− | '''Note: ★ - Solid | + | '''Note: ★ - Solid light, ○ - Flashing light, ` - Light is off x - Light Flashes every two seconds ''' |
{| class="wikitable" | {| class="wikitable" | ||
| rowspan="2"| Error Code | | rowspan="2"| Error Code | ||
Line 27: | Line 27: | ||
* The outdoor unit's main control board might have failed. | * The outdoor unit's main control board might have failed. | ||
|- | |- | ||
+ | | | ||
+ | | ★ | ||
+ | | ` | ||
+ | | ` | ||
+ | | Check Compressor Exhaust Temperature Sensor | ||
+ | | | ||
+ | * The compressor exhaust temperature sensor might be loose. | ||
+ | * The compressor exhaust temperature sensor might have failed. | ||
+ | * The outdoor unit's main control board might have failed. | ||
+ | |- | ||
+ | | | ||
+ | | ` | ||
+ | | ` | ||
+ | | ○ | ||
+ | | Communication Failure Between Indoor and Outdoor Unit | ||
+ | | | ||
+ | * The communication cable connection might be loose. | ||
+ | * The communication cable might have failed. | ||
+ | * The connection between the filter board and the outdoor control board might be incorrect or loose. | ||
+ | * The connection between the filter board and the terminal might be incorrect or loose. | ||
+ | * The indoor unit control board might have failed. | ||
+ | * The PFC board might have failed. | ||
+ | * The power board might have failed. | ||
+ | * The outdoor unit control board might have failed. | ||
+ | |- | ||
+ | | | ||
+ | | ★ | ||
+ | | ○ | ||
+ | | ` | ||
+ | | Current Overload Protection | ||
+ | | | ||
+ | * The fan motor might have run abnormally. | ||
+ | * The condenser and/or evaporator might be dirty. | ||
+ | * The air inlet and outlet might be abnormal. | ||
+ | |- | ||
+ | | | ||
+ | | ★ | ||
+ | | ○ | ||
+ | | ★ | ||
+ | | Maximum Current Protection | ||
+ | | | ||
+ | * The outdoor control board might have short-circuited. | ||
+ | * The drive board might have short-circuited. | ||
+ | * Other electrical components might have short-circuited. | ||
+ | |- | ||
+ | | | ||
+ | | ` | ||
+ | | ★ | ||
+ | | ★ | ||
+ | | Communication Error Between Outdoor Unit Control Board and Driver Board | ||
+ | | | ||
+ | * The connection between control board and driver board might be loose. | ||
+ | * Either the control or driver board might have failed. | ||
+ | |- | ||
+ | | | ||
+ | | ★ | ||
+ | | ★ | ||
+ | | ★ | ||
+ | | Check Outdoor EEPROM | ||
+ | | | ||
+ | * The EEPROM chip might be loose. | ||
+ | * The EEPROM chip might be inserted improperly. | ||
+ | * The EEPROM chip might have failed. | ||
+ | |- | ||
+ | | | ||
+ | | ` | ||
+ | | ○ | ||
+ | | ★ | ||
+ | | Compressor Exhaust Temperature Too High Protection | ||
+ | | | ||
+ | * The compressor exhaust temperature sensor might have failed. | ||
+ | * The unit has insufficient refrigerant. | ||
+ | |- | ||
+ | | | ||
+ | | ★ | ||
+ | | ★ | ||
+ | | ` | ||
+ | | Check Outdoor Ambient Temperature Sensor | ||
+ | | | ||
+ | * The outdoor ambient temperature sensor's connection might be loose. | ||
+ | * The outdoor ambient temperature sensor might have failed. | ||
+ | * The outdoor control board might have failed. | ||
+ | |- | ||
+ | | | ||
+ | | ` | ||
+ | | ★ | ||
+ | | ○ | ||
+ | | Compressor Shell Temperature Too High Protection | ||
+ | | | ||
+ | * The compressor exhaust temperature sensor might be loose. | ||
+ | * The unit has insufficient refrigerant. | ||
+ | |- | ||
+ | | | ||
+ | | ` | ||
+ | | ○ | ||
+ | | ○ | ||
+ | | Anti-Freeze Protection (Cooling) or Overload Protection (Heating) in Indoor Unit | ||
+ | | | ||
+ | * The indoor coil temperature sensor might be loose. | ||
+ | * The indoor coil temperature sensor might have failed. | ||
+ | * The indoor control board might have failed. | ||
+ | * The refrigerant system is abnormal. | ||
+ | |- | ||
+ | | | ||
+ | | ○ | ||
+ | | ` | ||
+ | | ○ | ||
+ | | Check Compressor Drive | ||
+ | | | ||
+ | * The outdoor drive board might have failed. | ||
+ | * The compressor might have failed. | ||
+ | * The outdoor control board might have failed. | ||
+ | |- | ||
+ | | | ||
+ | | ○ | ||
+ | | ○ | ||
+ | | ★ | ||
+ | | Outdoor Fan Motor Locked Rotor Protection | ||
+ | | | ||
+ | * The connection of the outdoor fan motor might be loose. | ||
+ | * There might be something obstructing the outdoor fan motor. | ||
+ | * The fan motor might have failed. | ||
