| − | '''Note: ★ - Solid | + | '''Note: ★ - Solid light, ○ - Flashing light, ` - Light is off x - Light Flashes every two seconds ''' |
{| class="wikitable" | {| class="wikitable" | ||
| rowspan="2"| Error Code | | rowspan="2"| Error Code | ||
| Line 227: | Line 227: | ||
| | | | ||
* Outdoor ambient temperature too low for operation. | * Outdoor ambient temperature too low for operation. | ||
| + | |- | ||
| + | | | ||
| + | | ○ | ||
| + | | x | ||
| + | | x | ||
| + | | Protection Against Overheated Outdoor Radiator | ||
| + | | | ||
| + | * Radiator sensors might have failed. | ||
| + | * Detection circuit of the sensor on the control panel might have failed. | ||
| + | |- | ||
| + | | | ||
| + | | ○ | ||
| + | | ○ | ||
| + | | x | ||
| + | | High Pressure System Protection | ||
| + | | | ||
| + | * The pressure switch might have failed. | ||
| + | * The pressure detection system on the control panel might have failed. | ||
| + | * The measured value of the system pressure might have exceeded the limit. | ||
Latest revision as of 15:48, 19 April 2017
Note: ★ - Solid light, ○ - Flashing light, ` - Light is off x - Light Flashes every two seconds
| Error Code | Outdoor PCB LED lights | Error Description | Troubleshooting | ||
| LED1 | LED2 | LED3 | |||
| ` | ` | ` | Normal Operation | ||
| ★ | ` | ★ | Check Outdoor Coil Temperature Sensor |
| |
| ★ | ` | ` | Check Compressor Exhaust Temperature Sensor |
| |
| ` | ` | ○ | Communication Failure Between Indoor and Outdoor Unit |
| |
| ★ | ○ | ` | Current Overload Protection |
| |
| ★ | ○ | ★ | Maximum Current Protection |
| |
| ` | ★ | ★ | Communication Error Between Outdoor Unit Control Board and Driver Board |
| |
| ★ | ★ | ★ | Check Outdoor EEPROM |
| |
| ` | ○ | ★ | Compressor Exhaust Temperature Too High Protection |
| |
| ★ | ★ | ` | Check Outdoor Ambient Temperature Sensor |
| |
| ` | ★ | ○ | Compressor Shell Temperature Too High Protection |
| |
| ` | ○ | ○ | Anti-Freeze Protection (Cooling) or Overload Protection (Heating) in Indoor Unit |
| |
| ○ | ` | ○ | Check Compressor Drive |
| |
| ○ | ○ | ★ | Outdoor Fan Motor Locked Rotor Protection |
| |
| ` | ★ | ` | Outdoor Coil Anti-Overload Protection With Cooling |
| |
| ` | ○ | ` | IPM Module Protection |
| |
| ○ | ` | ` | PFC Protection |
| |
| ○ | ★ | ○ | Compressor Pre-Heating Process |
| |
| ★ | ` | ○ | Check Outdoor Board Chip |
| |
| ★ | ★ | ○ | AC Voltage Higher or Lower Protection |
| |
| ○ | ○ | ` | DC Compressor Start Failure |
| |
| ★ | ○ | ○ | Outdoor Ambient Temperature Too Low Protection |
| |
| ○ | x | x | Protection Against Overheated Outdoor Radiator |
| |
| ○ | ○ | x | High Pressure System Protection |
|
|