Difference between revisions of "Bronze Series"

From Technical Support Wiki
Jump to: navigation, search
 
(26 intermediate revisions by the same user not shown)
Line 1: Line 1:
This is the support page for the Air-Con ''Bronze Series'' mini split line. Here you will find information pertaining to common issues with the Bronze Series units. [[File: Bronze-featured.png|right|thumb|300px|Upper Left: Indoor units for 9-18k. Upper Right: Indoor unit for 24k.]]
+
'''''The Bronze Series was discontinued in late 2014. All information preserved here is for legacy support.'''''
 
+
----
 
+
This is the support page for the Air-Con ''Bronze Series'' mini split line.  
== Outdoor Models ==  
+
{{Infobox
 +
|
 +
| bodyclass = infobox
 +
| name = Bronze Series
 +
| title      = Bronze Series
 +
| subheader  = Single Zone Mini Split Line
 +
| image = [[File: Bronze-featured.png|center|300px]]
 +
 +
| header1 =
 +
| label1 = Voltage
 +
| data1 = 115V-220V
 +
| header2 =
 +
| label2 = SEER Rating
 +
| data2 = 13
 +
| header3 =
 +
| label3 = Capacities
 +
| data3 = 9,000 - 24,000 BTU
 +
| header4 =
 +
| label4 = Heat Pump?
 +
| data4 = Yes
 +
| header5 =
 +
| label5 = Model Sold From
 +
| data5 = May 2010 - May 2014
 +
}}
 +
== Indoor Units ==
 +
* [[A13EM4H4G09]]
 +
* [[A13EM4H4G12]]
 +
* [[A13EM4H4G18]]
 +
* [[A13EM4H4G24]]
 +
== Outdoor Units ==  
 
* [[A13CH4H4G09]]
 
* [[A13CH4H4G09]]
 
* [[A13CH4H4G12]]
 
* [[A13CH4H4G12]]
 
* [[A13CH4H4G18]]
 
* [[A13CH4H4G18]]
 
* [[A13CH4H4G24]]
 