+ | * The outdoor control board might have failed. | ||
+ | |- | ||
+ | | | ||
+ | | ` | ||
+ | | ★ | ||
+ | | ` | ||
+ | | Outdoor Coil Anti-Overload Protection With Cooling | ||
+ | | | ||
+ | * There might be too much refrigerant. | ||
+ | * The outdoor fan motor might have failed. | ||
+ | * The outdoor fan might be broken. | ||
+ | * The condensor might be dirty. | ||
+ | * The air inlet and outlet of the indoor and outdoor unit is abnormal. | ||
+ | |- | ||
+ | | | ||
+ | | ` | ||
+ | | ○ | ||
+ | | ` | ||
+ | | IPM Module Protection | ||
+ | | | ||
+ | * The IPM board might have failed. | ||
+ | * The outdoor fan might be broken. | ||
+ | * The outdoor fan motor might have failed. | ||
+ | * The outdoor fan might be obstructed. | ||
+ | * The condenser might be dirty. | ||
+ | * The outdoor unit might have been installed incorrectly. | ||
+ | |- | ||
+ | | | ||
+ | | ○ | ||
+ | | ` | ||
+ | | ` | ||
+ | | PFC Protection | ||
+ | | | ||
+ | * The PFC might have failed. | ||
+ | * The outdoor drive board might have failed. | ||
+ | |- | ||
+ | | | ||
+ | | ○ | ||
+ | | ★ | ||
+ | | ○ | ||
+ | | Compressor Pre-Heating Process | ||
+ | | | ||
+ | * This is a normal operation mode in cold weather. | ||
+ | |- | ||
+ | | | ||
+ | | ★ | ||
+ | | ` | ||
+ | | ○ | ||
+ | | Check Outdoor Board Chip | ||
+ | | | ||
+ | * The drive board might not be compatible with this unit. | ||
+ | * The compressor might not be compatible with this unit. | ||
+ | |- | ||
+ | | | ||
+ | | ★ | ||
+ | | ★ | ||
+ | | ○ | ||
+ | | AC Voltage Higher or Lower Protection | ||
+ | | | ||
+ | * The supply voltage is higher or lower than normal. | ||
+ | * The inner supply voltage of the unit is higher or lower than normal. | ||
+ | |- | ||
+ | | | ||
+ | | ○ | ||
+ | | ○ | ||
+ | | ` | ||
+ | | DC Compressor Start Failure | ||
+ | | | ||
+ | * The outdoor drive board might have failed. | ||
+ | * The compressor might have failed. | ||
+ | |- | ||
+ | | | ||
+ | | ★ | ||
+ | | ○ | ||
+ | | ○ | ||
+ | | Outdoor Ambient Temperature Too Low Protection | ||
+ | | | ||
+ | * Outdoor ambient temperature too low for operation. | ||
+ | |- | ||
+ | | | ||
+ | | ○ | ||
+ | | x | ||
+ | | x | ||
+ | | Protection Against Overheated Outdoor Radiator | ||
+ | | | ||
+ | * Radiator sensors might have failed. | ||
+ | * Detection circuit of the sensor on the control panel might have failed. | ||
+ | |- | ||
+ | | | ||
+ | | ○ | ||
+ | | ○ | ||
+ | | x | ||
+ | | High Pressure System Protection | ||
+ | | | ||
+ | * The pressure switch might have failed. | ||
+ | * The pressure detection system on the control panel might have failed. | ||
+ | * The measured value of the system pressure might have exceeded the limit. |
Latest revision as of 15:48, 19 April 2017
Note: ★ - Solid light, ○ - Flashing light, ` - Light is off x - Light Flashes every two seconds
Error Code | Outdoor PCB LED lights | Error Description | Troubleshooting | ||
LED1 | LED2 | LED3 | |||
` | ` | ` | Normal Operation | ||
★ | ` | ★ | Check Outdoor Coil Temperature Sensor |
| |
★ | ` | ` | Check Compressor Exhaust Temperature Sensor |
| |
` | ` | ○ | Communication Failure Between Indoor and Outdoor Unit |
| |
★ | ○ | ` | Current Overload Protection |
| |
★ | ○ | ★ | Maximum Current Protection |
| |
` | ★ | ★ | Communication Error Between Outdoor Unit Control Board and Driver Board |
| |
★ | ★ | ★ | Check Outdoor EEPROM |
| |
` | ○ | ★ | Compressor Exhaust Temperature Too High Protection |
| |
★ | ★ | ` | Check Outdoor Ambient Temperature Sensor |
| |
` | ★ | ○ | Compressor Shell Temperature Too High Protection |
| |
` | ○ | ○ | Anti-Freeze Protection (Cooling) or Overload Protection (Heating) in Indoor Unit |
| |
○ | ` | ○ | Check Compressor Drive |
| |
○ | ○ | ★ | Outdoor Fan Motor Locked Rotor Protection |
| |
` | ★ | ` | Outdoor Coil Anti-Overload Protection With Cooling |
| |
` | ○ | ` | IPM Module Protection |
| |
○ | ` | ` | PFC Protection |
| |
○ | ★ | ○ | Compressor Pre-Heating Process |
| |
★ | ` | ○ | Check Outdoor Board Chip |
| |
★ | ★ | ○ | AC Voltage Higher or Lower Protection |
| |
○ | ○ | ` | DC Compressor Start Failure |
| |
★ | ○ | ○ | Outdoor Ambient Temperature Too Low Protection |
| |
○ | x | x | Protection Against Overheated Outdoor Radiator |
| |
○ | ○ | x | High Pressure System Protection |
|