* The indoor control board might have failed. | * The indoor control board might have failed. | ||
* The wiring of the display board might be incorrect. | * The wiring of the display board might be incorrect. | ||
| + | |- | ||
| + | | 0 | ||
| + | | | ||
| + | | | ||
| + | | | ||
| + | | | ||
| + | | Normal Operations | ||
| + | | | ||
| + | |- | ||
| + | | 1 | ||
| + | | x | ||
| + | | ○ | ||
| + | | x | ||
| + | | x | ||
| + | | Outdoor Coil Temperature Sensor Failure | ||
| + | | | ||
| + | * The outdoor coil temperature sensor might be loose. | ||
| + | * The outdoor coil temperature sensor might have failed. | ||
| + | * The indoor control board might have failed. | ||
| + | |- | ||
| + | | 2 | ||
| + | | x | ||
| + | | ○ | ||
| + | | ★ | ||
| + | | x | ||
| + | | Compressor Exhaust Temperature Sensor Failure | ||
| + | | | ||
| + | * The compressor exhaust temperature sensor might be loose. | ||
| + | * The compressor exhaust temperature sensor might have failed. | ||
| + | * The outdoor control board might have failed. | ||
| + | |- | ||
| + | | 5 | ||
| + | | ★ | ||
| + | | ○ | ||
| + | | x | ||
| + | | x | ||
| + | | IPM Module Protection | ||
| + | | | ||
| + | * The IPM board might have failed. | ||
| + | * The outdoor fan might be broken. | ||
| + | * The outdoor fan motor might have failed. | ||
| + | * The outdoor fan is being obstructed. | ||
| + | * The condenser might be dirty. | ||
| + | * The outdoor unit might not have been installed correctly. | ||
| + | |- | ||
| + | | 6 | ||
| + | | ★ | ||
| + | | ○ | ||
| + | | x | ||
| + | | ★ | ||
| + | | AC Voltage Higher or Lower Protection | ||
| + | | | ||
| + | * The supply voltage is higher or lower than normal. | ||
| + | * The inner supply voltage of the unit is higher or lower than normal. | ||
| + | |- | ||
| + | | 7 | ||
| + | | ★ | ||
| + | | ○ | ||
| + | | ★ | ||
| + | | x | ||
| + | | Communication Failure Between Indoor and Outdoor Units | ||
| + | | | ||
| + | * The communication cable connection might be loose. | ||
| + | * The communication cable might have failed. | ||
| + | * The connection between the filter board and the outdoor control board might be incorrect or loose. | ||
| + | * The connection between the filter board and the terminal might be incorrect or loose. | ||
| + | * The indoor unit control board might have failed. | ||
| + | * The PFC board might have failed. | ||
| + | * The power board might have failed. | ||
| + | * The outdoor unit control board might have failed. | ||
| + | |- | ||
| + | | 8 | ||
| + | | ★ | ||
| + | | ○ | ||
| + | | ★ | ||
| + | | ★ | ||
| + | | Current Overload Protection | ||
| + | | | ||
| + | * The fan motor might have run abnormally. | ||
| + | * The condenser and/or evaporator might be dirty. | ||
| + | * The air inlet and outlet might be abnormal. | ||
| + | |- | ||
| + | | 9 | ||
| + | | x | ||
| + | | x | ||
| + | | ○ | ||
| + | | x | ||
| + | | Maximum Current Protection | ||
| + | | | ||
| + | * The outdoor control board might have short-circuited. | ||
| + | * The drive board might have short-circuited. | ||
| + | * Other electrical components might have short-circuited. | ||
| + | |- | ||
| + | | 10 | ||
| + | | x | ||
| + | | x | ||
| + | | ○ | ||
