58 (1 1/8") | |||||
Capacity Connection | % | 50~130 | ||||
Number of Connectable Indoor Units | 53 | 58 |