* [[A13CH4H4G24]]
== Indoor Models ==  
+
== Error Codes ==
* [[A13EM4H4G09]]
+
{| class="wikitable"
* [[A13EM4H4G12]]
+
! Code
* [[A13EM4H4G18]]
+
! Error Name
* [[A13EM4H4G24]]
+
! Troubleshooting
== Error Codes ==
+
|-
The error codes are displayed on the indoor unit's display board. Specifically, the display board's temperature indicator. All error codes are the same among all of the Bronze Series units.  
+
| DF
* [[Error E0 (Silver Series)|Error E0]]
+
| Defrost
* [[Error E1 (Silver Series)|Error E1]]
+
| Currently in defrost mode. Will return to normal operations when defrost is finished.
* [[Error E2 (Silver Series)|Error E2]]
+
|-
* [[Error E3 (Silver Series)|Error E3]]
+
| FF
* [[Error E5 (Silver Series)|Error E5]]
+
| Outdoor Low Temperature Indication
* [[Error E6 (Silver Series)|Error E6]]
+
| The current temperature outside is too low for proper unit functionality.
* [[Error E7 (Silver Series)|Error E7]]
+
|-
* [[Error P0 (Silver Series)|Error P0]]
+
| E1
* [[Error P1 (Silver Series)|Error P1]]
+
| Outdoor Temp Sensor Fault
* [[Error P2 (Silver Series)|Error P2]]
+
|
* [[Error P4 (Silver Series)|Error P4]]
+
* Check whether the resistance of the sensor is normal. If it is abnormal the sensor should be replaced.
 +
* Check whether there is a short circuit or open circuit in the wire of the sensor, and whether the plug is connected correctly.
 +
* After checking for the above conditions and finding nothing, it check the electric control board.
 +
|-
 +
| E2
 +
| Room Temp Sensor Fault
 +
|
 +
* Check whether the resistance of the sensor is normal. If it is abnormal the sensor should be replaced.
 +
* Check whether there is a short circuit or open circuit in the wire of the sensor, and whether the plug is connected correctly.
 +
* After checking for the above conditions and finding nothing, it check the electric control board.
 +
|-
 +
| E3
 +
| Coil Temp. Sensor Fault
 +
|
 +
* Check whether the resistance of the sensor is normal. If it is abnormal the sensor should be replaced.
 +
* Check whether there is a short circuit or open circuit in the wire of the sensor, and whether the plug is connected correctly.
 +
* After checking for the above conditions and finding nothing, it check the electric control board.
 +
|-
 +
| E4
 +
| Outdoor Unit Abnormal
 +
|
 +
* Check whether the winding resistance and operation current of the compressor are normal.
 +
* Check whether the high and low pressure is normal when the unit is running.
 +
* Check whether the contact of the inserter on the circuit board is well, the coil pipe temperature sensor is well, the key is to check the evaporator temperature detected by the coil pipe temperature sensor has reached the cooling or heating temperature.  
 +
* Check whether the surface of the condenser is too dirty. It should be cleaned if it is too dirty.
 +
* Check whether the capacitance of the outdoor motor and the fan is damaged. Replace if damaged.
 +
* If all the of above is normal, then consider replacing the electric control board.
 +
|-
 +
| E5
 +
| No Feedback Signal of Indoor Fan
 +
|  
 +
* Check whether two sets of plugs on the outlet end of the motor have loosed from the socket of the electric control board. If it is loose, please insert firmly.
 +
* Check whether the indoor motor is damaged. Replace indoor motor if damaged.
 +
* Check whether the controllable silicon and other components on the electric control board are damaged. Replace controllable silicon or electric control board if damaged.
 +
|-
 +
| E6
 +
| No Over Zero Signal
 +
|
 +
* Check whether the indoor fan is normal.
 +
* Check whether the signal outputting from the integrated chip of the electric control board is normal. If not, please replace electric control board.
 +
|-
 +
| E7
 +
| Outdoor Feedback Fault
 +
|
 +
* Check whether the winding resistance and operation current of the compressor are normal.
 +
* Check whether the high and low pressure is normal when the unit is running.
 +
* Check whether the indoor and outdoor wiring is right; when it is wrong, refer to the wiring diagram.
 +
* Check whether the contact of the inserter on the circuit board and the connection is well. Repair if otherwise.
 +
* Check whether the signal feedback wire is disconnected. Replace or reconnect the feedback signal wire.
 +
* Check whether the supply power is phase-lacking or phase opposition.
 +
* Check whether the AC electromagnetic contractor is well.
 +
|-
 +
| E8
 +
| Frost/Overheat Protection
 +
|  
 +
* Check whether the filter of the indoor unit is dirty or blocked. Clean if it is dirty.
 +
* Check whether the indoor fan is running normally, and replace the motor if it is abnormal.
 +
* Check whether indoor pipe temperature sensor is normal, and replace the sensor if it is abnormal.
 +
* Check whether the system pressure is normal, if abnormal, you should check whether there is leakage and fill the refrigerant if need be.
 +
|}
 +
 
 +
== Document Downloads ==
 +
*[[:File:13_SEER-User-Manual-F.pdf|User's Manual]]
 +
*[[:File:13_SEER-Service-Manual.pdf|Service Manual]]
 
== Warranty Information ==  
 
== Warranty Information ==  
Each ''Bronze Series'' unit has a warranty of 2 years for parts and 5 years for the compressor. If you need more information, please visit the Air-Con [http://airconint.com/support/warranty-information/ Warranty Information] page.
+
Each ''Bronze Series'' unit has a warranty of 1 years for parts and 5 years for the compressor. If you need more information, please visit the Air-Con [[Warranty Policy]] page.

Latest revision as of 16:08, 13 October 2020

The Bronze Series was discontinued in late 2014. All information preserved here is for legacy support.


