Difference between revisions of "MHI VRF FDUH"

From Technical Support Wiki
Jump to: navigation, search
 
(One intermediate revision by the same user not shown)
Line 6: Line 6:
 
  | title      = Mitsubishi Heavy Industries VRF
 
  | title      = Mitsubishi Heavy Industries VRF
 
  | subheader  = Duct Connected (Compact & Flexible) (FDUH)
 
  | subheader  = Duct Connected (Compact & Flexible) (FDUH)
  |  image = [[File:Blue2-Logo.png|center|300px]]
+
  |  image = [[File:MHI-FDUH-IDU.png|center|300px]]
 
   
 
   
 
  | header1 =
 
  | header1 =
Line 26: Line 26:
 
!scope="col" colspan="2" | Item
 
!scope="col" colspan="2" | Item
 
!scope="col" | Unit
 
!scope="col" | Unit
 +
| FDUH22KXE6F
 +
| FDUH28KXE6F
 +
| FDUH36KXE6F
 +
|-
 +
| colspan="2" | Nominal Cooling Capacity
 +
| kW
 +
| 2.2
 +
| 2.8
 +
| 3.6
 +
|-
 +
| colspan="2" | Nominal Cooling Capacity
 +
| kW
 +
| 2.5
 +
| 3.2
 +
| 4.0
 +
|-
 +
| colspan="2" | Power Source
 +
|
 +
| colspan="3" style="text-align: center;" | 1 Phase 220V, 60Hz
 +
|-
 +
| rowspan="2" | Power Consumption
 +
| Cooling
 +
| rowspan="2" | kW
 +
| colspan="3" style="text-align: center;" | 0.07
 +
|-
 +
| Heating
 +
| colspan="3" style="text-align: center;" | 0.07
 +
|-
 +
| colspan="2" | Sound Power Level
 +
| dB(A)
 +
| colspan="3" style="text-align: center;" | 60
 +
|-
 +
| colspan="2" | Sound Pressure Level
 +
| dB(A)
 +
| colspan="3" style="text-align: center;" | Hi: 33 Me: 30 Lo: 27
 +
|-
 +
| colspan="2" | Exterior Dimensions HxWxD
 +
| mm
 +
| colspan="3" style="text-align: center;" | 257x570x530
 +
|-
 +
| colspan="2" | Net Weight
 +
| kg
 +
| colspan="3" style="text-align: center;" | 22
 +
|-
 +
| colspan="2" | Air Flow
 +
| m<sup>3</sup> / min
 +
| colspan="3" style="text-align: center;" | Hi: 7 Me: 6.5 Lo: 6
 +
|-
 +
| colspan="2" | External Static Pressure
 +
| Pa
 +
| colspan="3" style="text-align: center;" | 30
 +
|-
 +
| colspan="2" | Air Filter
 +
|
 +
| colspan="3" style="text-align: center;" | Filter kit: UH-FL1E (option)
 +
|-
 +
| colspan="2" | Remote Control (option)
 +
|
 +
|  colspan="3" style="text-align: center;" | wired: RC-EX3, RC-E5, RCH-E3 wireless: RCN-KIT4-E2
 +
|-
 +
| colspan="2" | Refrigerant Piping Size
 +
| mm(in)
 +
| colspan="2" style="text-align: center;" | Liquid Line: ⌀6.35 (1/4") Gas Line: ⌀9.52 (3/8")
 +
| Liquid Line: ⌀6.35 (1/4") Gas Line: ⌀12.7 (1/2")
 +
|-
 +
|}

Latest revision as of 14:33, 5 November 2018

This is the support page for the Duct Connected (Compact & Flexible) indoor unit (FDUH) for MHI VRF air conditioners.

Mitsubishi Heavy Industries VRF
Duct Connected (Compact & Flexible) (FDUH)
MHI-FDUH-IDU.png
Voltage 220V
Capacities (kW) 2.2-3.6
Heat Pump? Yes

Model Numbers

  • FDUH22KXE6F
  • FDUH28KXE6F
  • FDUH36KXE6F

Specifications

Item Unit FDUH22KXE6F FDUH28KXE6F FDUH36KXE6F
Nominal Cooling Capacity kW 2.2 2.8 3.6
Nominal Cooling Capacity kW 2.5 3.2 4.0
Power Source 1 Phase 220V, 60Hz
Power Consumption Cooling kW 0.07
Heating 0.07
Sound Power Level dB(A) 60
Sound Pressure Level dB(A) Hi: 33 Me: 30 Lo: 27
Exterior Dimensions HxWxD mm 257x570x530
Net Weight kg 22
Air Flow m3 / min Hi: 7 Me: 6.5 Lo: 6
External Static Pressure Pa 30
Air Filter Filter kit: UH-FL1E (option)
Remote Control (option) wired: RC-EX3, RC-E5, RCH-E3 wireless: RCN-KIT4-E2
Refrigerant Piping Size mm(in) Liquid Line: ⌀6.35 (1/4") Gas Line: ⌀9.52 (3/8") Liquid Line: ⌀6.35 (1/4") Gas Line: ⌀12.7 (1/2")