(Created page with "'''Note: ★ - Solid light, ○ - Flashing light, x - Light is off''' {| class="wikitable" | rowspan="3"| Error Code | colspan="4"| Indoor PCB LED lights | rowspan="3"| Error...")
 
 
(4 intermediate revisions by the same user not shown)
Line 15: Line 15:
 
| 3
 
| 3
 
| 4
 
| 4
 +
|-
 +
| EA
 +
|
 +
|
 +
|
 +
|
 +
| Display Board and Control Board Communication Error
 +
|
 +
* The connection between the display board and control board might be loose.
 +
* The indoor control board might have failed.
 +
* The wiring of the display board might be incorrect.
 +
|-
 +
| 0
 +
|
 +
|
 +
|
 +
|
 +
| Normal Operations
 +
|
 +
|-
 +
| 1
 +
| x
 +
| ○
 +
| x
 +
| x
 +
| Outdoor Coil Temperature Sensor Failure
 +
|
 +
* The outdoor coil temperature sensor might be loose.
 +
* The outdoor coil temperature sensor might have failed.
 +
* The indoor control board might have failed.
 +
|-
 +
| 2
 +
| x
 +
| ○
 +
| ★
 +
| x
 +
| Compressor Exhaust Temperature Sensor Failure
 +
|
 +
* The compressor exhaust temperature sensor might be loose.
 +
* The compressor exhaust temperature sensor might have failed.
 +
* The outdoor control board might have failed.
 +
|-
 +
| 5
 +
| ★
 +
| ○
 +
| x
 +
| x
 +
| IPM Module Protection
 +
|
 +
* The IPM board might have failed.
 +
* The outdoor fan might be broken.
 +
* The outdoor fan motor might have failed.
 +
* The outdoor fan is being obstructed.
 +
* The condenser might be dirty.
 +
* The outdoor unit might not have been installed correctly.
 +
|-
 +
| 6
 +
| ★
 +
| ○
 +
| x
 +
| ★
 +
| AC Voltage Higher or Lower Protection
 +
|
 +
* The supply voltage is higher or lower than normal.
 +
* The inner supply voltage of the unit is higher or lower than normal.
 +
|-
 +
| 7
 +
| ★
 +
| ○
 +
| ★
 +
| x
 +
| Communication Failure Between Indoor and Outdoor Units
 +
|
 +
* The communication cable connection might be loose.
 +
* The communication cable might have failed.
 +
* The connection between the filter board and the outdoor control board might be incorrect or loose.
 +
* The connection between the filter board and the terminal might be incorrect or loose.
 +
* The indoor unit control board might have failed.
 +
* The PFC board might have failed.
 +
* The power board might have failed.
 +
* The outdoor unit control board might have failed.
 +
|-
 +
| 8
 +
| ★
 +
| ○
 +
| ★
 +
| ★
 +
| Current Overload Protection
 +
|
 +
* The fan motor might have run abnormally.
 +
* The condenser and/or evaporator might be dirty.
 +
* The air inlet and outlet might be abnormal.
 +
|-
 +
| 9
 +
| x
 +
| x
 +
| ○
 +
| x
 +
| Maximum Current Protection
 +
|
 +
* The outdoor control board might have short-circuited.
 +
* The drive board might have short-circuited.
 +
* Other electrical components might have short-circuited.
 +
|-
 +
| 10
 +
| x
 +
| x
 +
| ○
 +
| ★
 +
| Communication Error Between Outdoor Unit Control Board and Driver Board
 +
|
 +
* The connection between control board and driver board might be loose.
 +
* Either the control or driver board might have failed.
 +
|-
 +
| 11
 +
| x
 +
| ★
 +
| ○
 +
| x
 +
| Check Outdoor EEPROM
 +
|
 +
* The EEPROM chip might be loose.
 +
* The EEPROM chip might be inserted improperly.
 +
* The EEPROM chip might have failed.
 +
|-
 +
| 12
 +
| x
 +
| ★
 +
| ○
 +
| ★
 +
| Outdoor Ambient Temperature Too Low Protection
 +
|
 +
* Outdoor ambient temperature too low for operation.
 +
|-
 +
| 13
 +
| ★
 +
| x
 +
| ○
 +
| x
 +
| Compressor Exhaust Temperature Too High Protection
 +
|
 +
* The compressor exhaust temperature sensor might have failed.
 +
* The unit has insufficient refrigerant.
 +
|-
 +
| 14
 +
| ★
 +
| x
 +
| ○
 +
| ★
 +
| Check Outdoor Ambient Temperature Sensor
 +
|
 +
* The outdoor ambient temperature sensor's connection might be loose.
 +
* The outdoor ambient temperature sensor might have failed.
 +
* The outdoor control board might have failed.
 +
|-
 +
| 15
 +
| ★
 +
| ★
 +
| ○
 +
| x
 +
| Compressor Shell Temperature Too High Protection
 +
|
 +
* The compressor exhaust temperature sensor might be loose.
 +
* The unit has insufficient refrigerant.
 +
|-
 +
| 16
 +
|
 +
|
 +
|
 +
|
 +
| Anti-Freeze Protection (Cooling) or Overload Protection (Heating) in Indoor Unit