This is the support page for the Air-Con Bronze Series mini split line.

Bronze Series
Single Zone Mini Split Line
Bronze-featured.png
Voltage 115V-220V
SEER Rating 13
Capacities 9,000 - 24,000 BTU
Heat Pump? Yes
Model Sold From May 2010 - May 2014

Indoor Units

Outdoor Units

Error Codes

Code Error Name Troubleshooting
DF Defrost Currently in defrost mode. Will return to normal operations when defrost is finished.
FF Outdoor Low Temperature Indication The current temperature outside is too low for proper unit functionality.
E1 Outdoor Temp Sensor Fault
  • Check whether the resistance of the sensor is normal. If it is abnormal the sensor should be replaced.
  • Check whether there is a short circuit or open circuit in the wire of the sensor, and whether the plug is connected correctly.
  • After checking for the above conditions and finding nothing, it check the electric control board.
E2 Room Temp Sensor Fault
  • Check whether the resistance of the sensor is normal. If it is abnormal the sensor should be replaced.
  • Check whether there is a short circuit or open circuit in the wire of the sensor, and whether the plug is connected correctly.
  • After checking for the above conditions and finding nothing, it check the electric control board.
E3 Coil Temp. Sensor Fault
  • Check whether the resistance of the sensor is normal. If it is abnormal the sensor should be replaced.
  • Check whether there is a short circuit or open circuit in the wire of the sensor, and whether the plug is connected correctly.
  • After checking for the above conditions and finding nothing, it check the electric control board.
E4 Outdoor Unit Abnormal
  • Check whether the winding resistance and operation current of the compressor are normal.
  • Check whether the high and low pressure is normal when the unit is running.
  • Check whether the contact of the inserter on the circuit board is well, the coil pipe temperature sensor is well, the key is to check the evaporator temperature detected by the coil pipe temperature sensor has reached the cooling or heating temperature.
  • Check whether the surface of the condenser is too dirty. It should be cleaned if it is too dirty.
  • Check whether the capacitance of the outdoor motor and the fan is damaged. Replace if damaged.
  • If all the of above is normal, then consider replacing the electric control board.
E5 No Feedback Signal of Indoor Fan
  • Check whether two sets of plugs on the outlet end of the motor have loosed from the socket of the electric control board. If it is loose, please insert firmly.
  • Check whether the indoor motor is damaged. Replace indoor motor if damaged.
  • Check whether the controllable silicon and other components on the electric control board are damaged. Replace controllable silicon or electric control board if damaged.
E6 No Over Zero Signal
  • Check whether the indoor fan is normal.
  • Check whether the signal outputting from the integrated chip of the electric control board is normal. If not, please replace electric control board.
E7 Outdoor Feedback Fault
  • Check whether the winding resistance and operation current of the compressor are normal.
  • Check whether the high and low pressure is normal when the unit is running.
  • Check whether the indoor and outdoor wiring is right; when it is wrong, refer to the wiring diagram.
  • Check whether the contact of the inserter on the circuit board and the connection is well. Repair if otherwise.
  • Check whether the signal feedback wire is disconnected. Replace or reconnect the feedback signal wire.
  • Check whether the supply power is phase-lacking or phase opposition.
  • Check whether the AC electromagnetic contractor is well.
E8 Frost/Overheat Protection
  • Check whether the filter of the indoor unit is dirty or blocked. Clean if it is dirty.
  • Check whether the indoor fan is running normally, and replace the motor if it is abnormal.
  • Check whether indoor pipe temperature sensor is normal, and replace the sensor if it is abnormal.
  • Check whether the system pressure is normal, if abnormal, you should check whether there is leakage and fill the refrigerant if need be.

Document Downloads

Warranty Information

Each Bronze Series unit has a warranty of 1 years for parts and 5 years for the compressor. If you need more information, please visit the Air-Con Warranty Policy page.