| + | | ★ | ||
| + | | Communication Error Between Outdoor Unit Control Board and Driver Board | ||
| + | | | ||
| + | * The connection between control board and driver board might be loose. | ||
| + | * Either the control or driver board might have failed. | ||
| + | |- | ||
| + | | 11 | ||
| + | | x | ||
| + | | ★ | ||
| + | | ○ | ||
| + | | x | ||
| + | | Check Outdoor EEPROM | ||
| + | | | ||
| + | * The EEPROM chip might be loose. | ||
| + | * The EEPROM chip might be inserted improperly. | ||
| + | * The EEPROM chip might have failed. | ||
| + | |- | ||
| + | | 12 | ||
| + | | x | ||
| + | | ★ | ||
| + | | ○ | ||
| + | | ★ | ||
| + | | Outdoor Ambient Temperature Too Low Protection | ||
| + | | | ||
| + | * Outdoor ambient temperature too low for operation. | ||
| + | |- | ||
| + | | 13 | ||
| + | | ★ | ||
| + | | x | ||
| + | | ○ | ||
| + | | x | ||
| + | | Compressor Exhaust Temperature Too High Protection | ||
| + | | | ||
| + | * The compressor exhaust temperature sensor might have failed. | ||
| + | * The unit has insufficient refrigerant. | ||
| + | |- | ||
| + | | 14 | ||
| + | | ★ | ||
| + | | x | ||
| + | | ○ | ||
| + | | ★ | ||
| + | | Check Outdoor Ambient Temperature Sensor | ||
| + | | | ||
| + | * The outdoor ambient temperature sensor's connection might be loose. | ||
| + | * The outdoor ambient temperature sensor might have failed. | ||
| + | * The outdoor control board might have failed. | ||
| + | |- | ||
| + | | 15 | ||
| + | | ★ | ||
| + | | ★ | ||
| + | | ○ | ||
| + | | x | ||
| + | | Compressor Shell Temperature Too High Protection | ||
| + | | | ||
| + | * The compressor exhaust temperature sensor might be loose. | ||
| + | * The unit has insufficient refrigerant. | ||
| + | |- | ||
| + | | 16 | ||
| + | | | ||
| + | | | ||
| + | | | ||
| + | | | ||
| + | | Anti-Freeze Protection (Cooling) or Overload Protection (Heating) in Indoor Unit | ||
| + | | | ||
| + | * The indoor coil temperature sensor might be loose. | ||
| + | * The indoor coil temperature sensor might have failed. | ||
| + | * The indoor control board might have failed. | ||
| + | * The refrigerant system is abnormal. | ||
| + | |- | ||
| + | | 17 | ||
| + | | | ||
| + | | | ||
| + | | | ||
| + | | | ||
| + | | PFC Protection | ||
| + | | | ||
| + | * The PFC might have failed. | ||
| + | * The outdoor drive board might have failed. | ||
| + | |- | ||
| + | | 18 | ||
| + | | | ||
| + | | | ||
| + | | | ||
| + | | | ||
| + | | DC Compressor Start Failure | ||
| + | | | ||
| + | * The outdoor drive board might have failed. | ||
| + | * The compressor might have failed. | ||
| + | |- | ||
| + | | 19 | ||
| + | | x | ||
| + | | x | ||
| + | | x | ||
| + | | ○ | ||
| + | | Check Compressor Drive | ||
| + | | | ||
| + | * The outdoor drive board might have failed. | ||
| + | * The compressor might have failed. | ||
| + | * The outdoor control board might have failed. | ||
| + | |- | ||
| + | | 20 | ||
| + | | ★ | ||
| + | | x | ||
| + | | x | ||
| + | | ○ | ||
| + | | Outdoor Fan Motor Locked Rotor Protection | ||
| + | | | ||
| + | * The connection of the outdoor fan motor might be loose. | ||
| + | * There might be something obstructing the outdoor fan motor. | ||