 +
|
 +
* The indoor coil temperature sensor might be loose.
 +
* The indoor coil temperature sensor might have failed.
 +
* The indoor control board might have failed.
 +
* The refrigerant system is abnormal.
 +
|-
 +
| 17
 +
|
 +
|
 +
|
 +
|
 +
| PFC Protection
 +
|
 +
* The PFC might have failed.
 +
* The outdoor drive board might have failed.
 +
|-
 +
| 18
 +
|
 +
|
 +
|
 +
|
 +
| DC Compressor Start Failure
 +
|
 +
* The outdoor drive board might have failed.
 +
* The compressor might have failed.
 +
|-
 +
| 19
 +
| x
 +
| x
 +
| x
 +
| ○
 +
| Check Compressor Drive
 +
|
 +
* The outdoor drive board might have failed.
 +
* The compressor might have failed.
 +
* The outdoor control board might have failed.
 +
|-
 +
| 20
 +
| ★
 +
| x
 +
| x
 +
| ○
 +
| Outdoor Fan Motor Locked Rotor Protection
 +
|
 +
* The connection of the outdoor fan motor might be loose.
 +
* There might be something obstructing the outdoor fan motor.
 +
* The fan motor might have failed.
 +
* The outdoor control board might have failed.
 +
|-
 +
| 21
 +
|
 +
|
 +
|
 +
|
 +
| Outdoor Coil Anti-Overload Protection With Cooling
 +
|
 +
* There might be too much refrigerant.
 +
* The outdoor fan motor might have failed.
 +
* The outdoor fan might be broken.
 +
* The condensor might be dirty.
 +
* The air inlet and outlet of the indoor and outdoor unit is abnormal.
 +
|-
 +
| 22
 +
|
 +
|
 +
|
 +
|
 +
| Compressor Pre-Heating Process
 +
|
 +
* This is a normal operation mode in cold weather.
 +
|-
 +
| 24
 +
|
 +
|
 +
|
 +
|
 +
| Check Outdoor Board Chip
 +
|
 +
* The drive board might not be compatible with this unit.
 +
* The compressor might not be compatible with this unit.
 +
|-
 +
| 25
 +
|
 +
|
 +
|
 +
|
 +
|Low Frequency Protection
 +
|
 +
* When frequency of system is too low, the unit will start self protection, and when working condition comes back, the unit will work again. Usually, after about 3 to 5 mins, the unit will recover or you can power off unit at first, then restart the unit.
 +
|-
 +
| 26
 +
|
 +
|
 +
|
 +
|
 +
| Protection Against Overheated Outdoor Radiator
 +
|
 +
* Radiator sensors might have failed.
 +
* Detection circuit of the sensor on the control panel might have failed.
 +
|-
 +
| 27
 +
|
 +
|
 +
|
 +
|
 +
| High Pressure System Protection
 +
|
 +
* The pressure switch might have failed.
 +
* The pressure detection system on the control panel might have failed.
 +
* The measured value of the system pressure might have exceeded the limit.
 +
|-
 +
| 33
 +
| ○
 +
| x
 +
| x
 +
| ★
 +
| Check Indoor Ambient Temperature Sensor
 +
|
 +
* The indoor ambient temperature sensor might be loose.
 +
* The indoor ambient temperature sensor might have failed.
 +
* The indoor ambient control board might have failed.
 +
|-
 +
| 34
 +
| ○
 +
| x
 +
| ★
 +
| x
 +
| Check indoor Coil Temperature Sensor
 +
|
 +
* The indoor coil temperature sensor might be loose.
 +
* The indoor coil temperature sensor might have failed.
 +
* The indoor control board might have failed.
 +
|-
 +
| 36
 +
| ○
 +
| ★
 +
| x
 +
| ★
 +
| Communication Failure Between Indoor and Outdoor Unit
 +
|
 +
* The communication cable connection might be loose.
 +
* The communication cable might have failed.
 +
* The connection between the filter board and the outdoor control board might be incorrect or loose.
 +
* The connection between the filter board and the terminal might be incorrect or loose.
 +
* The indoor unit control board might have failed.
 +
* The PFC board might have failed.
 +
* The power board might have failed.
 +
* The outdoor unit control board might have failed.
 +
|-
 +
| 38
 +
| ○
 +
| ★
 +
| ★
 +
| ★
 +
| Check Indoor EEPROM Failure
 +
|
 +
* The EEPROM chip might be loose.
 +
* The indoor control board might have failed.
 +
|-
 +
| 39
 +
| ○
 +
| x
 +
| ★
 +
| ★
 +
| Check Indoor Fan Motor
 +
|
 +
* The indoor fan motor might be obstructed.
 +
* The indoor fan motor cord might be loose.
 +
* The indoor fan motor might have failed.
 +
* The indoor control board might have failed.
 +
|-
 +
| 41
 +
| ★
 +
| ★
 +
| ○
 +
| ★
 +
|  Indoor Board Grounding Failure
 +
|
 +
* Indoor control board has failed.
 
