Difference between revisions of "MHI VRF FDT"
From Technical Support Wiki
Line 6: | Line 6: | ||
| title = Mitsubishi Heavy Industries VRF | | title = Mitsubishi Heavy Industries VRF | ||
| subheader = 4 way Ceiling Cassette (FDT) | | subheader = 4 way Ceiling Cassette (FDT) | ||
− | | image = [[File: | + | | image = [[File:MHI-FDT-IDU.png|center|300px]] |
| header1 = | | header1 = |
Latest revision as of 14:21, 5 November 2018
This is the support page for the 4 way ceiling cassette indoor unit (FDT) for MHI VRF air conditioners.
4 way Ceiling Cassette (FDT) | |
Voltage | 220V |
---|---|
Capacities (kW) | 2.8-16.0 |
Heat Pump? | Yes |
Model Numbers
- FDT28KXZE1
- FDT36KXZE1
- FDT45KXZE1
- FDT56KXZE1
- FDT71KXZE1
- FDT90KXZE1
- FDT112KXZE1
- FDT140KXZE1
- FDT160KXZE1
Specifications
Item | Unit | FDT28KXZE1 | FDT36KXZE1 | FDT45KXZE1 | FDT56KXZE1 | FDT71KXZE1 | FDT90KXZE1 | FDT112KXZE1 | FDT140KXZE1 | FDT160KXZE1 | |
---|---|---|---|---|---|---|---|---|---|---|---|
Nominal Cooling Capacity | kW | 2.8 | 3.6 | 4.5 | 5.6 | 7.1 | 9.0 | 11.2 | 14.0 | 16.0 | |
Nominal Heating Capacity | kW | 3.2 | 4.0 | 5.0 | 6.3 | 8.0 | 10.0 | 12.5 | 16.0 | 18.0 | |
Power Source | 1 Phase 220v, 60Hz | ||||||||||
Power Consumption | Cooling | kW | 0.02 | 0.03 | 0.04 | 0.08 | 0.13 | 0.14 | |||
Heating | 0.02 | 0.03 | 0.04 | 0.08 | 0.13 | 0.14 | |||||
Sound Power Level | dB(A) | 49 | 50 | 55 | 62 | 65 | 66 | ||||
Sound Pressure Level | dB(A) | Hi: 33 Me: 30 Lo: 28 | Hi: 33 Me: 31 Lo: 29 | Hi: 35 Me: 32 Lo: 28 | Hi: 38 Me: 36 Lo: 31 | Hi: 39 Me: 37 Lo: 31 | Hi: 42 Me: 39 Lo: 32 | Hi: 42 Me: 39 Lo: 33 | |||
Exterior Dimensions | mm | Unit: 236x840x840 Panel: 35x950x950 | Unit: 298x840x840 Panel: 35x950x950 | ||||||||
Net Weight | kg | Unit: 20 Standard Panel: 5 | Unit: 21.5 Standard Panel: 5 | Unit: 25 Standard Panel: 5 | |||||||
Air Flow | m3/min | Hi: 14 Me: 12 Lo: 10 | Hi: 15 Me: 13 Lo: 10 | Hi: 16 Me: 13 Lo: 11 | Hi: 17 Me: 14 Lo: 12 | Hi: 25 Me: 22 Lo: 15 | Hi: 26 Me: 23 Lo: 17 | Hi: 28 Me: 25 Lo: 18 | Hi: 29 Me: 26 Lo: 19 | ||
Outside air intake | Possible | ||||||||||
Panel | T-PSA-5AW-E, T-PSAE-5AW-E | ||||||||||
Air Filter, Qty | Pocket Plastic net x 1 (Washable) | ||||||||||
Remote Control (option) | wired: RC-EX3, RC-E5, RCH-E3 wireless: RCN-T-5AW-E2 | ||||||||||
Refrigerant Piping Size | mm (in) | Liquid Line: ⌀6.35 (1/4") Gas Line: ⌀9.52 (3/8") | Liquid Line: ⌀6.35 (1/4") Gas Line: ⌀12.7 (1/2") | Liquid Line: ⌀9.52 (3/8") Gas Line: ⌀15.88 (5/8") |