| + | * The fan motor might have failed. | ||
| + | * The outdoor control board might have failed. | ||
| + | |- | ||
| + | | 21 | ||
| + | | | ||
| + | | | ||
| + | | | ||
| + | | | ||
| + | | Outdoor Coil Anti-Overload Protection With Cooling | ||
| + | | | ||
| + | * There might be too much refrigerant. | ||
| + | * The outdoor fan motor might have failed. | ||
| + | * The outdoor fan might be broken. | ||
| + | * The condensor might be dirty. | ||
| + | * The air inlet and outlet of the indoor and outdoor unit is abnormal. | ||
| + | |- | ||
| + | | 22 | ||
| + | | | ||
| + | | | ||
| + | | | ||
| + | | | ||
| + | | Compressor Pre-Heating Process | ||
| + | | | ||
| + | * This is a normal operation mode in cold weather. | ||
| + | |- | ||
| + | | 24 | ||
| + | | | ||
| + | | | ||
| + | | | ||
| + | | | ||
| + | | Check Outdoor Board Chip | ||
| + | | | ||
| + | * The drive board might not be compatible with this unit. | ||
| + | * The compressor might not be compatible with this unit. | ||
| + | |- | ||
| + | | 25 | ||
| + | | | ||
| + | | | ||
| + | | | ||
| + | | | ||
| + | |Low Frequency Protection | ||
| + | | | ||
| + | * When frequency of system is too low, the unit will start self protection, and when working condition comes back, the unit will work again. Usually, after about 3 to 5 mins, the unit will recover or you can power off unit at first, then restart the unit. | ||
| + | |- | ||
| + | | 26 | ||
| + | | | ||
| + | | | ||
| + | | | ||
| + | | | ||
| + | | Protection Against Overheated Outdoor Radiator | ||
| + | | | ||
| + | * Radiator sensors might have failed. | ||
| + | * Detection circuit of the sensor on the control panel might have failed. | ||
| + | |- | ||
| + | | 27 | ||
| + | | | ||
| + | | | ||
| + | | | ||
| + | | | ||
| + | | High Pressure System Protection | ||
| + | | | ||
| + | * The pressure switch might have failed. | ||
| + | * The pressure detection system on the control panel might have failed. | ||
| + | * The measured value of the system pressure might have exceeded the limit. | ||
| + | |- | ||
| + | | 33 | ||
| + | | ○ | ||
| + | | x | ||
| + | | x | ||
| + | | ★ | ||
| + | | Check Indoor Ambient Temperature Sensor | ||
| + | | | ||
| + | * The indoor ambient temperature sensor might be loose. | ||
| + | * The indoor ambient temperature sensor might have failed. | ||
| + | * The indoor ambient control board might have failed. | ||
| + | |- | ||
| + | | 34 | ||
| + | | ○ | ||
| + | | x | ||
| + | | ★ | ||
| + | | x | ||
| + | | Check indoor Coil Temperature Sensor | ||
| + | | | ||
| + | * The indoor coil temperature sensor might be loose. | ||
| + | * The indoor coil temperature sensor might have failed. | ||
| + | * The indoor control board might have failed. | ||
| + | |- | ||
| + | | 36 | ||
| + | | ○ | ||
| + | | ★ | ||
| + | | x | ||
| + | | ★ | ||
| + | | Communication Failure Between Indoor and Outdoor Unit | ||
| + | | | ||
| + | * The communication cable connection might be loose. | ||
| + | * The communication cable might have failed. | ||
| + | * The connection between the filter board and the outdoor control board might be incorrect or loose. | ||
| + | * The connection between the filter board and the terminal might be incorrect or loose. | ||
