Difference between revisions of "MHI KXZ ODU5"

From Technical Support Wiki
Jump to: navigation, search
 
(2 intermediate revisions by the same user not shown)
Line 6: Line 6:
 
  | title      = Mitsubishi Heavy Industries VRF
 
  | title      = Mitsubishi Heavy Industries VRF
 
  | subheader  = Heat Pump Systems (FDC)
 
  | subheader  = Heat Pump Systems (FDC)
  |  image = [[File:MHI-FDT-IDU.png|center|300px]]
+
  |  image = [[File:MHI-FDC-ODU-5-Featured.png|center|300px]]
 
   
 
   
 
  | header1 =
 
  | header1 =
Line 77: Line 77:
 
| colspan="2" style="text-align: center;"| 532
 
| colspan="2" style="text-align: center;"| 532
 
|-
 
|-
| rowspan="2" colspan="2" | Refrigerant Charge
+
| colspan="2" | Refrigerant Charge
| R410A
+
| colspan="2" | R410A
 
| kg
 
| kg
 
| colspan="2" style="text-align: center;" | 11.0x2
 
| colspan="2" style="text-align: center;" | 11.0x2

Latest revision as of 14:41, 4 December 2018

This is the support page for the Heat Pump outdoor units for MHI VRF air conditioners.

Mitsubishi Heavy Industries VRF
Heat Pump Systems (FDC)
MHI-FDC-ODU-5-Featured.png
Voltage 220V
Capacities (kW) 61.5-67.0
Heat Pump? Yes

Model Numbers

  • FDC615KXZE1M (FDC280 + FDC335)
  • FDC670KXZE1M (FDC335 + FDC335)

Specifications

Item Unit FDC615KXZE1M FDC670KXZE1M
Nominal Horse Power 22HP 24HP
Power Source 3 Phase 3 wiring 220V, 60Hz
Starting Current A 10
Max Current A 42.4
Nominal Capacity Cooling kW 61.5 67.0
Heating 69.0 75.0
Electrical Characteristics Power Consumption Cooling kW 16.20 17.92
Heating 16.32 18.08
Exterior Dimensions HxWxD mm 1690x2700x720
Net Weight kg 532
Refrigerant Charge R410A kg 11.0x2
Refrigerant Piping Size Liquid Line mm (in) ⌀12.7 (1/2")
Gas Line ⌀28.58 (1 1/8")
Capacity Connection % 50~130
Number of Connectable Indoor Units 53 58