|-
 
|-

Latest revision as of 18:31, 29 April 2019

Note: ★ - Solid light, ○ - Flashing light, x - Light is off

Error Code Indoor PCB LED lights Error Description Troubleshooting
Running Timer Sleep Power
1 2 3 4
EA Display Board and Control Board Communication Error
  • The connection between the display board and control board might be loose.
  • The indoor control board might have failed.
  • The wiring of the display board might be incorrect.
0 Normal Operations
1 x x x Outdoor Coil Temperature Sensor Failure
  • The outdoor coil temperature sensor might be loose.
  • The outdoor coil temperature sensor might have failed.
  • The indoor control board might have failed.
2 x x Compressor Exhaust Temperature Sensor Failure
  • The compressor exhaust temperature sensor might be loose.
  • The compressor exhaust temperature sensor might have failed.
  • The outdoor control board might have failed.
5 x x IPM Module Protection
  • The IPM board might have failed.
  • The outdoor fan might be broken.
  • The outdoor fan motor might have failed.
  • The outdoor fan is being obstructed.
  • The condenser might be dirty.
  • The outdoor unit might not have been installed correctly.
6 x AC Voltage Higher or Lower Protection
  • The supply voltage is higher or lower than normal.
  • The inner supply voltage of the unit is higher or lower than normal.
7 x Communication Failure Between Indoor and Outdoor Units
  • The communication cable connection might be loose.
  • The communication cable might have failed.
  • The connection between the filter board and the outdoor control board might be incorrect or loose.
  • The connection between the filter board and the terminal might be incorrect or loose.
  • The indoor unit control board might have failed.
  • The PFC board might have failed.
  • The power board might have failed.
  • The outdoor unit control board might have failed.
8 Current Overload Protection
  • The fan motor might have run abnormally.
  • The condenser and/or evaporator might be dirty.
  • The air inlet and outlet might be abnormal.
9 x x x Maximum Current Protection
  • The outdoor control board might have short-circuited.
  • The drive board might have short-circuited.
  • Other electrical components might have short-circuited.
10 x x Communication Error Between Outdoor Unit Control Board and Driver Board
  • The connection between control board and driver board might be loose.
  • Either the control or driver board might have failed.
11 x x Check Outdoor EEPROM
  • The EEPROM chip might be loose.
  • The EEPROM chip might be inserted improperly.
  • The EEPROM chip might have failed.
12 x Outdoor Ambient Temperature Too Low Protection
  • Outdoor ambient temperature too low for operation.
13 x x Compressor Exhaust Temperature Too High Protection
  • The compressor exhaust temperature sensor might have failed.
  • The unit has insufficient refrigerant.
14 x Check Outdoor Ambient Temperature Sensor
  • The outdoor ambient temperature sensor's connection might be loose.
  • The outdoor ambient temperature sensor might have failed.
  • The outdoor control board might have failed.
15 x Compressor Shell Temperature Too High Protection
  • The compressor exhaust temperature sensor might be loose.
  • The unit has insufficient refrigerant.
16 Anti-Freeze Protection (Cooling) or Overload Protection (Heating) in Indoor Unit
