Difference between revisions of "MHI VRF FDU"
From Technical Support Wiki
Line 6: | Line 6: | ||
| title = Mitsubishi Heavy Industries VRF | | title = Mitsubishi Heavy Industries VRF | ||
| subheader = Duct Connected High Static Pressure (FDU) | | subheader = Duct Connected High Static Pressure (FDU) | ||
− | | image = [[File: | + | | image = [[File:MHI-FDU-IDU.png|center|300px]] |
| header1 = | | header1 = |
Latest revision as of 14:28, 5 November 2018
This is the support page for the Duct Connected High Static Pressure indoor unit (FDU) for MHI VRF air conditioners.
Duct Connected High Static Pressure (FDU) | |
Voltage | 220V |
---|---|
Capacities (kW) | 4.5-16.0 |
Heat Pump? | Yes |
Model Numbers
- FDU45KXE6F
- FDU56KXE6F
- FDU71KXE6F
- FDU90KXE6F
- FDU112KXE6F
- FDU140KXE6F
- FDU160KXE6F
- FDU224KXE6F
- FDU280KXE6F
Specifications
Item | Unit | FDU45KXE6F | FDU56KXE6F | FDU71KXE6F | FDU90KXE6F | FDU112KXE6F | FDU140KXE6F | FDU160KXE6F | |
---|---|---|---|---|---|---|---|---|---|
Nominal Cooling Capacity | kW | 4.5 | 5.6 | 7.1 | 9.0 | 11.2 | 14.0 | 16.0 | |
Nominal Heating Capacity | kW | 5.0 | 6.3 | 8.0 | 10.0 | 12.5 | 16.0 | 18.0 | |
Power Source | 1 Phase 220V, 60Hz | ||||||||
Power Consumption | Cooling | kW | 0.10 | 0.24 | 0.31 | 0.35 | 0.42 | ||
Heating | 0.10 | 0.24 | 0.31 | 0.35 | 0.42 | ||||
Sound Power Level | dB(A) | 60 | 65 | --- | |||||
Sound Pressure Level | dB(A) | Hi: 32 Me: 29 Lo: 26 | Hi: 33 Me: 29 Lo: 25 | Hi: 38 Me: 36 Lo: 30 | Hi: 40 Me: 34 Lo: 29 | Hi: 40 Me: 35 Lo: 30 | |||
Exterior Dimensions H x W x D | mm | 280x750x635 | 280x950x635 | 280x1370x740 | |||||
Net Weight | kg | 29 | 34 | 54 | |||||
Air Flow (Standard) | m3/min | Hi: 10 Me: 9 Lo: 8 | Hi: 19 Me: 15 Lo: 10 | Hi: 28 Me: 25 Lo: 19 | Hi: 32 Me: 26 Lo: 20 | Hi: 35 Me: 28 Lo: 22 | |||
Maximum External Static Pressure | Pa | 200 | |||||||
Outside Air Intake | Possible | ||||||||
Air Filter | Procure Locally | ||||||||
Remote Control (option) | wired: RC-EX3, RC-E5, RCH-E3 wireless: RCN-KIT4-E2 | ||||||||
Refrigerant Piping Size | mm (in) | Liquid Line: ⌀6.35 (1/4") Gas Line: ⌀12.7 (1/2") | Liquid Line: ⌀9.52 (3/8") Gas Line: ⌀15.88 (5/8") |
Item | Unit | FDU224KXE6F | FDU280KXE6F | |
---|---|---|---|---|
Nominal Cooling Capacity | kW | 22.4 | 28.0 | |
Nominal Heating Capacity | kW | 25.0 | 31.5 | |
Power Source | 1 Phase 220V, 60Hz | |||
Power Consumption | Cooling | kW | 1.16 | 1.16 |
Heating | 1.16 | 1.16 | ||
Sound Power Level | dB(A) | ---- | ||
Sound Power Level | dB(A) | Hi: 50 Me: 47 Lo: 45 | ||
Exterior Dimensions H x W x D | mm | 379x1600x893 | ||
Net Weight | kg | 89 | ||
Air Flow | m3/min | Hi: 72 Me: 64 Lo: 56 | ||
Maximum External Static Pressure | Pa | 200 | ||
Outside Air Intake | Possible (on Return Duct) | |||
Air Filter | Procure locally | |||
Remote Control (option) | wired: RC-EX3, RC-E5, RCH-E3 wireless: RCN-KIT4-E2 | |||
Refrigerant Piping Size | kg | Liquid Line: ⌀9.52 (3/8") Gas Line: ⌀19.05 (3/4") | Liquid Line: ⌀9.52 (3/8") Gas Line: ⌀22.22 (7/8") |