| + | * The indoor unit control board might have failed. | ||
| + | * The PFC board might have failed. | ||
| + | * The power board might have failed. | ||
| + | * The outdoor unit control board might have failed. | ||
| + | |- | ||
| + | | 38 | ||
| + | | ○ | ||
| + | | ★ | ||
| + | | ★ | ||
| + | | ★ | ||
| + | | Check Indoor EEPROM Failure | ||
| + | | | ||
| + | * The EEPROM chip might be loose. | ||
| + | * The indoor control board might have failed. | ||
| + | |- | ||
| + | | 39 | ||
| + | | ○ | ||
| + | | x | ||
| + | | ★ | ||
| + | | ★ | ||
| + | | Check Indoor Fan Motor | ||
| + | | | ||
| + | * The indoor fan motor might be obstructed. | ||
| + | * The indoor fan motor cord might be loose. | ||
| + | * The indoor fan motor might have failed. | ||
| + | * The indoor control board might have failed. | ||
| + | |- | ||
| + | | 41 | ||
| + | | ★ | ||
| + | | ★ | ||
| + | | ○ | ||
| + | | ★ | ||
| + | | Indoor Board Grounding Failure | ||
| + | | | ||
| + | * Indoor control board has failed. | ||
|- | |- | ||
Latest revision as of 18:31, 29 April 2019
Note: ★ - Solid light, ○ - Flashing light, x - Light is off
| Error Code | Indoor PCB LED lights | Error Description | Troubleshooting | |||
| Running | Timer | Sleep | Power | |||
| 1 | 2 | 3 | 4 | |||
| EA | Display Board and Control Board Communication Error |
| ||||
| 0 | Normal Operations | |||||
| 1 | x | ○ | x | x | Outdoor Coil Temperature Sensor Failure |
|
| 2 | x | ○ | ★ | x | Compressor Exhaust Temperature Sensor Failure |
|
| 5 | ★ | ○ | x | x | IPM Module Protection |
|
| 6 | ★ | ○ | x | ★ | AC Voltage Higher or Lower Protection |
|
| 7 | ★ | ○ | ★ | x | Communication Failure Between Indoor and Outdoor Units |
|
| 8 | ★ | ○ | ★ | ★ | Current Overload Protection |
|
| 9 | x | x | ○ | x | Maximum Current Protection |
|
| 10 | x | x | ○ | ★ | Communication Error Between Outdoor Unit Control Board and Driver Board |
|
| 11 | x | ★ | ○ | x | Check Outdoor EEPROM |
|
| 12 | x | ★ | ○ | ★ | Outdoor Ambient Temperature Too Low Protection |
|
| 13 | ★ | x | ○ | x | Compressor Exhaust Temperature Too High Protection |
|
| 14 | ★ | x | ○ | ★ | Check Outdoor Ambient Temperature Sensor |
|
| 15 | ★ | ★ | ○ | x | Compressor Shell Temperature Too High Protection |
|
| 16 | Anti-Freeze Protection (Cooling) or Overload Protection (Heating) in Indoor Unit |
| ||||
| 17 | PFC Protection |
| ||||
| 18 | DC Compressor Start Failure |
| ||||
| 19 | x | x | x | ○ | Check Compressor Drive |
|
| 20 | ★ | x | x | ○ | Outdoor Fan Motor Locked Rotor Protection |
|
| 21 | Outdoor Coil Anti-Overload Protection With Cooling |
| ||||
| 22 | Compressor Pre-Heating Process |
| ||||
| 24 | Check Outdoor Board Chip |
| ||||
| 25 | Low Frequency Protection |
| ||||
| 26 | Protection Against Overheated Outdoor Radiator |
| ||||
| 27 | High Pressure System Protection |
| ||||
| 33 | ○ | x | x | ★ | Check Indoor Ambient Temperature Sensor |
|
| 34 | ○ | x | ★ | x | Check indoor Coil Temperature Sensor |
|
| 36 | ○ | ★ | x | ★ | Communication Failure Between Indoor and Outdoor Unit |
|
| 38 | ○ | ★ | ★ | ★ | Check Indoor EEPROM Failure |
|
| 39 | ○ | x | ★ | ★ | Check Indoor Fan Motor |
|
| 41 | ★ | ★ | ○ | ★ | Indoor Board Grounding Failure |
|