  • The indoor coil temperature sensor might be loose.
  • The indoor coil temperature sensor might have failed.
  • The indoor control board might have failed.
  • The refrigerant system is abnormal.
17 PFC Protection
  • The PFC might have failed.
  • The outdoor drive board might have failed.
18 DC Compressor Start Failure
  • The outdoor drive board might have failed.
  • The compressor might have failed.
19 x x x Check Compressor Drive
  • The outdoor drive board might have failed.
  • The compressor might have failed.
  • The outdoor control board might have failed.
20 x x Outdoor Fan Motor Locked Rotor Protection
  • The connection of the outdoor fan motor might be loose.
  • There might be something obstructing the outdoor fan motor.
  • The fan motor might have failed.
  • The outdoor control board might have failed.
21 Outdoor Coil Anti-Overload Protection With Cooling
  • There might be too much refrigerant.
  • The outdoor fan motor might have failed.
  • The outdoor fan might be broken.
  • The condensor might be dirty.
  • The air inlet and outlet of the indoor and outdoor unit is abnormal.
22 Compressor Pre-Heating Process
  • This is a normal operation mode in cold weather.
24 Check Outdoor Board Chip
  • The drive board might not be compatible with this unit.
  • The compressor might not be compatible with this unit.
25 Low Frequency Protection
  • When frequency of system is too low, the unit will start self protection, and when working condition comes back, the unit will work again. Usually, after about 3 to 5 mins, the unit will recover or you can power off unit at first, then restart the unit.
26 Protection Against Overheated Outdoor Radiator
  • Radiator sensors might have failed.
  • Detection circuit of the sensor on the control panel might have failed.
27 High Pressure System Protection
  • The pressure switch might have failed.
  • The pressure detection system on the control panel might have failed.
  • The measured value of the system pressure might have exceeded the limit.
33 x x Check Indoor Ambient Temperature Sensor
  • The indoor ambient temperature sensor might be loose.
  • The indoor ambient temperature sensor might have failed.
  • The indoor ambient control board might have failed.
34 x x Check indoor Coil Temperature Sensor
  • The indoor coil temperature sensor might be loose.
  • The indoor coil temperature sensor might have failed.
  • The indoor control board might have failed.
36 x Communication Failure Between Indoor and Outdoor Unit
  • The communication cable connection might be loose.
  • The communication cable might have failed.
  • The connection between the filter board and the outdoor control board might be incorrect or loose.
  • The connection between the filter board and the terminal might be incorrect or loose.
  • The indoor unit control board might have failed.
  • The PFC board might have failed.
  • The power board might have failed.
  • The outdoor unit control board might have failed.
38 Check Indoor EEPROM Failure
  • The EEPROM chip might be loose.
  • The indoor control board might have failed.
39 x Check Indoor Fan Motor
  • The indoor fan motor might be obstructed.
  • The indoor fan motor cord might be loose.
  • The indoor fan motor might have failed.
  • The indoor control board might have failed.
41 Indoor Board Grounding Failure
  • Indoor control board has failed.